SET
SET
ENDA
OUT
°F
°C
ALR
ET141
2
A.Lol
min = 0,1°C, max = 60°C
A.uPL
A.Lol
min = -60°C, max = 60°C
A.uPL
A.Lol
min = -60°C, max = 150°C
A.uPL
o.HYS
Output hysteresis
o.PPn
On time for the output in the case of probe failure.
o.PPF
Off time for the output in the case of probe failure.
Unit
dres
Temperature unit.
C.tyP
Control mode (
Heat
= Heating control ,
Cool
=Cooling control.)
1.0
°C
°F
°C
°C
2
20.0
0
255
Min.
0
0
255
Min.
1
Heat
Cool
Heat
no
yes
no
Menu of Congiguration
Cn
PARAMETER TABLE
-60.0
-20.0
o.LoL
150.0
MIN
UNIT
MAX
DEFAULT
SET
o.uPL
-60
°C
°C
150
°C
0
20.0
Menu of Output control parameters
o.LoL
o.uPL
o.oFF
The lower limit of the setpoint
The upper limit of the setpoint
The offset value for the output
ou
ou
Çýkýþ kontrol parametreleri menüsü
ou
Menu of Alarm control parameters
AL
A. ou
-
A.ou.S.
Security parameter for menu of output control
= Menu is invisible.
NonE
P.yes
P.no
= Parameters of menu are changeable.
= Parameters of menu are only visible.
= Setpoint value is changeable.
= Setpoint value is only visible.
P.yes
P.no
Security parameter for output setpoint value
Menu of Parameter security
SE
A. Cn
-
Security parameter for menu of configuration
Security parameter for menu of alarm
A. AL
-
in.AL
20.0
°C
2
in.AL
bo.AL
A.HYs
A.typ
Alarm hysteresis value.(*)
Alarm type.
0.1
(*)
alarm set value.
If one of the band alarm types are selected, alarm hysteresis value should not be greater than
(
No
= no decimal point.
22
Decimal place
yes
= with decimal point.
22.3
°C )
°C
°C
A.LoL
A.uPl
The lower limit of Alarm sepoint.
The upper limit of Alarm sepoint.
A.uPL
A.lol
(**)
(**)
°C
°C
-60
150
(**)
Min. value of
parameter and max. value of
A.uPL
parameter are at the alarm types diagram.
A.LoL
Alarm type
A.upL
Alarm hysteresis
value.
A.Lol
A.typ
A.Hys
The upper limit of
Alarm setpoint.
The lower limit of
Alarm setpoint.
ET
1
412-E-07
2/2
Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode
.
When held down for a
few seconds, the change rate accelerates.
Used for selecting parameters and decreasing the setp
oint value
in the programming mode and for decreasing the setpoint value in the run mode
.
When held down for a few
seconds, the change rate accelerates.
OUT
LED
FAHRENHEIT
LED
Displayed process value in the run mode, parameter name or value in programming mode.
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding key, setpoint value of the
selected parameter appears and by using and keys the value can be adjusted.
The lower limit
of the setpoint.
Programming Mode
Run Mode
o.lol
The offset value
for the output
o.off
Output
hysteresis
o.Hys
T
he upper limit
of the setpoint.
o.uPl
If both keys are pressed,
run mode is entered.
ou
o.PPF
o.PPn
On time for the output
in the case of
probe failure.
Off time for the output
in the case of
probe failure.
Security parameter
for configuration menu
A.
-
Cn
Security parameter
for alarm menu
A.
-
AL
A.
-
ou
Security parameter
for output menu
S.Cod
Access code for
security menu.
This parameter should be
321
.
Se
AL
Control mode
C.typ
Decimal place
Unit
Cn
Temperature unit
dres
Security parameter
for output setpoint value
A.ou.S.
Pfa
Means, thermostat probe is short circuit.
Psc
Means, thermostat probe is broken.
Error Messages
Pfa
PsC
Temperature value is higher than the scale.
Temperature value is lower than the scale.
ALARM
LED
A.Set
A.Set
A.Hys
A.Hys
Alarm
on
Alarm
off
Alarm
on
Alarm
off
Alarm
on
Alarm Output Types
- °C
- °C
- °C
+ °C
+ °C
+ °C
-60
Alarm
off
Alarm
on
Alarm
off
- °C
+ °C
-60
+60
+60
ATyP
In.AL
=
(Independent alarm is
actived below the setpoint)
Alarm
off
- °C
+ °C
-60
+60
ATyP
de.AL
=
(Deviation alarm is
actived below the setpoint)
ATyP
In.AH
=
(Independent alarm is
actived above the setpoint)
A.Hys
ATP DAH
=
Alarm
on
- °C
+ °C
-60
+60
(Sapma alarmý, set
deðerinin üstünde aktif)
ATyP
de.AH
=
(Deviation alarm is
actived above the setpoint)
A.Hys
(Alarm is actived
inside the band)
ATyP
bi.AL
=
A.Hys
A.Hys
(
outside the band)
Alarm is actived
ATyP
bo.AL
=
A.Hys
A.Hys
o.Set
+
A.Set
o.Set
o.Set
+
A.Set
o.Set
-
A.Set
o.Set
o.Set
+
A.Set
o.Set
o.Set
+
A.Set
o.Set
-
A.Set
o.Set
Process
Value
30.0
o.Set
A.Set
30.0
25.0
If key is pressed,
o.SEt
(Output setpoint value) and
A.set
(Alarm setpoint value) parameters appear.
While holding key
o.set
value appears and by using and keys the value can be adjusted between
o.lol
and
o.upl
values.
While holding key
A.set
value appears and by using and keys the value can be adjusted according to
A.typ
parameter which is specified table of alarm output types.
If both keys are pressed and held for 3 seconds,
programming mode is entered.
A.Lol
min = 0,1°C, max = 60°C
A.uPL
A.Lol
min = -60°C,
max = 60°C
A.uPL
A.Lol
min = -60°C, max = 150°C
A.uPL
SET
SET
SET
SET
SET