Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Description of device parameters
Hauser
57
Navigation
Display: DIAG → SM1 → Simulation Switch Output (OU1)
IO-Link: Diagnosis → Simulation Switch Output (OU1)
Description
When IO-Link communication is active, the simulation affects the process data only.
It does not affect the physical switch output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A visual warning is indicated on the local display
(C485 - Simulation active) and a warning is communicated via IO-Link (C485 - Simulation
active). The simulation must be ended actively via the menu. If the device is disconnected
from the power supply during the simulation and power is then resupplied, the simulation
mode is not resumed, and instead the device continues operation in the measuring mode.
Options
• OFF
• OPN (switch output open)
• CLS (switch output closed)
Simulation Current Output (OU2)
Navigation
Display: Diag → SM2 → Simulation Current Output (OU2)
IO-Link: Diagnosis → Simulation Current Output (OU2)
Description
Simulation affects the process data and the physical current output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A warning is communicated via IO-Link (C485 -
simulation active). The simulation must be ended actively via the menu. If the device is
disconnected from the power supply during the simulation and then power is resupplied
afterwards, the simulation mode is not resumed, and instead the device continues
operation in the measuring mode.
Options
• OFF
• 3.5 mA
• 4 mA
• 8 mA
• 12 mA
• 16 mA
• 20 mA
• 21.95 mA
Device Search
Navigation
IO-Link: Diagnosis → Device Search
Description
This parameter is used to uniquely identify the device during installation. The green LED is
lit (= operational) on the device and starts to flash with increased luminosity.
Options
• OFF
• ON
Factory setting
OFF