Empire Comfort Systems Inc. • Belleville, IL
The main burner flame and pilot flame must be checked for
proper flame characteristics, as outlined in the Installation
Instructions and Owner's Manual.
VERIFYING INPUT RATE OF CONVERTED APPLIANCE
The input of the appliance must be checked as follows:
1. Turn off all other gas appliances. Clock the gas meter and
determine the number of seconds required to consume one
cubic foot of gas.
2. 3600 ÷ time (in seconds) = cu. ft. per hour.
3. Then cu. ft. per hour x heating value of gas = input rate (Btuh).
On installation without gas meters, check manifold for proper
pressure.
PLACEMENT OF CONVERSION LAbELS
1. Conversion label R1322 is to be placed in a location visible
when all appliance panels are installed.
2. Gas conversion label R1321 is to be placed near the gas valve.
If appliance is not installed or warranty card has not been returned
to Empire Comfort Systems, Inc., check off type of gas converted
to on card. Also, indicate conversion by adding “Conv.” behind gas.
The main burner flame and pilot burner flame must be checked
for proper flame characteristics, as outlined in the Installation
Instructions and Owner’s Manual.
VERIFYING INPUT RATE OF CONVERTED FIREPLACE
The input of the fireplace must be checked as follows:
1. Turn off all other gas appliances. Clock the gas meter and
determine the number of seconds required to consume one
cubic foot of gas.
2. 3600 ÷ time (in seconds) = cu. Ft. per hour.
3. Then cu. Ft. per hour x heating value of gas = input rate
(Btuh). On installation without gas meters, check manifold
for proper pressure.
If fireplace is not installed or warranty card has not been returned
to Empire Comfort System’s, Inc., check off type of gas converted
to on card. Also, indicated conversion by adding “Conv.” behind
type of gas.