Commissioning set up
Commissioning set up
Start
(AVR Active / Generator running ! )
Underspeed protection
Done
Threshold underspeed
Underspeed
Slowly
Until led on
Setpoint underspeed
Underspeed
Very slowly
Until led off
Led not red flickering!
Nominal speed
G
M
Note:
It is recommended to turn
the potentiometer a little
further clockwise,
to allow for short
frequency dips.
Indication setpoints