If connection can’t be established verify that:

1. ECpvh is powered up and running. ECpvh must have 24VDC (+/- 15%) supply

voltage. The green Power and the green Run LEDs in the front of the ECpvh must
both be illuminated. Note that a two low supply voltage can result in a situation
where sufficient voltage is present to power up the ECpvh but not to run the
program. In this case the Power LED is illuminated but the Run LED. When
powering up the ECpvh the Power LED will light up first and the Run LED will
come approximately 30s after when ECpvh is initialized and the program is up
and running.

2. Your laptop must be on the same subnet as the ECpvh. Even though you have an

ethernet cable going directly from your laptop to the ECpvh you still need to
make sure that your laptop is provided with a suitable IP address. In the case
where the default IP address of the ECpvh 192.168.1.101 is kept a suitable IP
address for your laptop would be 192.168.1.x, where x is a number in the range
[2;249] excluding “101” as this is used by the ECpvh itself.

3.

Once the IP of your laptop is in place you must be able to ping the ECpvh. This
can be done by opening a command prompt and writing the command “ping
xxx.yyy.zzz.www” where xxx.yyy.zzz.www is the IP address of the ECpvh as shown
below. First when the ECpvh replies to the command it is verified that your
laptop and the ECpvh can see each other on the network and you can connect to
ECweb using the browser as described above.

5

Summary of Contents for ECpvh

Page 1: ...ECpvh Quick Start Guide ...

Page 2: ...change log 2 Introduction 3 ECweb 4 Connecting to ECweb with Internet Explorer on PC laptop 4 Connecting to ECweb using any other browser or mobile device 4 Troubleshooting 5 Connection to ECweb established 6 1 ...

Page 3: ...Document change log 2021 04 26 First version 2021 09 20 Updated after release 1 01 0 2 ...

Page 4: ... device which will give you monitoring and control capabilities even from remote if connectivity to the ECpvh is in place Note that it is not mandatory for the control and balancing of the system to work to have HMI or laptop connected to ECweb It is required for commissioning of the ECpvh only This document explains how to establish a connection to the ECpvh from your laptop and mobile devices Re...

Page 5: ...on Internet Explorer Java download 1 Type in IP address of the ECpvh in the Internet Explorer browser command line Default IP address is 192 168 1 101 2 Type in login credentials when prompted Default login credentials are user web_user0 password web_password0 3 Accept Ignore all warnings populated 4 If tiles on the front page are out of order click on the page and they will fall into place If any...

Page 6: ...subnet as the ECpvh Even though you have an ethernet cable going directly from your laptop to the ECpvh you still need to make sure that your laptop is provided with a suitable IP address In the case where the default IP address of the ECpvh 192 168 1 101 is kept a suitable IP address for your laptop would be 192 168 1 x where x is a number in the range 2 249 excluding 101 as this is used by the E...

Page 7: ...an symbol will be presented alongside with the messages Furthermore when changing certain settings etc a reboot of the ECpvh is required before the changes take effect This will be communicated in the message as well and a dedicated button with refresh symbol will be presented alongside with the messages In the lower right corner is the internal clock of the ECpvh displayed In the lower center a t...

Page 8: ...dividual inverter and power meter 4 Control gives access to set up of ECpvh controller related parameters such as IP configuration Internal clock handling etc 5 Settings give access to setup of site specific parameters such as number and ratings of genset grid connections and inverters which power meters are used power and reactive control schemes etc 6 Logs give access to setup of log specific pa...

Reviews: