background image

ENVIROSTART MEC, SS & DVPR  INSTALLATION 

 

THE FOLLOWING DETAIL APPLIES TO ALL ENVIROSTART UNITS

 

PRIOR TO INSTALLATION 

 

 

 

Carefully remove the EnviroStart from the packaging and check that the parts supplied correspond with your order.      

  Check 

that 

the 

Voltage

Current 

and 

kW 

ratings of the EnviroStart corresponds with the motor nameplate details. 

 

 

 

Check that there are no loose parts or loose objects within the EnviroStart unit. 

 

Check sufficient space exists to correctly install the EnviroStart. 

 

 

 

Check you have sufficient tools to correctly install the EnviroStart.

 

MECHANICAL INSTALLATION 

Unless the EnviroStart is fitted within a suitable enclosure the following should be avoided. 

1. 

Exposure to rain, spray or wet areas. 

2. 

Exposure to explosive and/or corrosive atmospheres. 

3. 

Atmospheres containing a high proportion of conductive dust. 

4. 

Extremes of temperature and/or humidity beyond specified limits. 

WALL MOUNTING 

Fix the EnviroStart to a flat vertical surface using the mounting holes provided using adequately sized mounting bolts. 

Care should be taken to ensure the orientation of the EnviroStart is correct and a gap of 100mm is maintained above and below the EnviroStart. 
This is to ensure a safe exit path for the heat generated by the semiconductors within EnviroStart. 

COOLING ENVIROSTART WITHIN AN ENCLOSURE. S

ee section on cooling in the Installation and Commissioning Guide.

 

ELECTRICAL INSTALLATION 

INPUT/OUTPUT CONTROL CONNECTIONS

 To avoid ‘ pick up’ it is good practice to keep all control connections as short as possible 

and to run them separately from the main motor cables. If isolation and screening cannot be guaranteed an interposing relay fitted with suitable 
suppression must be used, this should be mounted as close to the EnviroStart as possible. 

POWER FACTOR CORRECTION CAPACITORS 

Power factor correction capacitors, if fitted, should be connected to the live side of K1 

and switched in or out before starting EnviroStart. 

NEVER CONNECT POWER FACTOR CORRECTION CAPACITORS TO THE 

OUTPUT TERMINALS OF THE ENVIROSTART, 

this will cause damage to the unit. 

ADDITIONAL EQUIPMENT

 all necessary electrical connections for mains, earth and control wiring are provided for in the EnviroStart unit, 

however the following additional components may be required, isolator; cable protection fuses; AC3, (three phase AC), rated contactor; motor 
overloads etcetera depending upon the wiring configuration and local regulations.

 

FUSE PROTECTION 

The mains supply and the control supply each require fuse protection. The installer should always fuse the mains 

supply with 

motor rated fuses

 before the input to the EnviroStart. 

THE FOLLOWING DETAIL APPLIES ONLY TO THREE PHASE SYSTEMS 

ENVIROSTART MAINS CONNECTION FOR STAR DELTA SYSTEM 

The EnviroStart must be fitted between the Isolator and the Line 

Contactor with no other circuits connected. Ensure that the feed to the control circuit is maintained. The mains in, is on L1, L2, L3, the feed to 
the motor is on U, V, W, these terminals are marked on the EnviroStart 

The start signal 

MUST

 be volt-free and can typically be taken from spare volt-free auxiliary contacts on the Delta Contactor to the EnviroStart 

connectors 1 through 4 in accordance with the details contained within the relevant Installation Guide. 

On Star Delta systems when there are back pressure switches on the Star Contactor (Compressors etcetera) you should wire the load solenoid of 
the (compressor) in series with the top of ramp, normally open contacts on the EnviroStart.  

ENVIROSTART MAINS CONNECTION FOR DIRECT ON LINE SYSTEM 

The EnviroStart must be fitted between the Contactor and 

the motor, put link between 1 and 2 and use the existing start and stop buttons to control the motor. Please ensure the motor is connected in 
Delta mode. The mains in, is on L1, L2, L3, the feed to the motor is on U, V, W, these terminals are marked on the EnviroStart. 

OVER TEMPERATURE TRIP 

On SS and MEC units of 55kW and above the over temperature trip will operate in the event that the heatsink 

temperature exceeds 90C. The temperature trip will need to be reset on the PCB in this event. (Please see detail in Installation Guides). 

     MAINTENANCE

  Periodically clean the fans, (if fitted), to ensure free air flow.  Check the security of power connections to unit every six 

months or more frequently if the unit is in a high vibration environment. Keeping the inside of your unit clean and dust free will enhance its life, 
however, it is not necessary for its normal operation. 

DEFAULT SWITCH SETTINGS TABLE 

EnviroStart is set to the ‘default settings’ before leaving the  factory. These settings should be              

tried first and further adjustments made only where necessary to fine-tune the  performance of the unit.  

THREE PHASE MOTOR ENERGY CONTROL DEFAULTS 

ADJUSTMENT 

 

FUNCTION 

 

DEFAULT            

 

RESULT   

SEE SECTION 

 

     SETTING 

    OF 

FULL 

GUIDE 

 

 

Switch 1, 2 & 3 

 

Ramp Up Time 

 

OFF, ON, OFF 

       Ramp set at 20s.   

6.2 

 Switch 

  Ramp 

Time 

Multiplier   

OFF 

 

       No Time Multiplication 

6.3 

 

Switch 5 & 6  

 

Energy Saving Level   

OFF, ON   

       Set at 75% of Full Power 

6.4 

 Switch 

 

  Thyristor 

Fault 

Detect 

 OFF 

 

       Fault Detection Enabled 

6.5 

 

Switch 8, 9 & 10 

 

Ramp Up Pedestal Voltage 

ON, OFF, OFF 

       Set at 40% of Full Voltage 

6.6 

 

Switch 11   

 

Soft Stop Enable 

 

OFF 

 

       Soft Stop Disabled  

6.7 

 

 Switch 

12 

  50/60Hz 

Select 

 OFF 

 

       50Hz Selected 

 

6.8 

 

Switch 13   

 

Thyristor Triggering Level 

OFF 

 

       Two Thyristors Fired 

6.9 

 

Switch 14   

 

Kick Start Enable 

 

OFF 

 

       Kick Start Disabled 

6.10 

 Switch 

15 

  Kick 

Start 

Voltage 

Level 

ON 

 

       Set at 90% Full Voltage 

6.10 

 

Switch 16 & 17 

 

Kick Start Time 

 

ON, ON 

 

       Set at 0.25s 

 

6.11 

 Switch 

18 

  Allows 

Remote 

E Save Disable 

OFF 

 

       No Remote Disabling 

6.4 

 

Switch 20   

 

Energy Save Enable 

 

ON 

 

       Energy Savings Enabled 

6.4 

 Rotary 

Pot. 

VR1 

 Current 

Limit 

 Mid 

Position 

       Partial Current Limit 

6.12 

 

 

THREE PHASE SOFT START DEFAULTS 

 
 

Switch 1, 2 & 3 

 

Ramp Up Time 

 

OFF, ON, OFF 

       Ramp set at 20s.   

6.6 

 Switch 

  Ramp 

Time 

Multiplier   

OFF 

 

       No Time Multiplication 

6.7 

 

Switch 5 & 6  

 

Ramp Down Time 

 

OFF, ON   

       Ramp set at 10s 

 

6.8 

 

Switch 7,8 & 9 

 

Ramp Up Pedestal Voltage 

ON, OFF, OFF 

       Set at 40% of Full Voltage 

6.9 

 

Switch 10 & 11 

 

Ramp Down Pedestal Voltage 

OFF, ON          

       Sets Initial Drop to 70% 

6.10 

 Switch 

12 

  50/60Hz 

Select 

 OFF 

        50Hz Selected 

 

6.11 

 

 Switch 

13 

  Thyristor 

Fault 

Detect 

 OFF 

 

       Fault Detection Enabled 

6.12 

 

Switch 14   

 

Kick Start Enable 

 

OFF 

 

       Kick Start Disabled 

6.13 

 Switch 

15 

  Kick 

Start 

Voltage 

Level 

ON 

 

       Set at 90% Full Voltage 

6.13 

 

Switch 16 & 17 

 

Kick Start Time 

 

ON, ON 

 

       Set at 0.25s 

 

6.14 

 

Switch 18   

 

Emergency Run 

 

OFF 

 

       Disabled 

 

6.15 

 

Switch 19 & 20 

 

Not Connected 

 Rotary 

Pot. 

VR1 

 Current 

Limit 

 Mid 

Position 

       Partial Current Limit 

6.2 

 
 

THREE PHASE DIGITAL VOLTAGE AND POWER REGULATORS

 

 
 

Switch 1 

 

 

Operational or Test Mode 

OFF 

 

        Operational 

 

7.1 

 

Switch 2 

 

 

PCB or External Control 

OFF 

 

        PCB Control 

 

7.2 

 

Switch 3 

 

 

0-10V or 4—20mA Select 

OFF 

 

        1—10V Selected   

7.2 

 

Switch 4 

 

 

Normal or Emergency Run 

OFF 

 

        Normal Operation  

7.3 

 

Switch 5 

 

 

DVR or DPR Mode 

 

OFF 

 

        DVR Mode 

 

7.4 

 

Switch 6 

 

 

Delta or Star Configuration 

OFF 

 

        Delta Configured Load 

7.5 

 Switch 

  50/60Hz 

Select 

 OFF 

         50Hz Selected 

 

7.6 

 

Switch 8, 9 & 10 

 

Current Limit 

Ballast 

Select 

     7.2 

 Rotary 

Pot. 

VR1 

 Current 

Limit 

 Fully Clockwise 

        Disabled 

 

7.7 

 

If the unit does not start the load please refer to the full Installation and Commissioning Guide 

STARTING AND STOPPING ENVIROSTART UNITS 

To start the EnviroStart MEC or SS provide a legitimate start signal to connectors 1 to 4 

on the terminal block, EnviroStart should start at the programmed settings. In the case of MEC and SS units the mains supply and the motor must be 
present to allow EnviroStart to start. In the case of the DVPR power may be provided to the output terminals even if no load is present. 

To stop the EnviroStart open link between terminals 1 to  4, In the case of MEC and SS units, if soft stop is enabled on either unit be aware that the 
motor may continue to be powered for a period after the start/run signal has been removed. 

Refer to the Full Installation and Commissioning Guide for details of relay operation and specific system function.

 

 

THE FOLLOWING DETAIL APPLIES TO BOTH SINGLE AND THREE PHASE SYSTEM

S

 

COMMISSIONING CHECKS 

1. 

Ensure that the terminal block is configured correctly and that the cables are all secure and are of the correct rating for the load. 

2. 

Ensure that ALL DIP switch settings are at Default or configured according to the details contained within the full Installation and 
Commissioning Guide. 

3. 

Ensure that the unit is correctly and safely wired to the load in accordance with the details contained within the full Installation and 
Commissioning Guide. 

4. 

Ensure that any Power Factor Correction Capacitors within the “local” system, (that is, within 20 cable metres of the EnviroStart control), are 
connected to the input side of the system Line Contactor and are switched in and out when EnviroStart is NOT running. It is imperative that the 
capacitors are out of circuit and isolated from the EnviroStart at the time that the motor is turned off as they can see the thyristors as a low 
impedance line to earth and will discharge through them causing severe damage and risk to operator safety. 

5. 

Ensure that all specifications relating to the product are adhered to especially with regard to starts per hour during commissioning. 

 

STARTING ENVIROSTART FOR THE FIRST TIME 

     Check that all the pre-commissioning checks have been followed, then initiate the start by linking 1 though 4 as detailed within the Installation and 

Commissioning Guide, EnviroStart should power the load smoothly to full  power, if starting is not satisfactory then refer to the full Guide. 

 

 

WARNING 

ENVIROSTART MUST BE EARTHED.

 

CONNECT THE EARTHING STUD WITHIN THE ENVIROSTART UNIT TO A SUITABLE LOW IMPEDANCE EARTH 

AS IS REQUIRED BY STATUTORY REGULATIONS COVERING THE INSTALLATION OF ELECTRICAL EQUIPMENT

Reviews: