Page 1: ...5000 RADIO LAN COMMUNICATION GUIDE...
Page 2: ...RICAL INSTALLATION 4 5 FACTORY SUPPLIED PRE PROGRAMMED SYSTEMS 6 5 FACTORY SUPPLIED PRE PROGRAMMED SYSTEMS 7 6 SHOULD A LAN UNIT GO OFFLINE ON THE 485 BUS 7 7 SHOULD THE RADIO LAN GO OFFLINE 8 8 MONIT...
Page 3: ...ls together The Radio LAN Module is hardwired to it s allocated control panel via a 2 core screened fireproof cable This then enables communication between control panels via radio therefore the need...
Page 4: ...screws situated on the front lid The front section of the unit can now be removed Check that the front tamper switch operates when the lid is removed Should the microswitch not operate carefully adjus...
Page 5: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 5...
Page 6: ...Finish TIME Network Router Setup local NUA View Network NUA Network Name Control Routing Send Test Rem Rxer DISABLED Push YES to change Push NO to escape Push YES NO TIME Collector ENABLED Push YES to...
Page 7: ...he master panel will automatically try to re online the pre programmed slave panels This can take up to 5 minutes to complete With control panels offline an OL fault will be displayed at the master pa...
Page 8: ...bove The offline fault should clear from the panel 7 Should the Radio LAN go offline The following type of fault screen should be displayed Should such a fault be listed as previously shown the node p...
Page 9: ...odes Panels Nodes can be checked for the amount of polls missed by checking the individual node s missed poll counter This will give an indication of the signalling between panels on the network As a...
Page 10: ...e number The third row details values of information that is currently being sent The fourth line gives information of the nodes current status Eg Online or Offline With reference to the second line b...
Page 11: ...peater panels are allowed on each system To change panel s to have this functionality at the main panel Access the Main menu Scroll down to Fire DB and press the YES key Now scroll down the menu until...
Page 12: ...21100 then press the YES key and the screen will now display 6 Press the button until the screen displays 7 Press the YES key followed 0 key on the Keypad the screen will now display 8 Press the butto...
Page 13: ...ll now display 19 Press the button until the screen displays 20 Press the YES key The screen will now display Re online Device Bus Master Setup Bus Remote Setup Yes Select Time Master Setup Polling Ba...
Page 14: ...y 30 The Rem Rxer should be set to DISABLED press the YES key to change Otherwise press the NO key The screen will display Reply Baudrate Port to use Yes Select Time Remote Port 0 0 Off 1 RS485 2 PAGE...
Page 15: ...utton until the screen displays 40 Press the YES key and the screen will display 41 The Routing should be set to ENABLED If already set press the NO key If DISABLED press the YES Key followed by the N...
Page 16: ...ote The Site ID is factory set and can only be altered by entering an EMS engineering password Note This must match on all control panels on the radio board network for communication to take place 48...
Page 17: ...al timer value varies depending on the number of slave panels within the system The time can be calculated using the table below Number of Slaves including Mimics Applicable Poll Interval Timer Values...
Page 18: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 18...
Page 19: ...S key followed by entering 3600 Now press the YES key and the screen should display 58 Now press the NO key until the screen displays 59 Turn the control keyswitch to the off position and the screen w...
Page 20: ...cies UHF 458 5 459 5 MHz Transceiver Operating Temperature 10 to 55 degrees C Humidity Up to 75 non condensing Channel Spacing 25 kHz Output Transmitter Power 0 75W 500 mW 27DBH Supply 230v ac Current...
Page 21: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 21...