EMS fusion FCX-532-001 Installation Manual Download Page 2

Specification

Operating

Temperature 

-10°C to 50°C (ambient)

Storage

Temperature 

0°C to 35°C

Humidity 

Up to 95% non-condensing

Operating 

Voltage   

17 to 28V DC

Power

Requirements 

17mA @24V DC

IP Rating 

IP54

Operating 

Frequency 868MHz

Output 

Transmitter

Power   

Variable 0 - 14 dBm

Dimensions 

270mm (W) 205mm (H) 75mm (D)

Weight  

0.95kg 

Location  

Type A: For indoor use

EMS. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom

Manufacturer
Year of 

manufacture 

See devices serial number label 

2002/96/EC (WEEE directive):

Products marked with this symbol cannot be disposed of as unsorted 

municipal waste in the European Union. For proper recycling, return this 

product to your local supplier upon purchase of equivalent new 

equipment, or dispose of it at designated collection points. For more 

information see www.recyclethis.info

Contact Information 

EMS. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom

t: +44 (0) 1227 369570

f: +44 (0) 1227 369679

e: [email protected]

www.emsgroup.co.uk

Regulatory Information

EMS General

European Union 

directives

1999/5/EC (R&TTE directive):

Hereby EMS Radio Fire & Security Systems declares that this device is in 

compliance with the essential requirements and other relevant provisions 

of Directive 1999/5/EC.

Approved to

EN54-17:2005

EN54-18:2005

EN54-25:2008

©2014 EMS Radio Fire & Security Systems Ltd. All rights reserved                               2/2                                                                                 TSD077  Iss 3c  15/04/14   AJM

Certification

     

Certification

body  

0359

CPR Certificate 0359-CPR-0222

Step 10

 Reassemble the Loop Module

Ensure that the Loop Module PCB is correctly inserted and the 

PCB retaining screw is refitted.

Refit the Loop Module lid, ensuring all four lid screws and 

corner covers are fitted.

POWER

FAULT

ISOLATOR

ACTIVE

Care must be taken to ensure the LEDs are not damaged by 

the light pipe when refitting the Loop Module Lid.

F

 

usion

Loop Module

Loop Module 1

Loop Module 2

Loop Module 3

Loop 

In

Loop 

Out

+

-

Control

Panel

Step 7

 Connection Wiring

Multiple Loop Modules (max 5)

Loop Module 1

Single Loop Module

+

-

Screen

Scr

Loop

In

Loop

Out

Scr

+ -

+ -

Scr

Loop

In

Loop

Out

Scr

+ -

+ -

Scr

Loop

In

Loop

Out

Scr

+ -

+ -

Scr

Loop

In

Loop

Out

Scr

+ -

+ -

Loop cables should only be passed via the access points 

available.
Flame retardant cable glands must be used.
Cable lengths should be kept to a minimum to ensure cables are 

away from the PCBs aerials.

LOOP 1

+

-

RX

IN   OUT    IN    OUT

+

-

LOOP 2

+

-

IN   OUT    IN    OUT

+

-

RF1

RF2

Step 9

 Applying Power

Apply power to the Control Panel. The normal LED states for the 

Loop Module are as below:

Healthy LED - Green LED will be on. 
Fault LED - Yellow LED will be off. 
Sys Fault LED -  Yellow LED will be off. 

TX

RADIO

WD

RESET

HELP

RX

ON

1 2 3 4 5 6 7 8

BACK

POWER

FAULT

ISOLATE

0V
RX
TX
3V

SCR

+

-

LOOP IN

SCR

LOOP OUT

+

-

1  2  3  4  5  6  7 

POWER

FAULT

ISOLATE

 

 

 

addr 

DIL 

switch 

setting 

1…….…8

 

  

 

 

addr 

DIL 

switch 

setting 

1…….…8

 

   

 

 

addr 

DIL 

switch 

setting 

1…….…8

 

  

 

 

addr 

DIL 

switch 

setting 

1…….…8

 

  

 

 

addr 

DIL 

switch 

setting

 

1…….…8

 

10000000   11  11010000   21  10101000   31  11111000   41  10010100

 

01000000   12  00110000   22  01101000   32  00000100   42  01010100

 

11000000   13  10110000   23  11101000   33  10000100   43  11010100

 

00100000   14  01110000   24  00011000   34  01000100   44  00110100

 

10100000   15  11110000   25  10011000   35  11000100   45  10110100

 

01100000   16  00001000   26  01011000   36  00100100   46  01110100

 

11100000   17  10001000   27  11011000   37  10100100   47  11110100

 

00010000   18  01001000   28  00111000   38  01100100   48  00001100

 

10010000   19  11001000   29  10111000   39  11100100   49  10001100

 

10  01010000   20  00101000   30  01111000   40  00010100   50  01001100

 

 

 

  

 

   

 

  

 

  

 

51  11001100   61  10111100   71  11100010   81  10001010   91  11011010

 

52  00101100   62  01111100   72  00010010   82  01001010   92  00111010

 

53  10101100   63  11111100   73  10010010   83  11001010   93  10111010

 

54  01101100   64  00000010   74  01010010   84  00101010   94  01111010

 

55  11101100   65  10000010   75  11010010   85  10101010   95  11111010

 

56  00011100   66  01000010   76  00110010   86  01101010   96  00000110

 

57  10011100   67  11000010   77  10110010   87  11101010   97  10000110

 

58  01011100   68  00100010   78  01110010   88  00011010   98  01000110

 

59  11011100   69  10100010   79  11110010   89  10011010   99  11000110

 

60  00111100   70  01100010   80  00001010   90  01011010   100  00100110

 

 

 

  

 

   

 

  

 

  

 

101  10100110   106  01010110   111  11110110   116  00101110   121  10011110

 

102  01100110   107  11010110   112  00001110   117  10101110   122  01011110

 

103  11100110   108  00110110   113  10001110   118  01101110   123  11011110

 

104  00010110   109  10110110   114  01001110   119  11101110   124  00111110

 

105  10010110   110  01110110   115  11001110   120  00011110   125  10111110

 

 

 

 

 

 

 

 

 

126  01111110

 

 

Step 8

 Configuration

The address number is set using the onboard 8 way switch.
Available selections are shown in the table below.

The Loop Modules programming is configured using the Loop 

Modules menu structure. 
Refer to the Engineers Guide (Doc Ref: TSD062) for full 

programming details.

Loop 

In

Loop 

Out

+

-

Control

Panel

+

-

Screen

Screen Not Connected

Screen Not Connected

Reviews: