1 Introduction

6 Connection wiring

2 Pre installation

Part no      Product description

EC-63-0001

EMS Conventional Interface Card

Conventional Interface Card (CIC)

Installation Guide

3 Connect CIC to the ZIM

5 Fasten the ZIM’s terminals 

SOUNDERS

FAULT

ZONE/RESET

EOL L1 L2 EOL L1 L2

ALARM

RES

EOL L1 L2

(+)    (-) (+)    (-) (+)    (-) (+)    (-) (+)    (-)

(+)    (-)

(+)    (-)

SOUNDERS

FAULT

ZONE/RESET

EOL       L1 L2

EOL        L1 L2

ALARM

RES

EOL        L1 L2

The CIC can be wired in two different ways. 

Fault notification can either be monitored via the conventional 

fire panel’s sounder or zone circuit.

See overleaf for the alternative wiring methods.

Ensure the pins line up with the ZIM’s terminal connections as 

shown.

!

Installation must conform to applicable local installation 

codes and should only be installed by a fully trained 

competent person. 

Only fit the CIC to the zone interface module 

(ZIM)

, when 

connecting to a conventional fire panel.

The CIC should only be connected to designated zone and 

sounder circuits.

 

Refer to the EMS wireless zone monitor engineers guide 

(TSD143)

 for full programming information.

Refer to the conventional control panel compatibility document 

(MK58) 

for details of compatible conventional fire alarm panels.

This device contains electronics that may be susceptible to 

damage from electrostatic discharge 

(ESD)

. Take appropriate 

precautions when handling electronic boards.

ZIM with 

CIC fitted 

WZM

ww

w .ems

gr

ou

p.c

o.u

k

Radio D

etec

tor Base

PRESS HERE T

O

L OG ON

IDENT

FireCell wireless devices

POWER
FAULT

WIRELESS ZONE MONITOR

FC-ZIM-001

Conventional

fire panel

The conventional interface card 

(CIC)

 when fitted to the zone 

interface module 

(ZIM)

, enables 30 FireCell wireless devices to be 

added to an existing conventional fire panel, via a wireless zone 

monitor 

(WZM)

.

*

*

 

Designated zone 

and sounder circuits.

4 Fasten the CIC PCB into the ZIM

©2021 EMS Ltd. All rights reserved                                                                      Page 1 of 2 

TSD147-99  Iss 6  15/12/2021   AJM