3. Connection between Eco- / Memograph and the COM-Server 

 
 
3.1. Connection to RS232 interface 

 
Connect the COM-Server with RS232 interface to the unit with a not crossed cable. 
It is included in delivery of  RSG10(20)A-E2 and RSG10(20)-E3. 
For W+T 58631 please ensure, that switch 8 of the internal switch is set to 

ON

  

(default factory setting). 
 

 

 
3.2. Connection to RS485 interface 

 
 
 

COM-Server RS485

  

      

Memograph         Ecograph

 

 

 

 

 

 

 

 

 

 

 

 

           1                                                     8  

 

8

 

 

           2 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

           6                                                      3 

 

           7 
            

 

Set the mode of the COM-Server via internal switches to 

2-wire automatic control

 

   

SW1 SW2 SW3 SW4  SW5 SW6 SW7  SW8
ON 

ON 

OFF  OFF  ON 

   x 

   x 

OFF 

 

 
All RS485 modes require a termination network on the bus ssytem which ensures a defined rest 
state in the high-ohmic phases of bus operation. Connection of the bus system with a 
termination network can be done in the interface by closing the DIP switches 6 and 7 in the 
COM-Server. 
 

 
 
 

4. Setting in ReadWin 2000 
 

It is only necessary to set the IP address in the unit settings. The port address normally is 
8000. 