Empire Heating Systems FAW-55SPP Owner'S Manual Download Page 4

12428-6-0408

Page 4

Ventilation and Combustion Air

Wall furnaces shall be installed in a location in which the facilities for 

ventilation permit satisfactory combustion of gas and proper venting 

under normal conditions. In buildings of conventional frame, brick, or 

stone construction without tight storm windows and doors, infiltration 

is normally adequate to provide air for combustion and draft hood dilu-

tion.

Where appliances are installed in confined and unconfined spaces 

within a building, the building being of unusually tight construction, air 

for combustion and ventilation must be obtained directly from outdoors 

or from such spaces that freely communicate with the outdoors. Under 

these conditions, the confined and unconfined spaces shall be provided 

with two permanent openings, one near the top of the enclosure and one 

near the bottom; each opening shall have a free area of not less than one 

square inch (6.45cm

2

) per 2,000 BTU hr. (.6KW/H) of total input.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or 

accessories and repair and servicing of equipment shall be performed 

only by a qualified agency. The term “qualified agency” means any indi-

vidual, firm, corporation or company which either in person or through 

a representative is engaged in and is responsible for (a) the installation 

or replacement of gas piping or (b) the connection, installation, repair or 

servicing of equipment, who is experienced in such work, familiar with 

all precautions required and has complied with all the requirements of 

the authority having jurisdiction. 

The installation must conform with local codes or, in the absence of 

local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54* 

Natural Gas and Propane Installation Code, CSA B149.1.

*Available from the American National Standards Institute, Inc., 11 

West 42nd St., New York, N.Y. 10036.

Clearances

1.  In selecting a location for installation , it is necessary to provide 

adequate accessibility clearances for servicing and proper installa-

tion.

2.  The FAW-55 can be attached to the wall or recessed into the wall up 

to 4 inches (102mm) in depth.

3.  The wall in which the furnace is recessed has (0) zero (0mm) clear-

ance to the furnace sides and top.

4.  When using side discharge registers, SOR-1 or SOK-1, the furnace 

cannot be recessed into the wall.

5.  Clearance  to  sidewall  or  combustible  material  is  4  inches 

(102mm).

6.  Ceiling clearance is 7 1/2 inches (191mm)

7.  Floor and rear wall clearance is (0) zero inches (0mm).

8.  Clearance of 18 inches (457mm) is required to adjacent wall or com-

bustible material when flushed mounted SOR-1, side outlet register 

is used.

Before Installing Consider The Following Venting

1.  A chimney for residential-type or low-heat gas utilization equipment 

shall extend at least 3 feet (914mm) above the highest point where it 

passes through a roof of a building and at least 2 feet (610mm) higher 

than any portion of building within a horizontal distance of 10 feet 

(3m).

2.  This  furnace  must  not  be  connected  to  a  chimney  flue  serving  a 

separate solid-fuel burning appliance.

3.  Uninsulated Single-Wall Metal Pipe shall not be used outdoors in 

cold climates for venting gas utilization equipment.

4.  Attention! This Fan Type Vented Wall Furnace is equipped with a 

vent safety switch. In the event of spillage of flue products due to 

improper venting the vent safety switch will open, which results in 

State of Massachusetts: 

The installation must be made by a 

licensed plumber or gas fitter in the Commonwealth of Mas-

sachusetts.

the main burners to “shut off.”

Refer to Figure 1 and Page 12 for additional information regarding U.L. 

Listed gas vent equipment.

Installing Optional Side Outlets

Side outlet register, SOR-1 may be installed on one or both sides of the 

furnace at the required clearances of 18 inches (457mm) to adjacent wall 

or combustible material as shown in Figure 2.
1.  Locate and cut the 5 1/2” (140mm) square opening in the cabinet side 

using the template from the kit, exposing the inner liner knock-out.

2.  Remove the knock-out.

3.  Place the register on the 5 1/2” (140mm) opening with the louvers 

set for the desired direction and mark the mounting holes using the 

register as a template.

4.  Drill two (2) 1/8” (3mm) diameter holes in cabinet side and fasten the 

register in place with two (2) #10 x 1” (25mm) screws provided.

Side outlet kit, 10” (254mm) boot assembly with register, SOK-1 for warm 

air discharge into an adjoining room may be installed on either side of the 

furnace at the required clearance of 4 inches (102mm) to adjacent wall as 

shown in Figure 3A.
1.  Locate and cut the 5 1/2” (140mm) square opening in the cabinet side 

using the template from the kit, exposing the inner liner knock-out.

2.  Remove the knock-out.

3.  Using the inner and outer boots as hole templates, mark and drill (8) 

1/8” (3mm) diameter holes in the inner liner and cabinet side.

4.  Using Figure 3A locate and cut a 6 3/4” (171mm) square opening 

through walls.

5.  Attach furnace to wall (see 

Attaching Furnace to Wall

).

6.  With furnace in place, after checking alignment of side outlet opening 

in wall and furnace, place the 9 3/8” x 9 3/8” (238mm x 238mm) side 

outlet wall plate over outer boot, pass the outer boot through the wall 

and attach side outlet wall plate to furnace side of wall with (2) #10 

x 1” (25mm) screws provided.

7.  Fasten outer boot to the cabinet side with (4) #8 x 1/4” (6mm) screws 

provided.

8.  Position and attach inner boot to inner liner with (4) #8 x 1/4” (6mm) 

screws provided.

9.  Locate  the  register  with  its  louvers  positioned  for  the  desired  air 

discharge direction and mark the mounting holes using the register 

as a template.

10.Drill (2) 1/8” (3mm) diameter holes in the wall and fasten the register 

in place with (2) #10 x 1” (25mm) screws provided.

Installing Optional Rear Outlet

Rear outlet kit, 10” (254mm) boot assembly with register, ROK-1 for warm 

air discharge into an adjoining room.

Attention:

 Before furnace is attached to the wall, the wall opening for 

the rear outlet must be cut, in addition to removal of the outer and inner 

casing knockouts on furnace.

1.  The wall opening measurements for the rear outlet are the follow-

ing.

  A.  From floor to bottom of wall opening is 14 3/4” (375mm).

  B.  From the bottom of wall opening to top of wall opening is 8 1/2” 

(216mm).

  C.  Wall opening width is 12 1/8” (308mm).

2.  Remove outer casing knockout from outer casing back.

3.  Remove inner casing knockout from inner casing.

4.  Attach furnace to wall (see 

Attaching Furnace to Wall

).

5.  Align clearance holes on 8” x 12” (203mm x 305mm) boot with 

screw holes on outer casing back and mark boot to be flush with 

wall surface. Remove boot and cut to proper length.

6.  Attach 8” x 12” (203mm x 305mm) boot to outer casing back with 

(6) #10 x 1/2” (13mm) screws provided.

7.  Align clearance holes on 6” x 10” (152mm x 254mm) duct with screw 

holes on inner casing and mark duct to be 2 1/4” (57mm) shorter than 

Summary of Contents for FAW-55SPP

Page 1: ...or other amma ble vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any pho...

Page 2: ...ocated not less than 18 457mm above the oor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehicle Speci cations Model FAW 55SPP Input BTU HR KW H 55...

Page 3: ...as can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clos...

Page 4: ...age of ue products due to improper venting the vent safety switch will open which results in State of Massachusetts The installation must be made by a licensed plumber or gas tter in the Commonwealth...

Page 5: ...Gas Supply The gas line can enter the furnace either though the oor or wall The gas line opening should be made at this time Location of the opening will be determined by the position of oor joists a...

Page 6: ...Insert 7 8 22mm strain relief bushing into the 7 8 22mm hole in the side panel Attention The7 8 22mm strainreliefbushingislocatedwithinthesame yellow envelope as the Installation Instructions and Own...

Page 7: ...pilot ame Figure 6 will be blue extending past the thermo couple The ame will surround the thermocouple just below the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5...

Page 8: ...Main Burner Ori ces Disconnect the gas supply at the inlet to the control valve Then remove the burner door to which the above compo nents are attached Servicing The Fan Motor The upper front panel t...

Page 9: ...ontrol knob clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the oor If you smell gas STOP Fol low B in the safety information above If you don t smell gas...

Page 10: ...59 GASKET TUBING SEAL 7 11787 FAN BLADE 34 722040 MANIFOLD UNION 8 DV 635 B COMBUSTION CHAMBER 35 R 5655 GAS VALVE VR8200C LP GAS 9 11766 FAN HOUSING 35 R 2148 GAS VALVE VR8200C NATURAL GAS 10 11759 S...

Page 11: ...12428 6 0408 Page 11...

Page 12: ...re a baseplate one pair of ceiling plate spacers at the rst oor ceiling and one pair of re stop spacers at each successive ceiling level Stud space around gas vents must be free of obstructions and bu...

Reviews: