Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
84
Hauser
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST.
UNIT FACT. H.
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and Mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
See also
CUSTOMER UNIT H.
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and Mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m (1,6 ft)
i
1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select the volume unit for the 2nd measured value.
Prerequisite:
• COMB. MEASURAND = Height and Volume or %-Height and Volume
Options:
• l
• hl
• cm
3
• dm
3
• m
3
• m
3
E
3
• ft
• ft
3
E
3
• gal
• Igal
• bbl
• User unit,
see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m
3
Table 13: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description