![EMS EC-41-0200 Installation Manual Download Page 2](http://html1.mh-extra.com/html/ems/ec-41-0200/ec-41-0200_installation-manual_2404568002.webp)
7 Power device
When fitting / replacing batteries; observe correct polarity,
using only specified batteries.
Connect the power jumper across the PIN header.
6 Connection wiring
Once powered, reassemble the device.
OUTPUT 2
OUTPUT 1
3VDC SET RST
INPUT 1 INPUT 2
LED
ENABLE
PO
WER
INPUT
1
INPUT
2
FAULT
CLOSED
0
1
1
64
F-SAFE
N/O COM N/C
IP- IP+ IP- IP+
3VDC SET RST
N/O COM N/C
EXPAN1
EXPAN2
RELA
Y ON
RELA
Y ON
2
4
8
16
32
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
Refer to the wireless zone
monitor engineers guide
(TSD143)
for full wiring
details.
Free to download from
www.emsgroup.co.uk
8 Configuration
The ZIM must be added to the WZM, before adding other wireless
devices to the system.
Refer to the wireless zone monitor engineers guide
(TSD143)
for full programming details.
Free to download from
www.emsgroup.co.uk
9 LED operation
The device has six indication LEDs. Pressing the LED enable button
enables their illumination for 10 minutes before automatically
timing out.
2x input fault: YELLOW LED ON = FAULT
2x input closed: RED LED ON = ACTIVE
2x output: RED LED ON = ACTIVE
CLOSED
FAULT
INPUT 1
INPUT 2
Input 2
LEDs
Input 1
LEDs
Output 1 LED Output 2 LED
Operating
temperature
-10 to +55 °C
Storage
temperature
5 to 30 °C
Humidity
0 to 95% non-condensing
Supply
6x
AA
alkaline
(Panasonic LR6AD Powerline
/
Varta
4006
Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
Output rating
2A at 24 VDC
IP rating
IP65
Operating frequency
868 MHz
Output transmitter
power
Auto adjusting 0 to 14 dBm
(0 to 25 mW)
Dimensions
(W x H x D)
270 x 205 x 75 mm
Weight
0.95
kg
Location
Type A: For indoor use
2012/19/EU
(WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For recycling, return this product to
your local supplier upon purchase of equivalent new
equipment, or dispose of it at designated collection
points. For more information see
www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
European Union
directives
EMS declares that this device is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the following
internet address:
www.emsgroup.co.uk
Approved to
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008. Incorporating corrigenda
September 2010 and March 2012. Fire detection
and fire alarm systems. Part 25: Components using
radio links.
Certification
Certification body
CPR DoP
0359-CPR-00436
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa
24. 39-100 Ropczyce, Poland
Manufacturer
Year of
manufacture
See devices serial number label
0905
14
Specification
Regulatory Information
©2021 EMS Ltd. All rights reserved. Page 2 of 2
TSD142-99 Iss 6 15/12/2021 AJM