7.4.
Electrical Installation:
Step 1:
Air Conditioning Unit wiring:
Check the wiring of the label after removing the cover, including the power line (G,
N, L) fan signal line 0-10v (Y,0)
Step 2:
Main Power Supply Connection:
Connect main Power Supply connection to the power distribution unit at the rear
port for the main power, as shown below.
Figure 7.4-1: 63A Rack Mounted Distribution Unit
7.5.
Electronic Parameters
Model AOIB
ECX-AOIB-3K50-42U
Indoor Unit
Full Load Current
63A
Cable Advice
10 mm
2
Breaker Advice
D63
Table 7.5-1: Electrical Parameters
Notice:
1.
All the connections of the electrical supply circuit, control line, and ground electrode
must conform to the local laws and regulations.
2.
For the full-load current of unit please refer to the unit nameplate. The size of the
supply cable should conform to the electrical standards and regulations.
3.
Electrical and Electronic Installation must be installed and carried out by a
professional Installer.
18