Appendix A
–
Meter programming
12.1
Programming the ADL400 meter
The meter will come pre-programmed and the installer should not need to change anything. This section
was included in case some of the settings are incorrect.
The minimal connection for programming is a 230v connection between UA and UN on the top panel.
To change a setting, press
↵
until a digit starts to flash.
To change that digit, use the
button.
To move to the next digit, use the
button
1.
Hold
↵
for 3 seconds
2.
Enter the password 0001 and press
↵
3.
Change the Address to 001
4.
Change the Ct to 30
5.
Verify the following:
a.
Baud 9.6
b.
Par None
6.
Then hold
↵
for 3 seconds
7.
Change Save? To Yes, and press
↵