Simulation for level
Enter the level value to be simulated. The appropriate current is given by the
electronic insert.
Step
Entry Cursor in Display at
Significance
1 3
SERVICE/SIMULATION
Service/Simulation
2
6
SIM. LEVEL
Simulation for level
e.g. 77.06
Actual measured value is displayed
3
e.g. 35.00
35.00
Level to be simulated is entered
4 F4
[ENTER]
Confirms entry, value to be transmitted
Simulation for volume
Enter the volume value to be simulated. The appropriate current is given by the
electronic insert.
Step
Entry Cursor in Display to
Significance
1 3
SERVICE/SIMULATION
Service/Simulation
2
7
SIM. VOLUME
Simulation of volume
e.g. 77.06
Actual measured value is displayed
3
e.g. 5.00
5.00
Volume to be simulated is entered
4 F4
[ENTER]
Confirms entry, value to be transmitted
Simulation for current
Enter directly the current value to be simulated.
Step
Entry Cursor in Display at
Significance
1 3
SERVICE/SIMULATION
Service/Simulation
2
7
SIM. CURRENT
Simulation of current output
e.g. 17.02
Actual measured value is displayed
3
e.g. 8.00
8.00
Current to be simulated is entered
4 F4
[ENTER]
Confirms entry, value to be transmitted
Note!
The values entered during simulation are stored until simulation is again switched off.
Note!
6 Diagnosis and Troubleshooting
Electronic insert FEC 12 (HART)
16