10
BDAMON02-NPA72 Manual
© 2016 EMR Corporation
BDAMON02-NFPA72
USERS MANUAL
APPENDIX
A.3 Relay Output Port
The Relay Output Port (J11) is a DB25 Male connector typically located on the bottom right
panel of the BDA. A label of the pin-outs is also located inside of the door of the BDA. A
DB25 Female connector (with hood hardware) is supplied with the unit for the Install
Technician to connect to the Alarm Panel.
Note: Pin Numbers are written on the DB25 Connectors
There are 7 alarm relays available, these will supply contact closure (Supervisory Signal)
to the fire alarm panel for the following alarm:
(1) AC Power Failure
(2) Signal Booster Failure
(3) Battery Charger Failure
(4) Low-battery capacity
(5) Power Supply Failure
(6) Antenna Malfunction
(7) Signal Booster Trouble
Note: Signal Booster trouble (any alarm) closes on any alarm except the door alarm.