Operation with an operating menu
Deltabar FMD71, FMD72
14
Any customer-specific configuration carried out at the factory is not affected by a
reset (customer-specific configuration remains). If you want to change the customer-
specific configuration carried out at the factory, please contact Hauser
Service.
Reset code
Description and effect
62
PowerUp reset (warm start)
• The device is restarted.
• Data is read back anew from the EEPROM (process is reinitialized).
• Any simulation which may be running is ended.
333
User reset
• This code resets all the parameters apart from:
- Device tag (022)
- Linearization table
- Operating hours (162)
- Event logbook
- Curr. trim 4 mA (135)
- Curr. trim 20 mA (136)
- Lo trim sensor (131)
- Hi trim sensor (132)
- Lo trim sensor (277)
- Hi trim sensor (278)
• Any simulation which may be running is ended.
• The device is restarted.
7864
Total reset
• This code resets all the parameters apart from:
- Operating hours (162)
- Event logbook
- Lo trim sensor (131)
- Hi trim sensor (132)
- Lo trim sensor (277)
- Hi trim sensor (278)
• Any simulation which may be running is ended.
• The device is restarted.
1)
To be entered in "System" → "Management" → "Reset" (124)
After a "Total reset" in FieldCare you have to press the "refresh" button in order to
ensure that the measuring units are also reset.
Summary of Contents for Deltabar FMD71
Page 2: ......