background image

30816-1-0912

Page 9

3.  Add the BTU/Hr of all fuel burning appliances in the space.

 Vent-free heater    

 BTU/Hr

 Gas water heater  

 BTU/Hr

 Gas  furnace 

 

 BTU/Hr

 Vented gas heater 

 BTU/Hr

 Gas fireplace logs 

 BTU/Hr

 Other gas appliances*  +   

 BTU/Hr

 Total 

 

 BTU/Hr

Example:  Vented gas heater  

20,000 

BTU/Hr

  

  Vent-free heater  

18,000 

BTU/Hr

  

  Total 

 

38,000 

BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4.  Compare the maximum BTU/Hr the space can support with the 

actual amount of BTU/Hr used.

 

 BTU/Hr (maximum the space can support)

 

 BTU/Hr (actual amount of BTU/Hr used)

  Example: 

    25,600 

BTU/Hr (maximum the space can support)

    38,000 

BTU/Hr (actual amount of BTU/Hr used)

 

WARNING

If the area in which the heater may be operated is smaller than that 

defined as an unconfined space or if the building is of unusually 

tight construction, provide adequate combustion and ventilation 

air by one of the methods described in the National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation, 

or applicable local codes.

The space in the above example is a confined space because the 

actual BTU/Hr used is more than the maximum BTU/HR the space 

can support. You must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an adjoining room. If 

the extra space provides an unconfined space, remove door 

to adjoining room or add ventilation grills between rooms. See 

Ventilation Air From Inside Building.

 

B.  Vent room directly to the outdoors. See 

Ventilation Air From 

Outdoors.

C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes room 

unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

 

WARNING

You must provide additional ventilation air in a confined 

space.

This heater shall not be installed in a confined space or unusu

-

ally tight construction unless provisions are provided for adequate 

combustion and ventilation air.
A confined space is an area with volume less than 50 cubic feet per 

1,000 Btuh of the combined input rates of all appliances drawing 

combustion air from that space. Small areas such as equipment 

rooms are confined spaces. Furnaces installed in a confined space 

which supply heated air to areas outside the space must draw return 

air from outside the space through tightly sealed return air ducts. A 

confined space must have 2 openings into the space for combus

-

tion air. One opening must be within 12 inches of the ceiling and 

the other must be within 12 inches of the floor. The required sizing 

of these openings is determined by whether inside or outside air is 

used to support combustion, the method by which the air is brought 

to the space (vertical or horizontal duct) and by the total input rate 

of all appliances in the space.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

 

Unusually  tight  construction  is  defined  as  construction 

where:

a.  Walls and ceilings exposed to the outside atmosphere have 

a continuous water vapor retarder with a rating of one perm 

or less with openings gasketed or sealed, and

b.  Weatherstripping has been added on openable windows and 

doors, and

c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 

around window and door frames, between sole plates and 

floors, between wall-ceiling joints, between wall panels, at 

penetrations for plumbing, electrical, and gas lines, and at 

other openings.

  If your home meets all of the three criteria above, you must provide 

additional fresh air. See 

“Ventilation Air From Outdoors,”

 page 

10.

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined 

space.  

 

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.
1. Determine the volume of the space (length x width x height).

  Length x Width x Height = 

 cu. ft. (volume of 

space)

Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling 

height) = 1,280 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space.

2.  Divide  the  space  volume  by  50  cubic  feet  to  determine  the 

maximum BTU/Hr the space can support.

 

 (volume of space) ÷ 50 cu. ft. = (maximum 

BTU/Hr the space can support)

Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 

25,600 (maximum BTU/Hr the space can support)

pROVISIONS FOR ADEqUATE COMBUSTION & VENTILATION AIR

Summary of Contents for P)-2VFD26FM20NN-2

Page 1: ...phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and...

Page 2: ...10 000 BTU MILLIVOLT LIGHTING INSTRUCTIONS 19 MILLIVOLT LIGHTING INSTRUCTIONS 20 INTERMITTENT PILOT LIGHTING INSTRUCTIONS 21 HYDRAULIC THERMOSTAT LIGHTING INSTRUCTIONS 22 PILOT FLAME CHARACTERISTICS...

Page 3: ...all not be installed in a bedroom or bathroom Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Children and adults should be alerted to the...

Page 4: ...this occurs some new internal rusting could occur If the valve is left open then treat the container as a new tank Always be sure your container is under vapor pressure by turning it off at the conta...

Page 5: ...t in sooting and property damage Instructions to Installer 1 Installer must leave instruction manual with owner after installation 2 Installer must have owner fill out and mail warranty card supplied...

Page 6: ...shown in Figure 2 for corner rough opening Be sure to provide gas line for fireplace and electrical power for optional blower assembly 1 Attach two nailing flanges to firebox sides with two 10 x 1 2 s...

Page 7: ...NE OPENING JUNCTION BOX ASSEMBLY GAS LINE OPENING J I K B C G A D E Figure 4 VFD26 Series Dimensions Index Letter Dimension A 30 1 4 768mm B 30 762mm C 13 1 8 333mm D 18 1 8 460mm E 26 660mm G 25 635m...

Page 8: ...rmostat FREC Electric Remote Control FWS 1 Wall Switch TMV Wall Thermostat Millivolt Reed Switch TRW Wireless Remote Wall Thermostat Water vapor is a by product of gas combustion An unvented room heat...

Page 9: ...are confined spaces Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts A conf...

Page 10: ...iling and one with 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces In most cases for direct communication with...

Page 11: ...Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a flex ible appliance connector cannot exceed three feet in l...

Page 12: ...the top of the fireplace opening to the ceiling should not be less than 36 inches Mantel Clearances for Built in Installation Figure 9 Do not attach combustible material to the mantel of your firepla...

Page 13: ...Remove shrink wrap and logs from fireplace 6 Place back base and fireplace in desired location 7 Connect gas line and electrical wiring at this time in accor dance with local codes ELECTRICAL CONNECT...

Page 14: ...ogs per the Log Placement Instructions See Page 16 14 Install hood See Page 15 9 Attach mantel assembly to studs in the wall through the back brace using two 3 drywall screws provided 10 Slide front b...

Page 15: ...holes in fireplace Attach top frame to fireplace Use two 8 x 1 2 Phillips screws for top frame 5 Replace bottom louver 6 Replace top louver 3 PIECE FRAME KIT SIDE TRIM HOOD INSTRUCTIONS 1 Remove uppe...

Page 16: ...his step is optional for VFD26FP3L10 log sets Place front twig 5 onto 1 log and flat area on 3 log The bottom of the front twig is to be placed behind the grate tang that is second from the left Atten...

Page 17: ...etween the front and middle logs Rock wool should not be placed in the area of the pilot assembly Glowing embers rock wool can cover the burner in between the front and middle logs but very little is...

Page 18: ...r location of items discussed below Do not use cleaning fluid to clean logs or any part of heater Logs brush with soft bristle brush or vacuum with brush attachment Remove loose particles and dust fro...

Page 19: ...tom louver assembly if applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob...

Page 20: ...f applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned fro...

Page 21: ...R YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a...

Page 22: ...liance 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable Lighting Instructions 7 Turn gas control knob counterc...

Page 23: ...e incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut down MILLIVOLT Pilot Correct Pilot Flame Pattern Figu...

Page 24: ...he Oxygen Depletion Sensor as follows 1 Clean the ODS pilot by loosening nut B from the pilot tubing When this procedure is required grasp nut A with an open end wrench 2 Blow air pressure through the...

Page 25: ...setting Cleaning and Maintenance Main Burner WARNING Turn off heater and let cool before cleaning CAUTION You must keep control areas burner and circulating air passageways of heater clean Inspect th...

Page 26: ...urner assembly NOTICE Do not let remote control receiver come in contact with burner assembly On circulating vent free firebox install remote control receiver behind bottom louver Refer to remote cont...

Page 27: ...f Gas regulator setting is not correct Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Cont...

Page 28: ...the appliance 2 During the operating season or in power outage periods it is recommended that the pilot remain in the CPI standing pilot mode to reduce cold start issues and or conserve battery backu...

Page 29: ...t is used CAUTION Do not operate the appliance with panel s removed cracked or broken Replacement of the panel s should be done by a licensed or qualified service person WARNING Improper installation...

Page 30: ...ore proceeding with the procedures in the following trouble shooting table verify that the power supply AC DC adapter is present and that the batteries inside the receiver and or optional battery pack...

Page 31: ...ire harness 4 Replace the DFC board 1 Verify the electrical connections integrity and make sure they are in accordance with the relevant system wiring diagram If necessary replace the wire harness 2 I...

Page 32: ...and verify voltage at ignition between the EV1 terminal and the ground connection on the valve body 5 1 If the voltage is greater than 0 then Replace Valve 5 2 Or Replace DFC 6 Check the pressure at...

Page 33: ...ODE ANSI NFPA 70 LAT EST EDITION A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached to the receptacle that is prov...

Page 34: ...REGULATOR LPG 29 R2708 IGNITOR PIEZO VFD26F M P 30L N P 10 R3623 PILOT ASSEMBLY LPG 10 R3624 PILOT ASSEMBLY NAT 11 21590 PILOT BRACKET LPG 11 23106 PILOT BRACKET NAT 12 23449 PILOT SHIELD 14 R9022 BUR...

Page 35: ...LEX WITH SHUT OFF VFD26F M P 70L10 N P 10 R11327 PILOT ASSEMBLY LPG 10 R11328 PILOT ASSEMBLY NAT 11 30703 PILOT BRACKET LPG 14 27426 BURNER TUBE 16 P214 ORIFICE NAT 16 P193 ORIFICE LPG 18 30704 BURNER...

Page 36: ...MBL INTERMITTENT PILOT VALVE A Y SSEMBL VFD26F M P 2 3 VFD26F M P 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 22 20 21 18 23 24 25 26 30 41 42 43 44 45 1 1 1 THERMOSTATIC VALVE Y ASSEMBL 22 20 21 23 2...

Page 37: ...The magnets on the bottom of speed control will sufficiently hold the speed control in place 13 Attach fan control bracket to upper right side of firebox with one 10 x 1 2 hex screw provided See Figu...

Page 38: ...PEED CONTROL FAN SWITCH GROUND BLACK FAN WHITE BLACK SWITCH BRACKET FBBX Wiring Diagram FBBX BLOWER KIT EXTENSION INSTALLATION INSTRUCTIONS FBB4 OPTIONAL VARIABLE SPEED BLOWER 1 18858 Blower Base 2 R7...

Page 39: ...one side panel into firebox 5 Align clearance hole on brick panel bracket with screw hole in the left or right interior top of firebox Use two 10 x 1 2 screws to attach brick panel bracket to interior...

Page 40: ...reet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTR...

Page 41: ...of defective workmanship within one year from the date of purchase Empire will repair or replace at Empire s option Duties Of The Owner The appliance must be installed by a qualified installer and op...

Page 42: ...30816 1 0912 Page 42 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 43: ...30816 1 0912 Page 43 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 44: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: