Seite 7/7
3. Connection between Eco- / Memograph and the COM-Server
3.1. Connection to RS232 interface
Connect the COM-Server with RS232 interface to the unit with a not crossed cable.
It is included in delivery of RSG10(20)A-E2 and RSG10(20)-E3.
For W+T 58631 please ensure, that switch 8 of the internal switch is set to
ON
(default factory setting).
3.2. Connection to RS485 interface
COM-Server RS485
Memograph Ecograph
1 8
8
2
6 3
9
7
Set the mode of the COM-Server via internal switches to
2-wire automatic control
:
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
ON
ON
OFF OFF ON
x
x
OFF
All RS485 modes require a termination network on the bus ssytem which ensures a defined rest
state in the high-ohmic phases of bus operation. Connection of the bus system with a
termination network can be done in the interface by closing the DIP switches 6 and 7 in the
COM-Server.
4. Setting in ReadWin 2000
-
It is only necessary to set the IP address in the unit settings. The port address normally is
8000.