132
Functional description
CG Drives & Automation 01-7491-01r0
11.3.5 Speed [340]
Menu with all parameters for settings regarding to speeds,
such as Min/Max speeds, Jog speeds, Skip speeds.
Sets the minimum speed. The minimum speed will operate
as an absolute lower limit. Used to ensure the motor does
not run below a certain speed and to maintain a certain
performance.
Stop/Sleep when less than
Minimum Speed [342]
With this function it is possible to put the AC drive in “sleep
mode” when it is running at minimum speed for the length
of time set in menu “Stp<MinSpd [342]”. The AC drive will
go into sleep mode after programmed time.
When the reference signal or PID Process controller output
value (if PID Process controller is used) raises the required
speed value above the min speed value, the AC drive will
automatically wake up and ramp up to the required speed.
Fig. 109
If you want to use this function when having “process
reference” signal via an analogue input, you need to make
sure that the concerning analogue input is set up correct,
meaning that AnIn Advanced parameter "AnIn1 FcMin
[5134]" should be set from "Min" (=default) to
"User defined" and “AnIn1 VaMin[5135]” set to a value less
than “Min Speed [341]” to make it possible that the
analogue input reference can go below the "Min Speed" level
to activate the “Sleep mode”. This applies when PID Process
controller is not used
.
Sets the maximum speed. The maximum speed will operate
as an absolute maximum limit. This parameter is used to
prevent damage due to high speed.
The synchronous speed (Sync-spd) is determined by the
parameter motor speed [225].
341
Min Speed
Default:
0 rpm
Range:
0 - Max Speed
Dependent
on:
Set/View ref [310]
NOTE: A lower speed value than the set minimum
speed can be shown in the display due to motor slip.
Min
[342]
speed
Speed
Time
= Speed + Reference
= Reference
= Speed
[341]
NOTE: If [381] PID Process controller is used, then
the PID sleep functionality [386] - [389] is
recommended instead of [342]. See further page 138.
NOTE: Menu [386] has higher priority than menu
[342].
342
Stp<MinSpd
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
343
Max Speed
Default:
Sync Speed
Sync Speed
0
Synchronous speed, i.e. no load
speed, at nominal frequency.
1-35940rpm 1-
35940
Min Speed - 4 x Motor Sync
Speed
NOTE: It is not possible to set the maximum speed
lower than the minimum speed.
Note: Maximum speed [343] has priority over Min
Speed [341], i.e. if [343] is set below [341] then the
drive will run at [343] Max Speed with acceleration
times given by [335] and [336] respectively.
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......