EngyVolt RV15
Operation
17
5
Operation
5.1
Display
The display screen is used in 2 operating modes:
• Display mode (
17) to display measured values
• Configuration mode (
17) of the multifunction electrical energy meter. The possible settings
are described in the "Commissioning" section (
5.2
Operating elements
You can directly access various measured values via the 4 keys on the front of the multifunction
electrical energy meter. The keys are used to configure the device in the configuration mode.
A0016376
Is used to display voltage and frequency. This is the "Back" function in the configuration mode.
A0016377
Is used to display the currents. This is the "Up" function in the configuration mode.
A0016379
Is used to display the power values and the power factor. This is the "Down" function in the
configuration mode.
A0016378
Is used to display the energy values. This is the "Enter" function in the configuration mode.
5.3
Display mode
The measured values are shown on the backlit liquid crystal display.
Order in which measured values are displayed in the display mode
Key
View No. Description
3-phase, 4-wire
View No. Description
3-phase, 3-wire
View No. Single-phase, 2-wire
A0016376
1
V L1-N (voltage L1/N)
V L2-N (voltage L2/N)
V L3-N (voltage L3/N)
1
V L1-L2 (voltage L1/L2)
V L2-L3 (voltage L2/L3)
V L3-L1 (voltage L3/L1)
1
V L1 (voltage L1)
2
V L1-L2 (voltage L1/L2)
V L2-L3 (voltage L2/L3)
V L3-L1 (voltage L3/L1)
3
Frequency
2
Frequency
2
Frequency
4
V L1-N %THD*
(%THD voltage L1/N)
V L2-N %THD*
(%THD voltage L2/N)
V L3-N %THD*
(%THD voltage L3/N)
5
V L1-L2 %THD*
(%THD voltage L1/L2)
V L2-L3 %THD*
(%THD voltage L2/L3)
V L3-L1 %THD*
(%THD voltage L3/L1)
3
V L1-L2 %THD*
(%THD voltage L1/L2)
V L2-L3 %THD*
(%THD voltage L2/L3)
V L3-L1 %THD*
(%THD voltage L3/L1)
3
V L1 %THD*
*) %THD = % Total Harmonic Distortion