27
GB
2. Parameter lists in CRONO-TH
The full list of parameters is divided into two different menus: “Set Menu” and “Prg Menu”
2.1
Set Menu
Set Menu parameters list:
Par Icona Label
Description
U.M.
Range
Default
min
max
405
SEt Room set point in cooling mode (Comfort temperature)
°C
15
30
24
202
SEt Room set point in heating mode (Comfort temperature)
°C
5
30
20
201
Att Attenuation value on Room set point in cooling mode
°C
1
10
6
203
Att Attenuation value on Room set point in heating mode
°C
1
10
4
122
ESA DHW Production: On: Enabled / Off: Not enabled
-
Off
On
On
126
SEt DHW Set point (Storage tank)
°C
10
60
50
119
SrH Room humidity set point
%
30
90
60
103
OUt Outdoor air temperature
°C
--
-
Read Value
109
OUtu Outlet water temperature from heating pump
°C
--
-
Read Value
111
Inu Inlet water temperature from heating pump (see page 111
INSTALLATION AND USE MANUAL)
°C
--
-
Read Value