6.3
Commissioning with an operating menu
Commissioning comprises the following steps:
1.
Function check (
2.
Selecting the language, measuring mode and pressure unit (
55)
3.
Position adjustment (
4.
Configuring measurement:
– Pressure measurement (
– Level measurement (
6.3.1
Selecting the language, measuring mode and pressure unit
Language selection
Measuring mode selection
Pressure unit selection
Parameter name
Description
Language (000)
Selection
Menu path:
Main menu
Language
Select the menu language for the local display.
Options:
• English
• Another language (as selected when ordering the device)
• Possibly a third language (language of the manufacturing plant)
Factory setting
:
English
Parameter name
Description
Measuring mode (005)
Selection
Menu path: Setup
Measuring mode
Select the measuring mode.
The operating menu is structured differently depending on the measuring mode selected.
!
Note!
If the measuring mode is changed, no conversion takes place. If necessary, the device has
to be recalibrated after the measuring mode has been changed.
Options:
• Pressure
• Level
• Flow
Factory setting:
Pressure
Parameter name
Description
Press. eng. unit (125)
Selection
Menu path: Setup
Press. eng. unit
Select the pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O
• ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
2
Factory setting:
mbar or bar depending on the sensor nominal measuring range, or as per order
specifications