Ecograph T, RSG35
Technical data
Hauser
71
15.5 Performance characteristics
Response time
Input
Output
Time [ms]
Current, voltage, pulse
Relay
≤ 550
RTD
Relay
≤ 1150
TC
Relay
≤ 1550
Cable open circuit detection, current input
Relay
≤ 1150
Sensor error RTD, TC
Relay
≤ 5000
Digital input
Relay
≤ 350
1)
If internal measuring point temperature compensation is used, otherwise values as for voltage
Reference operating
conditions
Reference temperature
25 °C (77 °F) ±5 K
Warm-up period
120 min.
Humidity
20 to 60 % rel. humidity
Hysteresis
Can be configured for limit values in the setup
Long-term drift
As per IEC 61298-2: max. ±0.1%/year (of measuring range)
15.6 Installation
Mounting location and
installation dimensions
The device is designed for use in a panel in non-hazardous areas.