Description of device parameters
Deltabar FMD72
78
Note
• In the case of wet calibration, the level (container full) must actually be available. The associated
pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (container full) does not have to be available. The associated
pressure has to be entered in the "Full Pressure" parameter for the "In pressure" level selection.
The associated height has to be entered in the "Full height" parameter for the "In height" level
selection.
Factory setting
100,0
Set LRV (013, 056, 166, 168)
Navigation
Setup
®
Set LRV (013, 056, 166, 168)
Setup
®
Advanced Setup
®
Current Output
®
Set LRV (013, 056, 166, 168)
Write permission
Operators/Service engineers/Expert
Description
Set the pressure value, level or content for the lower current value (4 mA).
Factory setting
• 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Set URV (014, 057, 167, 169)
Navigation
Setup
®
Set URV (014, 057, 167, 169)
Setup
®
Advanced Setup
®
Current output
®
Set URV (014, 057, 167, 169)
Write permission
Operators/Service engineers/Expert
Description
Set the pressure value, level or content for the upper current value (20 mA).
Factory setting
• 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Get LRV (015)
Navigation
Setup
®
Advanced Setup
®
Current Output
®
Get LRV (015)
Write permission
Operators/Service engineers/Expert
Description
Setting lower range value. The pressure for the lower current value (4 mA) is present at the device.
Use the "Confirm" option to assign the lower current value to the applied pressure value.
Prerequisite
Pressure measuring mode
Options
• Cancel
• Confirm