ENCON 3661 Installation, Operation And Maintenance Manual Download Page 5

Doc. No: 01999901 

Revision: A 

4 of 10

 

Issue Date: 08/15/21

 

TROUBLESHOOTING 

SYMPTOM 

PROBLEM 

SOLUTION 

 

Heater and Pump not working 

 
1) 

No power to the unit. 

 
 
 
 
 
 
 
 
 

2) 

Float 1-FS not working. 

3) 

Float switch device stuck in 
down position. 

4) 

Float switch is defective. 

 
 

5) 

Foam  float  is  in  the  wrong 
orientation. 

 
1) 

Check the following: 
a)  Main  power  source  and  correct  voltage  is 

applied. 

b)  Disconnect  switch  is  in  the  “ON”  position 

and fuses are not blown. 

c)  Inspect  terminals  TB1  and  TB2.  Electrical 

termination  should  be  tight,  free  of  oxide 
build-up, and wiring is per wiring diagram. 

d) Relay 1-CR using a voltmeter at Terminal 5 

to TB2. Replace relay, if not energized. 

2) 

Check water level in tank. 

3) 

Clean  float  switch  device.  See  Operation  & 
Maintenance section for instructions. 

4) 

Check  by  moving  float  full  stroke  to  see  if 

power is restored to components. Remove and 
replace float switch, if defective. 

5) 

Turn  foam  float  around;  must  be  orientated 

downward.  

NOTE:

 Long term cleaning and main-tenance 

schedules must be performed. See Operation 
& Maintenance section. 

 

Pump working; Heater not working 

 
1) 

Thermostat assembly (1-
TAS or 2-TAS) is defective. 

 
 

2) 

Heater contactor 1-CON is 
defective. 

 

3) 

Heater 

coil 

1-HTR 

is 

defective. 

 
 

 
1) 

Check  water  temperature  is  below  70

°

F.  1-

TAS shuts off heater when water temperature 
is  over  85

°

F.  Remove  and  replace  defective 

thermostat. 

2) 

1-CON  must  be  energized.  Check  using 
voltmeter  at  Terminals  3  &  5.  Replace 
contactor, if not energized. 

3) 

Check  heater  terminals.  Electrical  terminals 
should be tight, free of oxide build-up. 1-HTR 
must be energized. Check using voltmeter at 
TB5  to  2W3.  Replace  heater,  if  all  terminals 
are confirmed and not energized. 

 

Pump not working; Heater working 

 
1) 

Pump is defective. 

 
 

2) 

Pump impeller is jammed. 

 

3) 

Pump is damaged. 

 

 
1) 

1-MTR  must  be  energized.  Check  using 
voltmeter at TB6 to 2W5. Replace pump, if not 
energized. 

2) 

Clean  pump.  See  Operation  &  Maintenance 
section for instructions. 

3) 

Remove and replace pump. 

NOTE:

 Long term cleaning and maintenance 

schedules must be performed. See Operation 
& Maintenance section. 

 

Pump volume low 

 

Pump impeller is dirty. 

 

Clean  pump.  See  Operation  &  Maintenance 
section for instructions. 

NOTE:

  Long  term  cleaning  and  maintenance 

schedules must be performed. See Operation & 
Maintenance section. 

 

Tank Dirty 

 

Proper  maintenance  schedule 
not performed. 

 

Drain  and  clean  tank.  See  Operation  & 
Maintenance section for instructions. 

NOTE

:  Recommended  cleaning  and  main-

tenance  schedule  of  tank  is  every  60  days 
minimum  and  not  to  exceed  180  days.  More 
often if conditions warrants. 

 

Contactor chatter 
Relay chatter 

 

Defective contactor or relay. 

 

Replace contactor or relay. 

Summary of Contents for 3661

Page 1: ...SAF T TUB JUMP TANK MODEL 01052539 S N 3661 INSTALLATION OPERATION AND MAINTENANCE MANUAL 01999901 Revision A 08 15 2021 ...

Page 2: ...TURE Maintains 70 85 F through use of a 1 5 KW two thermostats and level switch control circuit ELECTRICAL REQUIREMENT 13 1 amp 120 volt circuit GFCI 30mA EPD type circuit protector is required by others ELECTRICAL CLASSIFICATION NEMA 4 and Class 1 Div 2 Group D models are available WEIGHT 175 lbs tare 1545 lbs full DIMENSIONS Overall 78 L x 35 D x 40 W Inside Tank 71 1 2 L x 28 3 4 D x 27 W CONST...

Page 3: ...re the unit is being controlled properly and no visible leaks are present POWER ON and PUMP ON indicator lights should be illuminated NOTE If water temperature is below 70 F the HEATER ON indicator light should be illuminated See Junction Box Detail drawing attached OPERATION MAINTENANCE WARNING WARNING WARNING PROPER PERSONAL CARE SHOULD BE TAKEN TO AVOID BURNS AND ELECTRIC SHOCK DISCONNECT POWER...

Page 4: ...Locate pump clamp and remove clamp using a flat head screwdriver d Remove pump from instrumentation compartment and disassemble for cleaning Refer to Figure 1 e Remove the screen intake 2 and volute plate 3 f Carefully remove the o ring 4 Caution should be taken to avoid damage to o ring g Lightly clean any corrosion or debris which may clog the impeller 5 h Use a brush and penetrating oil and lig...

Page 5: ... water temperature is below 70 F 1 TAS shuts off heater when water temperature is over 85 F Remove and replace defective thermostat 2 1 CON must be energized Check using voltmeter at Terminals 3 5 Replace contactor if not energized 3 Check heater terminals Electrical terminals should be tight free of oxide build up 1 HTR must be energized Check using voltmeter at TB5 to 2W3 Replace heater if all t...

Page 6: ...Doc No 01999901 Revision A 5 of 10 Issue Date 08 15 21 INSPECTION TEST REPORT ...

Page 7: ...Doc No 01999901 Revision A 6 of 10 Issue Date 08 15 21 ...

Page 8: ...Doc No 01999901 Revision A 7 of 10 Issue Date 08 15 21 ...

Page 9: ...Doc No 01999901 Revision A 8 of 10 Issue Date 08 15 21 ...

Page 10: ...f original ownership as proof of warranty coverage and Encon must receive any claim under this Limited Warranty within one year of purchase of the product NOTWITHSTANDING ANYTHING TO THE CONTRARY CONTAINED HEREIN ENCON SHALL NOT BE LIABLE FOR LOSS DAMAGE OR EXPENSE ARISING DIRECTLY OR INDIRECTLY AS A CONSEQUENCE OF USE OF THE EQUIPMENT WITH OTHER PRODUCTS OR FROM ANY OTHER CAUSE INCLUDING ANY CONS...

Page 11: ...Doc No 01999901 Revision A 10 of 10 Issue Date 08 15 21 DRAWINGS ...

Reviews: