EMX Industries CarSense202 CS202 Instruction Manual Download Page 5

EMX Industries, Inc. 

Tech support: 216-518-9889 

5/5

 

CS202_Rev1.8_072220                                        [email protected]

 

 

Troubleshooting 

 

 

 

 

Warranty 

 

EMX Industries, Inc. products have a warranty against defects in materials and workmanship for a period 
of two years from date of sale to our customer. 

Symptom 

Possible Cause 

Solution 

False triggering 

Electrical disturbances 
 
Damaged probe cable 
 
Moisture in probe cable 
 

Movement in the probe’s 

 

environment 

 

Dirty or noisy power supply 

 

Lightning 

1.

 

Disconnect  from  operator  power  supply, 
temporarily connect the  red and black wires 
to a 9 or 12V battery.  Wait 5 minutes for the 
system  to  stabilize.  If  the  false  triggering 
stops, consider using a separate power supply 
for  the  CS202  such  as  a  120  VAC  to  
12 VDC power converter (min. 100 ma).  

 

2.

 

Disconnect the relay wires and see if the false 
triggering  continues.    If  the  false  triggering 
stops, switch the brown and green wires in the 
operator and/or add earth ground connection 
to  COM  input  in  operator.    Verify  that  the 
earth  ground  is  connected  securely.  If  the 
connection is not secure, reconnect the earth 
ground and retest the system. 

 

3.

 

Inspect  the  area  around  the  probe  to  see  if 
any ferrous metal objects may be subject to 
any  movement.  These  may  include  fences, 
flagpoles, signs, etc. Other possible causes are 
electrical power lines, electric motors, invisible 
dog  fences,  low  voltage  lighting  and  
high-power lighting. 

No detection 

Minimum 5 mph 
 
Bad wire connection 
 
Faulty power connection 
 
Failed relay 

1.

 

Disconnect  the  output  contacts  from  the 
operator.   

 

2.

 

Connect  a  digital  multi-meter,  set  to  read 
ohms,  to  the  CS202  internal  relay  COM  and 
NO  contacts.    The  meter  should  read  open 
(infinity).  Move a metal tool over the length of 
the  probe.  Verify  that  the  meter  reads  less 
than 10 ohms.  If the meter reads more than 
10 ohms, the CS202 is defective. 

 

3.  Check  the  supply  voltage  using  a  digital 

multimeter. Verify the voltage is 9-41 VDC or  
6-29 VAC. 

 

If voltage is present and there is still 

no detection, the CS202 is defective.

 

Summary of Contents for CarSense202 CS202

Page 1: ...his vehicle motion detector is available in 50 100 or 150 foot lead lengths Cautions and Warnings The CS202 is designed to detect moving vehicles It is not suitable for use as a vehicle presence detector such as a reversing loop for a gate or door The CS202 detects ferrous metals It will not detect aluminum but will detect any moving ferrous metallic object The probe must be stationary to function...

Page 2: ...te NC Brown NO Green COM and 8 earth ground White NC Brown NO Green COM Red Power 9 41 VDC Black Power 9 41 VDC and 8 earth ground AC Wiring Diagram DC Wiring Diagram IMPORTANT EARTH GROUND CONNECTION The CS202 contains transient protection devices to guard the sensitive electronic circuitry from damage and false triggering due to electrical transients caused by lightning or other sources Always p...

Page 3: ...nces gates or horses with metal shoes Do not mount on any moving surface such as bridges or walkways that may vibrate under traffic The probe must always be installed in such a way that it remains completely motionless Any movement will cause the probe to trigger Probes are available in various cable lengths when possible select the appropriate cable length for the installation If it is necessary ...

Page 4: ... The probe may be positioned prior to paving or a cut may be made in the finished pavement for installation 2 Connect the power output relay contact and earth ground to the intended equipment Reference EARTH GROUND CONNECTION in Wiring Connections DO NOT EXCEED 41 VDC or 29 VAC 3 Apply power and allow 5 minutes of warm up for system stabilization 4 Drive a vehicle at a minimum speed of 5 mph passe...

Page 5: ... the operator and or add earth ground connection to COM input in operator Verify that the earth ground is connected securely If the connection is not secure reconnect the earth ground and retest the system 3 Inspect the area around the probe to see if any ferrous metal objects may be subject to any movement These may include fences flagpoles signs etc Other possible causes are electrical power lin...