background image

25664-0-0309

Page 5

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part 

for residential purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent termination 

is  less  than  seven  (7)  feet  above  finished  grade  in  the  area  of 

the venting, including but not limited to decks and porches, the 

following requirements shall be satisfied:

1.  INSTALLATION 

OF 

CARBON 

MONOXIDE 

DETECTORS. 

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gasfitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, the installing 

plumber  or  gasfitter  shall  observe  that  a  battery  operated 

or  hard  wired  carbon  monoxide  detector  with  an  alarm  is 

installed on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner 

to secure the services of qualified licensed professionals for 

the installation of hard wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

 

b.  In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with  the  above  requirements;  provided,  however,  that 

during  said  thirty  (30)  day  period,  a  battery  operated 

carbon  monoxide  detector  with  an  alarm  shall  be 

installed.

2.  APPROVED CARBON MONOXIDE DETECTORS. Each 

carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified. 

3.  SIGNAGE. A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line 

with the exhaust vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The sign shall read, 

in print size no less than one-half (1/2) inch in size, 

“GAS 

VENT  DIRECTLY  BELOW.  KEEP  CLEAR  OF  ALL 

OBSTRUCTIONS”.

4.  INSPECTION. The state or local gas inspector of the side 

wall  horizontally  vented  gas  fueled  equipment  shall  not 

approve the installation unless, upon inspection, the inspector 

observes carbon monoxide detectors and signage installed in 

accordance  with  the  provisions  of  248  CMR  5.08(2)(a)  1 

through 4.

 

(b)  EXEMPTIONS:  The  following  equipment  is  exempt 

from 248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The  equipment  listed  in  Chapter  10  entitled 

“Equipment  Not  Required  To  Be  Vented”  in  the 

most current edition of NFPA 54 as adopted by the 

Board; and 

 

 

2.  Product Approved side wall horizontally vented gas 

fueled  equipment  installed  in  a  room  or  structure 

separate  from  the  dwelling,  building  or  structure 

used in whole or in part for residential purposes. 

 

(d)  MANUFACTURER  REQUIREMENTS  -  GAS 

EQUIPMENT VENTING SYSTEM NOT PROVIDED. 

When  the  manufacturer  of  a  Product  Approved  side 

wall horizontally vented gas fueled equipment does not 

provide the parts for venting the flue gases, but identifies 

“special  venting  systems”,  the  following  requirements 

shall be satisfied by the manufacturer:

 

 

1.  The referenced “special venting system” instructions 

shall be included with the appliance or equipment 

installation instructions; and

 

 

2.  The  “special  venting  systems”  shall  be  Product 

Approved  by  the  Board,  and  the  instructions  for 

that  system  shall  include  a  parts  list  and  detailed 

installation instruction.

 

(e)  A  copy  of  all  installation  instructions  for  all  Product 

Approved  side  wall  horizontally  vented  gas  fueled 

equipment,  all  venting  instructions,  all  parts  lists  for 

venting instructions, and/or all venting design instructions 

shall  remain  with  the  appliance  or  equipment  at  the 

completion of the installation. 

Summary of Contents for Tahoe DVP42FP30N-3

Page 1: ...ng plate This appliance is not convertible for use with other gases unless a certified kit is used The Tahoe Direct Vent Zero Clearance Gas Fireplace Heater GAS FIRED Installer Leave this manual with...

Page 2: ...raming and Finishing 39 40 Horizontal Termination 41 DVVK 5F Flex Vent Instructions 42 Vertical Termination 43 Log Placement 4 Log Set 45 Operating Instructions 46 47 Standing Pilot Wiring Diagram 48...

Page 3: ...ries Theglassfrontoranypartremovedforservicingtheappliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean...

Page 4: ...m service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of...

Page 5: ...isions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minim...

Page 6: ...f local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from the American National Standards Institute Inc 11 West...

Page 7: ...rmostat TRW Millivolt REED SWITCH Wall Thermostat FWS 1 Direct Ignition Millivolt Wall Switch DVP42 DVP48 Input Btu hr Maximum 28 000 30 000 Btu hr Minimum millivolt only 19 000 20 500 KWH Maximum 8 2...

Page 8: ...er positions a minimum of 6 inches clearance must be maintained from the perpendicular wall and the front edge of the appliance Figure 2 Combustible Material No greeting cards stockings or ornamentati...

Page 9: ...5kPa Attention If one of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Pr...

Page 10: ...e flue pipe and discarded VENT SYSTEMS The following vent systems are acceptable for use with the DVP 42 48 series fireplaces Simpson Duravent GS 5 8 Refer to Page 36 American Metal Products 5 8 Selki...

Page 11: ...wall strip and then screw into pre drilled holes on fireplace side Measure from face of fireplace to face of drywall strip to determine final depth Figure 8 Vent Pipe Clearance Note Maintain one inch...

Page 12: ...erial must be used These joints are not required to be sealed Only non combustible material using 300 F minimum adhesive if needed can be applied as facing to the fireplace surround Flush Mount Mantel...

Page 13: ...l four 4 perimeter edges on the bottom of the unit VERTICAL 90 ELBOW WITH HORIZONTAL TERMINATION Figure 14 3 OF NON COMBUSTIBLE MATERIAL FINISHED WALL FRONT TRIM OR NON COMBUSTIBLE MATERIAL INSTALLATI...

Page 14: ...65mm DVP 42 48 9 229mm 8 1 8 206mm to 91 2 241mm DVP 42 12 305mm 11 1 8 283mm to 12 1 2 317mm DVP 42 A B C 6 152mm 11 1 4 286mm to 12 3 4 324mm 4 3 4 121mm to 6 1 4 159mm 9 229mm 14 1 4 362mm to 15 3...

Page 15: ...installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 degree elbows are installed on the vertical part of the vent system Reduce 3...

Page 16: ...7 178mm below grade level The 7 178mm is measured from the center of the horizontal vent pipe as it penetrates through the wall Ensure the sidewall venting clearances are observed If venting systemis...

Page 17: ...positioned in its permanent location the hole through the exterior wall of the house can be cut This hole must be 12 305mm high x 10 254mm wide with its center line determined by the amount of vertica...

Page 18: ...25664 0 0309 Page 18 Figure 26 Figure 27 Figure 28 24 24 MINIMUM CLEARANCE TO COMBUSTIBLES EXAMPLES TOP VENT RUN...

Page 19: ...25664 0 0309 Page 19 VENTING EXAMPLES WHEN USING DVA47 ADAPTOR Vertically Off Top of Fireplace Only Figure 29 Figure 30 Figure 31...

Page 20: ...alified field service person Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow In spect entire venting system to ensure proper function Pleas...

Page 21: ...ion Kit WARNING Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches 305mm above the roof WARNING Refer to your fireplace homeowner s manual f...

Page 22: ...enough to provide a mini mum 1 air space clearance from the vertical vent pipe to any combustible framing 6 Install the Firestop Thimble assembly to the framed opening in the ceiling using common nai...

Page 23: ...step 5 Feed the flex vent end down through the roof opening and firestop thimble assembly installed in steps 4 through 6 14 Secure the roof support assembly to the roof sheathing with at least 4 nail...

Page 24: ...ed as an attic insulation shield The collar can be installed around the flex pipe or hard pipe just above the firestop thimble This collar will act as a shield to prevent blown in sulation from enteri...

Page 25: ...ps As Req d Venting Support With Gasket Clamps 7 Dia Adapter Collar 4 Dia Flue Connector Assembly Firestop Thimble Adjustable Storm Collar Use TO Keep Insulation Out Of Inlet Vent Connections Clamps A...

Page 26: ...eter by 6 ft MF07ALA2F006 1 5 4 7 x 48 Rigid Pipe Assembly MF100554 1 6 Firestop Thimble Assembly MF100124 1 7 Roof Flashing 0 12 to 6 12 MF100091 1 8 7 Flex Adapter Collar with Gasket MF100524 1 9 7...

Page 27: ...sion and position the unit in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 12 feet 4 inches the horizontal run to the outer wall flange must not exceed 12 fee...

Page 28: ...25664 0 0309 Page 28 Figure 40 Figure 41 Figure 42 Figure 43 Model Maximum Pipe Length H1 DVP42 24 DVP48 18 Model Maximum Pipe Length H1 DVP42 24 DVP48 6 EXAMPLES REAR VENT RUN...

Page 29: ...hether or not the extension thimble is to be used If the combustible wall depth is over 5 3 8 137mm then the extension thimble should be used Figure 44 3 Install the wall thimble assembly through the...

Page 30: ...1 1 2 screws Ensure upward slope 11 From inside Attach the inlet tube to the collar on the back of the fireplace or the rigid venting system using 3 self tapping screws 12 Seal the 4 102mm diameter fl...

Page 31: ...gh temperature sealant to the opposite end of the tube on the inside of the tube The end with the gasket will attach to the back of the unit Continue with Step 13 Connecting to Rigid Vent System If th...

Page 32: ...e installed to the Termination Cap 10 Apply sealant to the outside of the flue pipe adapter and connect to the flex flue pipe Then insert the adapter into the fireplace flue Secure flue adapter to the...

Page 33: ...hat minimizes the number of offsets and horizontal vent length Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust certai...

Page 34: ...r line of the regulator I clearance to service regulator vent outlet 6 feet 1 8m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 1...

Page 35: ...Continueaddingcomponentsperthepre plannedventsystemconfiguration Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system WALL THIM...

Page 36: ...he vent pipe is now locked together Continue adding components per the pre planned vent system configuration Be certain that each succeeding vent component is securely fitted and locked into the prece...

Page 37: ...all for 10 3 8 inch x 12 3 8 inch hole Attention Wall firestop hole is off set towards bottom of wall opening Securewithnailsorscrews Continuetheventrunthrough the firestop See Figure 59 10 3 8 12 3 8...

Page 38: ...25664 0 0309 Page 38 Figure 60 Figure 62 See Horizontal Termination Page 41 and Vertical Termination Pages 43 and 44 Figure 61 8 VENTING FRAMING AND FINISHING continued...

Page 39: ...nch x 11 inch hole previously cut Secure with nails or screws The heat shields of the firestops MUST BE placed towards the top of the hole Continue the vent run through the firestops See Figure 64 10...

Page 40: ...25664 0 0309 Page 40 Figure 67 See Horizontal Termination Page 41 and Vertical Termination on Pages 43 and 44 6 VENTING FRAMING AND FINISHING continued Figure 65 Figure 66...

Page 41: ...e edge too so as to make a seal to the exterior wall NOTE Wood screws can and should be replaced with appropriate fasteners for use on stucco brick concrete or other types of siding CAUTION If exterio...

Page 42: ...ided See Figure 71 10 Attach the Outer Vent pipe to the 8 dia Collar on the fireplace with a large band clamp provided Sealant may also be used on the outer vent connections 11 Check all vent connecti...

Page 43: ...spect are as follows 1 Check areas of the venting system which are exposed to the elements for corrosion These will appear as rust spots or streaks and in extreme cases holes These components should i...

Page 44: ...uilding codes Therefore your local building codes must be checked to determine the requirements for these steps NOTE When installing this vent system in a chase it is always good building practice to...

Page 45: ...ver lift and pull forward 2 Lower bottom louver lift and hinge forward 3 Release two glass frame spring clamps at bottom of firebox 4 Place rear 1 log onto two 2 pins on rear log support 5 Place left...

Page 46: ...te an additional one 1 to two 2 minutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical current to build up to a suffi...

Page 47: ...s fail in the remote and immediate heat is desired turn the REMOTE OFF ON switch from the REMOTE position to the ON position Electric 120 volt Operated Remote Control FREC Connectthegreenandred stripp...

Page 48: ...25664 0 0309 Page 48 Figure 82 OPTIONAL THERMOSTAT OPTIONAL WALL SWITCH STANDING PILOT WIRING DIAGRAM...

Page 49: ...which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to smell next to the floor because some g...

Page 50: ...me Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take th...

Page 51: ...when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Providedontheintermittentpilotwiringharnessaretwo 2 stripped and bare wires th...

Page 52: ...pped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B Before lighting smell all around the appliance area for gas Be sure to smell next to the floor...

Page 53: ...n the gas line to the appliance D Do gas leak test ahead of gas control if piping has been disturbed Gas Leak Test Paint pipe joints with rich soap and water solution Bubbles indicate gas leak Tighten...

Page 54: ...IED Valves close Pilot and main burners are off START STAGE 1 Trial for Ignition STAGE 2 Main Burner Operation END S8600H NORMAL OPERATING SEQUENCE Pilot burner does not light Thermostat Wall Switch R...

Page 55: ...om ignition cable or other heavily insulated wire A Close the manual gas valve B Disconnect the ignition cable at the SPARK terminal on the module WARNING Whenperformingthefollowingsteps donottouchstr...

Page 56: ...25664 0 0309 Page 56 INTERMITTENT PILOT TROUBLESHOOTING continued...

Page 57: ...nor mal operation after a one minute delay ChecktransformerandAClineforproper input voltage to the control Check with full system load on the transformer 6 2 Failed trial for ignition resulting in loc...

Page 58: ...hermostat performance Flame cycles and modulates such that heat output equals heat loss from the room Auto mode Flame fan are controlled automatically Self powered millivolt control No external power...

Page 59: ...a heated living space to make sure that the main burner is not on continuously On Mode When the control is in the ON mode the flame and fan levels and the delay timer are changed with the UP and DOWN...

Page 60: ...25664 0 0309 Page 60 WIRING DIAGRAM WITH BLOWER Figure 85 RF WIRING DIAGRAM...

Page 61: ...to the appliance if applicable FOR YOUR SAFETY READ BEFORE LIGHTING WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR L...

Page 62: ...er airborne particles to cling to the glass surface Also initial paint curing may deposit a slight film on the glass It is therefore recommended that the glass be cleaned two or three times with a non...

Page 63: ...33 32 34 40 38 42 39a 36a 37a 41 52 39b 34 33 32 24 30 29 28 27 31 36b 44 46 37b 33 34 32 36c 37c 31 29 28 27 24 23 30 48 49 50 51 47 45 15 26 26 26 43 MILLIVOLT BURNER ASSEMBLY INTERMITTENT PILOT BUR...

Page 64: ...7162 JUNCTION BOX ASSEMBLY 14 R 3492 R 3492 RECEPTACLE 3 PRONG 15 17357 17357 JUNCTION BOX SHIELD 16 17445 17446 TOP SHIELD 17 17804 17805 INNER TOP HEAT SHIELD 18 17381 17447 BAFFLE FLUE VENT 19 1718...

Page 65: ...36c R 6115 R 6115 VALVE RF GAS LP 37a 17161 17161 VALVE BRACKET SIT 37b 17795 17795 VALVE BRACKET IP 37c 17796 17796 VALVE BRACKET RF 38 16223 16223 SPRING LATCH ASSEMBLY 39a R 3435 R 3435 WIRING HARN...

Page 66: ...ble speed blower assembly is completed Wiring The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Co...

Page 67: ...LT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN 1 FBB4 B L O W E R A S S E M B LY COMPLETE 2 R7649 FAN CONTROL 3 R4192 SPEED CONTROL KNOB 4 R4186 SPEED CONTROL FBB4 OPTIONAL VARIABL...

Page 68: ...on fireplace 3 Remove glass frame assembly from fireplace 4 Remove rear logs from burner assembly 5 Place brick panel rear against rear wall in fireplace Note The top edge will have a half moon cutou...

Page 69: ...d to enhance the appearance of your fireplace imitating the look of authentic masonry HERRINGBONE DVP3DH DVP42 DVP4DH DVP48 Simulated Brick Panels The simulated brick panels were designed to enhance t...

Page 70: ...Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites ww...

Page 71: ...25664 0 0309 Page 71 SERVICE NOTES...

Page 72: ...25664 0 0309 Page 72 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: