background image

19563-4-0610

Page 3

•  Due to high temperatures the appliance should be located 

out of traffic and away from furniture and draperies.

•  Children and adults should be alerted to the hazards of 

high surface temperatures and should stay away to avoid 

burns or clothing ignition.

•  Young children should be carefully supervised when they 

are in the same room as the appliance.

•  Clothing or other flammable material should not be placed 

on or near the appliance.

•  Any  safety  screen  or  guard  removed  for  servicing  an 

appliance  must  be  replaced  prior  to  operating  the 

appliance.

•  Keep burner and control compartment clean.  
•  Vent cap hot while furnace is in operation.
•  For manufactured home (USA only) or mobile home or 

residential installation convertible for use with natural gas 

and liquefied petroleum gases when provision is made for 

the simple conversion from one gas to the other. 

• 

Installation and repair should be done by a qUALIFIED 

SERVICE PERSON.   The appliance should be inspected 

before use and at least annually by a qualified service person.  

More frequent cleaning may be required due to excessive 

lint from carpeting, bedding materials, etc.  It is imperative 

that control compartments, burners and circulating air 

passageways of the appliance be kept clean.

•  Do not 

put anything around the furnace that will obstruct 

the flow of combustion and ventilation air.

•  Do

 keep the appliance area clear and free from combustible 

material,  gasoline  and  other  flammable  vapors  and 

liquids.

•  Do

  examine  venting  system  periodically  and  replace 

damaged parts.

•  Do 

make a periodic visual check of burner.  Clean and 

replace damaged parts.

•  Do not 

use this heater if any part has been under water.  

Immediately call a qualified service technician to inspect 

the heater and to replace any part of the control system 

and any gas control which has been under water. 

THIS IS A HEATING APPLIANCE

DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.

IMPORTANT SAFETY INFORMATION

Summary of Contents for DV-55E-5

Page 1: ...Canada This appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance Consumer Ret...

Page 2: ...ts for Massachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 11 Lighting Instructions 12 Wiring 13 Maintenance 14 Operation and...

Page 3: ...other Installation and repair should be done by a qualified service person The appliance should be inspected beforeuseandatleastannuallybyaqualifiedserviceperson More frequent cleaning may be require...

Page 4: ...pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or ads...

Page 5: ...equiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the ext...

Page 6: ...t shall be performed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible...

Page 7: ...let of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed...

Page 8: ...supply to furnace is off prior to conversion and disconnect electrical power to unit 2 Open brass union located between the gas valve and burner box Remove the 4 mounting screws securing manifold pla...

Page 9: ...de Warning The nearest point of the vent cap should be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will...

Page 10: ...in wall if plastic anchors are used Attach the two wall mounting brackets to the casing back by using 4 10 x 1 2 13mm hex head screws provided Figure 5 Figure 6 Figure 7 Figure 8 2 51mm TO 13 330mm 2...

Page 11: ...6 To attach the right shroud and left shroud to the casing back the 3 4 wide flange on the shroud must be positioned toward the casing side When positioned correctly the 6 louvers on the shroud will b...

Page 12: ...system and any gas control which has been under water 1 Stop Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance i...

Page 13: ...talled turn off gas supply and electric supply 2 Remove casing front 3 Remove black hose from front nipple on pressure switch 4 Remove junction box cover 4 screws 5 Please refer to wiring diagram for...

Page 14: ...m gas valve 4 Remove gas valve from gas valve bracket Removing Main Burner Orifice s 1 Remove front grill assembly 2 Remove burner compartment access panel 2 screws 3 Disconnect manifold union assembl...

Page 15: ...o the W terminal on the board The inducer blower circuit is energized and the inducer blower comes on for 15 seconds pre purging out any gas and closing the pressure switch The hot surface ignitor is...

Page 16: ...ashes Pressure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far from...

Page 17: ...EQUIRED 11 R 2663 BLOWER WHEEL 2 REQ 12 R 2662 BLOWER MOTOR 13 R 2598 MOTOR BASE WASHER 4 REQ 14 R 1279 LIMIT SWITCH 15 DV 1367 INNER TOP 16 R 2546 CONTROL KNOB 17 R 2522 ON OFF SWITCH 18 19561 JUNCTI...

Page 18: ...19563 4 0610 Page 18 PARTS VIEW...

Page 19: ...19563 4 0610 Page 19 SERVICE NOTES...

Page 20: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Page 21: ...t peut vous ex poser des mati res contenues dans le carburant ou provenant de la combustion du carburant lesquelles peuvent causer la mort ou de s rieuses maladies Ne pas entreposer ni utiliser d esse...

Page 22: ...en Gaz 6 Les Instructions Pour La Conversion des Gaz 7 Espaces Libres 8 Installation du Radiateur 8 10 Instructions d Allumage 11 Installation lectrique 12 Maintenance 13 Fonctionnement et D tection d...

Page 23: ...stallation et la r paration doivent tre faites par une PERSONNE QUALIFI E L appareil doit tre inspect avantl usageetaumoinsunefoisparann e parunepersonne qualifi e S il y a un exc s de poussi re venan...

Page 24: ...orte que vous ne pouvez pas d celer l odeur du propane en cas de fuite L affaiblissement d odeur attribuable l oxydation par la rouille oul adsortionsurlesparoisdesnouveauxr servoirsetbouteilles est p...

Page 25: ...s de fa on ce qu un v hicule en se d pla ant ne puisse les endommager AGENCE D INSTALLATION QUALIFI E L installationetleremplacementdestuyaux gaz des quipements ou accessoires la r paration et l entre...

Page 26: ...les Si les connexions ne sont pas expos es un test de pression doit tre fait Ne jamais employer une flamme pour v rifier les fuites Lors d untestdepression letuyaud arriv edelavalvedecommande doit tre...

Page 27: ...re faite par un technicien d entretien qualifi Les orifices du br leur principal et la nouvelle tiquette pour le changement des gaz sont fournis dans l ensemble de conversion qui est attach au tuyau d...

Page 28: ...du r gulateur de pression Dans le cas d un malfonc tionnement du r gulateur la distance de 6 1 83m r duira la possibilit pour le gaz d entrer par le capuchon de l vent Installation sur un Tapis ou Tu...

Page 29: ...enting Figures 7 and 8 Figure 5 TAPE 1 TAPE 2 TAPE 3 BLINDAGE DU DESSUS COUDE D VACUATION AVEC COLLIER DE SERRAGE ALLANT VERS LE BAS 2 51mm 13 330mm POUR L ENSEMBLE D VENT STANDARD 2 51mm 32 813mm AVE...

Page 30: ...i arri re le rebord de la paroi de 3 4 de largeur doit tre positionn vers la paroi de c t Lorsqu elle est bien positionn e les 6 volets de la paroi seront vers le haut et l entr e d fon able sera vers...

Page 31: ...teur et remplacer toute pi ce du syst me de commande et les commandes de gaz qui ont t en contact avec l eau 1 Arr ter Lire les informations de s curit ci dessus 2 Mettre le thermostat son plus bas r...

Page 32: ...anostat enlever le tuyau noir 4 Enlever le couvercle de la bo te de jonction 4 vis 5 S il vous pla t r f rez vous au sch ma de l installation lectrique pour enlever les fils suivants 6 Thermostat lect...

Page 33: ...ux fils de 24 volt Identifier les fils avant de les d brancher de la valve de gaz 4 Enlever la valve de gaz du support de la valve de gaz Enlever les Orifices du Br leur Principal 1 Enlever l assembla...

Page 34: ...at int gral 24 VAC est appliqu la borne W sur le tableau Le circuit d induction pour la soufflerie est aliment et l inducteur delasouffleriesemetenmarchepour15secondespurgeanttout gaz et fermant l int...

Page 35: ...est ferm avec la soufflante d induction arr t e Contr ler et changer le manocontact 4 clignotements Verrouillage caus par l absence d allumage Contr ler l tat de l allumeur V rifier le bon tat du sup...

Page 36: ...identification de l appareil Puis en vous r f rant l illustration et la liste des pi ces d terminer le num ro de la pi ce pas le num ro d index et la description de chaque pi ce Soyez certain de donne...

Page 37: ...19563 2 0907 Page 17 VUE DES PI CES...

Page 38: ...19563 2 0907 Page 18 NOTES DE SERVICE...

Page 39: ...19563 2 0907 Page 19 NOTES DE SERVICE...

Page 40: ...19563 2 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: