4.2.3 Engine

ENABL/DISBL

Sec

Min

Default Unit

ENGINE START OPTIONS (

)

Engine->Starting options

Max

Audible Alarm Prior To Starting En/Dis
Number Of Start Attempts

Cranking Time

Crank Rest Time

DISBL

3

5

1
1

10
99

10

5

99

Pickup Sensor Fail Delay

3.0

0.1

10.0

Horn prior start
No. of crank attemp
Cranking time
Crank rest time
Pickup fail dely*

3

Sec
Sec

10

Note:

*

3

= This parameter is only available at Trans-MidiAUTO.MPU

dis = disable

Min

Default

Unit

ENGINE SPEED SETS (

)

Engine->Speed settings

Max

Engine Under Speed Shutdown

Engine Under Speed Prealarm

Engine Under Speed Prealarm Reset

dis

Engine Over Speed Shutdown

500(dis) 5000
500(dis)

RPM

500

500 5000

Engine Over Speed Prealarm Reset

Engine Speed Shutdown Delay Time

500

1.0

RPM

RPM
RPM
RPM
RPM

Sec

5000

500(dis) 5000

5000
5000

10.0

Engine Over Speed Prealarm

Under speed shutdown
Under speed prealarm
Under speed reset
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time

500

0.0

Nominal Speed

1500

500 5000

RPM

Nominal speed

dis

dis
dis

500(dis)

Min

Default

Unit

ENG. CRANK DISCONNECT (

)

Engine->Crank disconnect

Max

Crank Disconnect On Gen. Frequency

Crank Disconnect On Gen. Voltage
Crank Disconnect On Charge Alt. Voltage

30.0

Crank Disconnect On Oil Pressure En/Dis

Crank Disconnect On Oil Pressure Value

Check Oil Pressure Before Start

10.0 75.0

Hz

500

100

1.0

6000

RPM

300

60 (dis) 600

V

V

dis

6.0 (dis) 30.0

V

Z

1.0

30.0

BAR

Generator frequency
Engine speed
Generator volt
Charge alt. volt
Oil pres. enab./dis.
Oil pressure value
Check oil befor.start

Crank Disconnect On Engine RPM

ENABL/DISBL DISBL

ENABL/DISBL ENABL

Min

Default

ENGINE PLANT BATTERY (

)

Engine->Plant battery

Max

Battery Undervolts Warning

Battery Undervolts Shutdown

Battery Undervolts Warning Reset

Battery Undervolts Volts Delay

Battery Overvolts Warning

Battery Overvolts Shutdown

11.0

dis

Battery Overvolts Warning Reset

6.0(dis)

6.0(dis)

30.0

30.0

11.5

6.0

1.0

0.0

9.9

29.0

dis

28.5

Charge Alternator Warning

dis

30.0

30.0

30.0

6.0 30.0

Battery Overvolts Delay

1.0

0.0

9.9

30.0

6.0(dis)

6.0(dis)

6.0(dis)

Under volt warning

Under volt shutdown

Under volt reset
Under volt delay

Over volt warning

Over volt shutdown

Over volt reset
Over volt delay
Alt. chg. warning

Unit

V

Z

V

Z

V

Z

V

Z

V

Z

V

Z

Sec

Sec

V

Z

Summary of Contents for Trans-midiAUTO.CAN.232.GPRS

Page 1: ...hanical reliability of the device Use a cloth dampened in ethyl alcohol or water to clean the external plastic case 1 Introduction 1 1 General Specifications The unit provides automatic start and stop...

Page 2: ...ning installation of this product please read the instruction manual and warnings below carefully 2 Installation indekiler 2 1 Unit Configuration indekiler 2 2 Panel Mounting The unit is designed for...

Page 3: ...l Sender or Configurable Analog Input Temperature Sender Oil Sender 36 35 18 19 BATTERY BATTERY 38 Sender Common 21 20 16 17 15 22 RX TX RS 232 J1939 ECUs 34 BATTERY 33 32 31 30 29 High Temperature or...

Page 4: ...setting Technician setting Factory adjustment TECHNICIAN SETTING Password 0162 TECHNICIAN SETTING Password 0000 TECHNICIAN SETTING System Generator Engine Inputs TECHNICIAN SETTING System Generator E...

Page 5: ...delay time Unit GENERATOR LEVEL FREQ Generator level Frequency 75 0 75 0 Hz 30 0 Nominal Alternator Frequency 50 0 43 0 Hz Nominal frequency Under freq shutdown Generator Under Frequency Shutdown 30...

Page 6: ...to Scroll Number Scroll Time For Error Messages 0 0 dis 250 Sec 5 18 2 1 250 Auto scroll number 1 Err mesg scroll time Auto scroll time Sec 1 ENGLISH ENA DISBL BL DISBL Min Default Unit BREAKERS Syste...

Page 7: ...ings Max Save setting to default Reset default sets Save setting to def Reset default sets YES NO NO Reset factory sets Reset factory sets YES NO NO YES NO NO Min Default Unit COMMUNICATION System Com...

Page 8: ...t Max Generator Under Current Pre Alarm Reset Generator Under Current Actions Delay Time Generator Current Over IDMT Alarm Generator Over Current Set Generator Over Current Pre Alarm Generator Over Cu...

Page 9: ...rse power set Reverse power act Rv pow act delay time GEN LEVEL POWER Generator Power level Generator Under Delay Time Power Action 0 dis 0 3 99 0 dis 2 Sec Generator Under Actions Disable Warning Ala...

Page 10: ...dis Min Default Unit ENG CRANK DISCONNECT Engine Crank disconnect Max Crank Disconnect On Gen Frequency Crank Disconnect On Gen Voltage Crank Disconnect On Charge Alt Voltage 30 0 Crank Disconnect On...

Page 11: ...alue 0 100 Speed set point 1500 1500 1800 Speed Set Point Selection RPM ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL DISBL Baud Rate 0 20 1 50 2 100 3 125 4 250 5 500 6 800 7 1 000 J193...

Page 12: ...enerator Followed By Shutdown After Cooling 4 Shutdown Alarm And Shutdown 2 0 2 0 0 dis 4 Amber warn activation Amber warn actions Sec J1939 Amber Warning Lamp Delay 2 0 250 Amber warn delay J1939 Amb...

Page 13: ...day 1 Start time on monday 2 Start time on monday 3 Start time on monday 4 Stop time on monday 1 Stop time on monday 2 Stop time on monday 3 Stop time on monday 4 Start time on tues 1 Start time on tu...

Page 14: ...on day 4 Satur Exercise Stop Time on day 1 Sun Exercise Stop Time on day 2 Sun Exercise Stop Time on day 3 Sun Exercise Stop Time on day 4 Sun Start time on day 1 fri Start time on day 2 fri Start tim...

Page 15: ...pres sensor break Oil press input type 0 dis 60 0 dis 70 Low Temperature Warning C Low temp warning Conf AI1 unit Configurable Analog Input 1 Type Conf AI1 low shutdwn 0 dis 0 Not Used Disable 1 Digit...

Page 16: ...e Analog Input 1 control OFF 3000 0 dis 0 dis 3000 Conf AI1 control ON Configurable Analog Input 1 control ON Conf AI1 high shutd Configurable Analog Input 1 High Shutdown 0 dis 3000 0 dis 90 0 3000 C...

Page 17: ...Point 4 Configurable Analog Input 1 Point 5 15 31 49 66 85 101 117 132 149 178 579 404 342 250 179 136 103 77 67 63 10 30 50 70 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1300 1300 1300 130...

Page 18: ...Point 6 Configurable Analog Input 1 Point 7 Configurable Analog Input 1 Point 8 Configurable Analog Input 1 Point 9 Configurable Analog Input 1 Point 10 110 130 150 170 190 0 0 0 0 0 1300 1300 1300 1...

Page 19: ...2 Always Active Input active delay in 26 in2 24 in3 24 in4 26 in5 25 1 in 25 in2 0 in3 4 in4 25 in5 25 1 in1 2 2 in3 1 in4 5 2 in1 0 in2 0 in3 4 in4 0 in5 0 in1 2 2 in3 4 2 in5 2 in1 2 0 in3 5 in4 5 0...

Page 20: ...LTAGE PRE ALARM 58 GENERATOR LOW VOLTAGE SHUTDOWN 59 GENERATOR STOPPING 60 GENERATOR OPEN BREAKER 61 HORN OUTPUT LATCHED 62 HORN OUTPUT PULSED 63 LAMP TEST 64 RESERVED 65 LOSS OF MAGNETIC PICK UP SPEE...

Page 21: ...PUT 2 Outputs Conf output 2 CONF OUTPUT 3 Outputs Conf output 3 CONF OUTPUT 4 Outputs Conf output 4 CONF OUTPUT 5 Outputs Conf output 5 CONF OUTPUT 6 Outputs Conf output 6 Polarity Polarity Polarity P...

Page 22: ...250 5 4 2 6 Timers Warmup Time 3 0 250 Warming up time Sec Note dis disable cont continuous Min Default STOPPING TIMERS Timers Stopping timers Max Remote Stop Delay Cooling Time 4 0 250 60 0 dis 3600...

Page 23: ...rrent I offset 2 Current I offset 3 Current I1 Offset Current I Offset 2 Current I Offset 3 20 20 20 AV AV AV Min Default Unit BATTERY CHRG GEN VOL User adjustment Battery chrg gen vol Max 0 0 0 5 0 5...

Page 24: ...Max operating current is 370 mA Battery voltage can be 0 VDC for max 50 ms during cranking battery voltage should be at least nominal voltage before cranking 8 to 32 V accuracy 1 FS resolution 0 1 V 3...

Page 25: ...et controller speed sensing from Magnetic Pickup RS 232 communication Auto Start GenSet controller CanBus J1939 ECU communication RS 232 communication Auto Start GenSet controller speed sensing from M...

Reviews: