Description of device parameters
Deltabar FMD71, FMD72
26
Factory setting
• 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Get LRV (015)
Navigation
Expert → Output → Current Output → Get LRV (015)
Write permission
Operators/Service engineers/Expert
Description
Setting lower range value. The pressure for the lower current value (4 mA) is present at
the device. Use the "Confirm" option to assign the lower current value to the applied
pressure value.
Prerequisite
Pressure measuring mode
Options
• Cancel
• Confirm
Factory setting
Cancel
Get URV (016)
Navigation
Expert → Output → Current Output → Get URV (016)
Write permission
Operators/Service engineers/Expert
Description
Setting upper range value. The pressure for the upper current value (20 mA) is present at
the device. Use the "Confirm" option to assign the applied pressure value to the upper
current value.
Prerequisite
Pressure measuring mode
Options
• Cancel
• Confirm
Factory setting
Cancel
Damping (017)/(184)
Navigation
Expert → Measurement → Basic Setup → Damping (017)/(184)
Write permission
Operators/Service engineers/Expert
(if the "Damping" DIP switch is set to "on")