Functional description
CG Drives & Automation 01-7491-01r0
Reference control [214]
To control the speed of the motor, the AC drive needs a
reference signal. This reference signal can be controlled by a
remote source from the installation, the keyboard of the
AC drive, or via communication (RS-485, Fieldbus, or
Wireless interfaces). Select the required reference control for
the application in this menu
.
Run/Stop Control [215]
This function is used to select the source for run and stop
commands. This is described on page 132.
Start/stop via analogue signals can be achieved by using
function “Stp<MinSpd [342]”.
Reset Control [216]
When the AC drive is stopped due to a failure, a reset
command is required to make it possible to restart the AC
drive. Use this function to select the source of the reset
signal.
214
Ref control
Default:
Remote
Remote
0
The reference signal comes from the
analogue inputs of the terminal strip
(terminals 1-22).
Keyboard
1
Reference is set with the + and - keys on
the Control Panel. Can only be done in
menu “Set/View reference [310]”.
Com
2
The reference is set via communication
(RS-485, Fieldbus, or Wireless interfaces).
See section 9.5, page 82 for further
information.
Option
3
The reference is set via an option. Only
available if the option can control the
reference value.
NOTE: If the reference is switched from Remote to
Keyboard, the last remote reference value will be the
default value for the control panel.
NOTE: Drive should be stopped in case configured
source of reference or run/stop control is lost, e.g.
due to communication errors. Hence, it is highly
recommended to use the available mechanisms to
monitor the communication between the AC drive
and the controlling equipment.
See the following menus for more information:
Keyboard [2645] and [2646]
Communication: RS-485 [262], Fieldbus [263],
Wireless [270]
215
Run/Stp Ctrl
Default:
Remote
Remote
0
The start/stop signal comes from the digital
inputs of the terminal strip (terminals 1-22).
For settings, see menu group [330] and
[520].
Keyboard
1
Start and stop is set on the Control Panel.
Com
2
The start/stop is set via
communication, i.e. via RS-485, Fieldbus,
or wireless interface. See Fieldbus or RS-
232/485 option manual for details and
chapter 9.4 Start and stop commands
page 82.
Option
3
The start/stop is set via an option.
216
Reset Ctrl
Default:
Remote
Remote
0
The command comes from the inputs of
the terminal strip (terminals 1-22).
Keyboard
1
The command comes from the
command keys of the Control Panel.
Com
2
The command comes from the wireless
communication (RS-485, Fieldbus).
Keyb
3
The command comes from the inputs of
the terminal strip (terminals 1-22) or the
keyboard.
Com +
Keyb
4
The command comes from the wireless
communication (RS485, Fieldbus) or the
keyboard.
Rem+Keyb
+Com
5
The command comes from the inputs of
the terminal strip (terminals 1-22), the
keyboard or the wireless communication
(RS485, Fieldbus).
Option
6
The command comes from an option.
Only available if the option can control
the reset command.
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......