7 Power device 

When fitting / replacing batteries; observe correct polarity, 

using only specified batteries.

Connect the power jumper across the PIN header.

6 Connection wiring

Once powered, reassemble the device.

OUTPUT  2

OUTPUT  1

3VDC SET RST

INPUT 1 INPUT 2 

LED

ENABLE

PO

WER

INPUT 

1

INPUT 

2

FAULT

CLOSED

0

1

1

64

F-SAFE

N/O COM N/C

IP-    IP+ IP-    IP+

3VDC SET RST

N/O COM N/C

EXPAN1

EXPAN2

RELA

Y ON

RELA

Y ON

2

4

8

16

32

device

unpowered

(pins unlinked)

device

powered

(both pins linked) 

Refer to the wireless zone 

monitor engineers guide 

(TSD143)

 for full wiring 

details. 

Free to download from 

www.emsgroup.co.uk

8 Configuration

The ZIM must be added to the WZM, before adding other wireless 

devices to the system.

Refer to the wireless zone monitor engineers guide 

(TSD143)

 

for full programming details.

Free to download from 

www.emsgroup.co.uk

9 LED operation

The device has six indication LEDs. Pressing the LED enable button 

enables their illumination for 10 minutes before automatically 

timing out.

2x input fault: YELLOW LED ON        = FAULT

2x input closed: RED LED ON        = ACTIVE

2x output: RED LED ON        = ACTIVE

CLOSED

FAULT

INPUT 1

INPUT 2

Input 2 

LEDs

Input 1 

LEDs

Output 1 LED Output 2 LED

Operating

temperature

   

 

-10 to +55 °C

Storage

temperature

   

 

5 to 30 °C

Humidity    

0 to 95% non-condensing

Supply

 

   6x 

AA 

alkaline 

(Panasonic LR6AD Powerline  

    / 

Varta 

4006 

Industrial)

  

CAUTION! 

Fitting of an incorrect battery type invalidates the product certification and

may result in poor performance.

Output rating

   

 

2A at 24 VDC

IP rating 

 

 

IP65

Operating frequency

   

868 MHz

Output transmitter

power

   

 

 

Auto adjusting 0 to 14 dBm

 (0 to 25 mW)

Dimensions 

(W x H x D)

 

270 x 205 x 75 mm

Weight

 

   0.95 

kg

Location

 

 

 

Type A: For indoor use

2012/19/EU 

(WEEE directive):

Products marked with this symbol cannot be 

disposed of as unsorted municipal waste in the 

European Union. For recycling, return this product to 

your local supplier upon purchase of equivalent new 

equipment, or dispose of it at designated collection 

points. For more information see 

www.recyclethis.info

Dispose of your batteries in an environmentally 

friendly manner according to your local regulations.

European Union 

directives

EMS declares that this device is in compliance with 

Directive 2014/53/EU. The full text of the EU 

declaration of conformity is available at the following 

internet address: 

www.emsgroup.co.uk 

Approved to

EN54-18:2005. Fire detection and fire alarm 

systems. Part 18: Input/output devices.

EN54-25:2008. Incorporating corrigenda 

September 2010 and March 2012. Fire detection 

and fire alarm systems. Part 25: Components using 

radio links.

Certification

     

Certification body

  

CPR DoP 

 0359-CPR-00436

Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa 

24. 39-100 Ropczyce, Poland

Manufacturer

Year of 

manufacture

   

See devices serial number label 

          

0905

14

Specification

Regulatory Information

©2021 EMS Ltd. All rights reserved.                                                                     Page 2 of 2 

TSD142-99  Iss 6 15/12/2021   AJM