Installation 

 

1.

 

Remove the plastic and threaded plugs from both sides of the housing. Determine which direction 
the conduit will enter the housing and insert the threaded plug on the opposite side. 

2.

 

Connect 12-24 VDC/AC 

power to the “Power Input” terminals on the transmitter (marked “TX”) 

and receiver (marked “RX”). 

The power input terminals are not polarity sensitive. 

3.

 

Connect the Common (COM) to the control input terminal per the operator manufacturer. 

4.

 

Connect either the Normally Open (NO) or Normally Closed (NC) as needed to the control input 
terminal per the operator manufacturer. 

5.

 

Adjust  the  sensitivity  potentiometer  as  needed  by  turning  counter  clockwise  to  increase  gain.  
Use the minimum sensitivity setting needed to achieve reliable detection. 

6.

 

Verify that the IRB-EXP transmitter and receiver are aligned and apply power. 

 

LED Indicators 

Green transmitter LED on 

Power 

Green receiver LED on 

Power 

Red receiver LED on 

Beam blocked or not aligned 

7.

 

Place an obstruction (ex. hand) between the IRB-EXP transmitter and receiver. The red LED on the 
receiver will turn on. Check the operator control board and verify that the safety input is recognized 
by  the  operator.    Test  the  beam  with  an  obstruction  between  the  transmitter  and  receiver  at 
multiple distances to confirm proper operation. 

8.

 

Remove the obstruction and red LED will turn off. 

 

 

If  IRB-EXP  is  aligned  but  not  detecting  an  obstruction,  consider  slowly  reducing  
the  sensitivity  (clockwise)  on  the  receiver  until  the  obstruction  is  detected.  
This may be applicable for installations with a detection zone of less than 20 ft.  