EDS800 series Service Manual
14
3.5 Basic running wiring diagram
Notice1:When FWD,RWV,X1
~
X5 terminal imput signal need low level(or pup
joint with COM) is effective. Please put JP3 on “L”.
Notice2:When FWD,REV,X1
~
X4 terminal imput signal need high level(or pup
joint with +10v) is effective. Please put JP3 on “H”.
3.6 Control loop collocation and wiring
3.6.1 Location&function of terminal and jump-wire:
For location of terminal and switch on the CPU board, please see Fig.3-7.
Function description of terminal provided for the user, please see Table 3-2
,
function and setup description of switch, please see Table 3-3
,
terminal CN1 is for
manufacturer’s use. Should carry on terminal wiring correctly and set switch on the
CPU board before using the inverter
,
to use at least No.24 conducting wire as
terminal connecting wire is recommended.
Fig. 3-6 basic wiring diagram
Braking unit (external,fitting part, interface at the
right side of inverter )
P+
PB
L1
L2
L3
breaker
forward run/stop
reverse run/stop
multi-function 1
multi-function 2
multi-function 3
multi-function 4
multi-function 5
FWD
REV
X5
X4
X3
X2
X1
U
V
W
E
GND
AO
DO
OC
TA
TB
TC
485A
485B
EDS800
Standard RS485
communication port
Malfunction relay output
open circuit collector output
Cymometer
Output 12V impulse signal
M
0~10V or 4~20mA
0~10V
speed command
+10V
VCI
CCI
GND
COM
power
supply
DC amperometer
4-20mA current signal
or 0~10v voltage signal
COM
OCG
Maximum 220VAC, 0.5A
+10V
JP3
H
L
multi-function5 canbe
used for high speed
pulse input
①
Notice 1
②
Notice2