Commissioning
Deltabar PMD55B HART
18
Hauser
1
4 5 6 7 8
2
3
A0047143
4
Segment display
1
Measured value
2
Bar graph proportional to the current output
3
Unit of measured value
4
Locked (symbol appears when the device is locked)
5
Bluetooth (symbol flashes if Bluetooth connection is active)
6
HART communication (symbol is displayed if HART communication is active)
7
Square root extraction (appears if a square root extraction of the measured value is output)
8
Measured value output in %
8
Commissioning
8.1
Preliminaries
The measuring range and the unit in which the measured value is transmitted correspond to
the data on the nameplate.
L
WARNING
The settings of the current output are relevant for safety!
This situation can result in product overflow.
‣
The setting of the current output depends on the setting in the
Assign PV
parameter.
‣
After changing the
Assign PV
parameter, check the settings for the range (LRV and URV)
and reconfigure them if necessary.
L
WARNING
Process pressure above or below permitted maximum/minimum!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
‣
If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, a message is output.
‣
Only use the device within the measuring range limits!