If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the gas quality or pressure is 

low, contact your local gas supplier immediately.

 

1.  When ignitor button is pressed, there is no spark at ODS/

pilot. 

a.  Ignitor electrode positioned wrong - Replace pilot.

b.  Ignitor electrode is broken - Replace pilot.

c.  Ignitor electrode not connected to ignitor cable - Reconnect 

ignitor cable.

d.  Ignitor cable pinched or wet. Keep ignitor cable dry - Free 

ignitor cable if pinched by any metal or tubing. 

e.  Broken ignitor cable - Replace ignitor cable.

  2.  Appliance produces unwanted odors.

a.  Appliance burning vapors from paint, hair spray, glues, 

etc. - Ventilate room. Stop using odor causing products 

while heater is running.

b.  Gas leak - Locate and correct all leaks.

  3.  Appliance shuts off during use. (Pilot and main burner 

are off.)

a.  Not enough fresh air is available for ODS/pilot to operate 

- Open window and/or door for ventilation.

b.  Low line pressure - Contact local gas company.

c.  ODS/pilot is partially clogged - Clean ODS/pilot.

d.  Defective thermocouple - Replace pilot.

  4.  Appliance shuts off during use. (Pilot stays on.)

a.  Low line pressure - Check line pressure to the valve.

b.  Defective  thermopile  -  Check  pilot  flame,  check  wire 

connections, output should be a minimum of 325 millivolts 

across. TH/TP  and TP  terminals  with  ON/OFF  switch 

off.

  5.  Gas odor even when control knob is in OFF position.

a.  Gas leak - Locate and correct all leaks.

b.  Control valve defective - Replace control valve.

  6.  When ignitor button is pressed, there is spark at ODS/pilot, 

but no ignition.

a.  Gas  supply  turned  off  or  manual  shutoff  valve  closed 

- Turn on gas supply or open manual shutoff valve.

b.  Control knob not in PILOT position - Turn control knob 

to PILOT position.

c.  Control  knob  not  pressed  in  while  in  PILOT  position 

- Press in control knob while in PILOT position.

d.  Air in gas lines when installed - Continue holding down 

control  knob.  Repeat  igniting  operation  until  air  is 

removed.

e.  ODS/pilot is clogged - Replace ODS/pilot assembly or 

have it serviced.

g.  Gas  regulator  setting  is  not  correct  -  Replace  gas 

regulator. 

  7.  ODS/pilot lights but flame goes out when control knob is 

released.

a.  Control knob not fully pressed in - Press in control knob 

fully.

b.  Control knob not pressed in long enough - After ODS/pilot 

lights, keep control knob pressed in 30 seconds.

c.  Manual Shutoff valve not fully open - Fully open manual 

shutoff valve.

d.  Thermocouple connection loose at control valve - Hand 

tighten until snug, then tighten 1/4 turn more.

e.  Pilot  flame  not  touching  thermocouple,  which  allows 

thermocouple to cool, causing pilot flame to go out. This 

problem could be caused by either low gas pressure or 

dirty or partially clogged ODS/pilot - Contact local gas 

company. 

f.  Control valve damaged - Replace control valve.

  8.  Burner does not light after ODS/pilot is lit.

a.  Burner orifice clogged - Clean burner or replace main 

burner orifice.

b.  Burner  orifice  diameter  is  too  small  -  Replace  burner 

orifice.

c.  Inlet gas pressure is too low - Contact qualified service 

person. 

  9.  If burning at main burner orifice occurs (a loud, roaring 

blow torch noise).

a.  You must turn off burner assembly and contact a qualified 

service person.

b.  Manifold  pressure  is  too  low  -  Contact  local  gas 

company.

c.  Burner orifice clogged - Clean burner or replace burner 

orifice.

 10.  Logs appear to smoke after initial operation.

a.  Vapors from paint or curing process of logs - Problem 

will stop after a few hours of operation. Open a window 

for the first few hours. 

  Log heater is intended to be smokeless. Turn OFF heater 

and call qualified service person.

 11.  Heater produces a whistling noise when main burner is 

lit.

a.  Turning control knob to HIGH position when main burner 

is cold - Turn control knob to LOW position and let warm 

up for a minute.

b.  Air in gas line - Operate burner until air is removed from 

line. Have gas line checked by local gas company.

c.  Dirty or partially clogged burner orifice - Clean burner or 

replace burner orifice.

 12.  No gas to pilot.

a.  LP-regulator shut down due to inlet pressure too high - 

Verify LP tank regulator is installed and set at 11" to 13" 

w.c. 

TROUBLESHOOTING

SYMPTOMS - POSSIBLE CAUSES AND CORRECTION

S

Turn appliance OFF and allow to cool before servicing. Only a qualified service person should service and repair the heater.

Summary of Contents for superb CHBR-16-3

Page 1: ...ted manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other...

Page 2: ...for Adequate Combustion and Ventilation Air 7 Clearances 8 Gas Supply 9 Set Up Instructions 10 Placement of Glowing Embers and Lava Rock 11 Operation Instructions Flame Appearance 12 Thermostat Opera...

Page 3: ...re and draperies Do not place clothing or other ammable material on or near the appliance Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid...

Page 4: ...lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption...

Page 5: ...r future reference Please read this manual before installing and using the appliance Instructions to Installer 1 Installer must leave instruction manual with owner after installation 2 Installermustha...

Page 6: ...fore you get started Carefully inspect the contents for shipping damage If any parts are missing or damaged immediately inform the dealer from whom you purchased the appliance Do not attempt to instal...

Page 7: ...installed measure the length width and height of the area Example The area measures 16 feet in length 12 feet in width and 8 feet in height the area is 1 536 cubic feet The CHBR 16 can be installed in...

Page 8: ...Page 8 16934 3 0806 CLEARANCES CLEARANCES Minimum Clearances From Combustible Construction Figures 2 and 3 Side 2 Rear 2 Top 24 Floor Combustible Figure 1 Figure 2...

Page 9: ...s capped on the bottom in which condensation and foreign particles may collect Figure 3 The use of the following gas connectors is recommended ANSZ21 24ApplianceConnectorsofCorrugatedMetalTubing and F...

Page 10: ...tion where it will t through the front door opening Guide the gas valve through the large hole in the bottom of the body casting The burner support plate will come to rest on the three at mounting tab...

Page 11: ...ddle logs Rock wool should not be placed in the area of the pilot assembly Replacement of loose material glowing embers must be purchased from Empire Comfort Systems Inc Application of excess loose ma...

Page 12: ...n to light maintain the standing pilot Low Minimum gas rate pleasing yellow ames glowing embers High Maximum gas rate pleasing yellow ames glowing embers Generator Ignition Piezo Ignitor allows lighti...

Page 13: ...ent to lowest setting If applicable Turn off all electric power to the heater Note For easy access to valve for lighting pilot remove branch log and middle log from burner assembly before lighting 1 S...

Page 14: ...ame Figure 8 If pilot ame pattern is incorrect as shown in Figure 8 See Troubleshooting page 17 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot Figure 9 When the pilot has a large yellow...

Page 15: ...hole Remove lint or particles with brush Failure to keep air intake hole clean will result in sooting and poor combustion ANNUALCLEANING INSPECTION Refer to parts diagram for location of items discus...

Page 16: ...te Receiver Figure 10 1 The remote receiver can be placed behind the gas valve on under side of chimenea 2 Attach remote receiver to the at bottom of casing behind gas valve on underside of chimenea R...

Page 17: ...mbly or have it serviced g Gas regulator setting is not correct Replace gas regulator 7 ODS pilot lights but ame goes out when control knob is released a Control knob not fully pressed in Press in con...

Page 18: ...STING ASSEMBLY GREEN INCLUDES STACK CASTING R 6476 KNOB GREEN R 6474 CAP GREEN 2 R 6641 MOUNTING RING RED 2 R 6642 MOUNTING RING GREEN 3 R 6479 CHIMENEA BODY CASTING ASSEMBLY RED INCLUDES BODY CASTING...

Page 19: ...Page 19 16934 3 0806 PARTS VIEW...

Page 20: ...20 16934 3 0806 SERVICE NOTES Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort...

Reviews: