14
7. Specifications
Equipment Use
Housing& Mounting
Panel Cut-Out
Protection
Weight
Environmental Ratings
Operating/Storage Temperature
Installation Overvoltage Category
Pollution Degree
Mode of Operation
EMC
Electrical Safety
Supply Voltage
Supply Voltage Measurement
Mains Voltage Measurement
Generator Voltage Measurement
Measurement Accuracy
Cranking Dropouts
Generator Speed Measurement
Alternator Frequency Range
Magnetic Pickup Freq. Range
Charge Generator Excitation
Communication Interface
Contact Sensing Input
Outputs
Display (
)
Failure Indicators
Status Indicators
Information Alarms
: Electrical control equipment for generating sets
: 144 mm x 204 mm x 37 mm (including connectors) plastic
housing for panel mounting
: 138 mm x 186 mm
: NEMA 4X (IP65 at front panel, IP20 at rear side).
: Approximately 0.45 Kg.
: Standard, indoor at an altitude of less than 2000 meters with
non-condensing humidity.
: -25 C to +70 C / -40 C to +85 C
: II Appliances, portable equipment
: II, normal office or workplace, none conductive pollution
: Continuous
: EN-61000-6-4, EMC generic emission standard for industrial
equipment EN-61000-6-2, EMC generic immunity standard for
industrial equipment
: EN-61010-1, safety requirements for electrical equipment for
measurement, control and laboratory use
: 8-32 V
: 8-32 V
. Accuracy : 1%, Resolution : 0.1V
: Three phase, 4 wire 35 to 300 VL-N
Accuracy : 1%FS,
Resolution : 1V
: Single phase, 2 wire 35 to 300 VL-N
Accuracy : 1%FS,
Resolution : 1V
: 1% of the range
: Battery voltage can be 0 V
for max. 100msec during cranking
(battery voltage should be at least nominal voltage before cranking)
: From alternator or magnetic pickup
:10-110 Hz. (@35-300 VL-N
)
: 35 Hz - 10 kHz (@3-35 Volts peak)
: 12 V
or 24 V
, 200 mA, max 3W
: RS-232 serial communication
: Emergency stop (NC), Oil pressure switch, Temperature switch,
Remote inhibit input (NO), Configurable input 1, Configurable input 2,
Over current input
: Start, Fuel, Horn, Configurable Output, Mains Contactor Output,
Generator Contactor Output (All outputs are 500mA Transistor Output)
: Mains L1 – L2 Voltage, Mains L1 – N Voltage, Mains L2 – L3
Voltage, Mains L2 – N Voltage, Mains L3 – L1 Voltage, Mains L3 – N
Voltage, Alternator Voltage, Alternator Frequency, Engine Speed,
Battery voltage, Engine running time, Error indication,
Program Parameters
: Failed to start, High temperature, Low oil pressure, Over speed,
Generator voltage failure, Charge failure, Over current, Configurable
input 1, Configurable input 2, Low battery voltage, Maintenance due,
Emergency stop
: Off mode, Auto mode, Test mode, Manual mode, Engine start,
Engine stop, Engine running, Mains voltage available, Generator is
ready to take the load, Mains contactor, Generator contactor
: Low battery voltage, Maintenance due, Emergency stop
o
o
o
o
Z
Z
Z
V
V
V
V
Z
Z
Z
Z
4-digit, 7-segment LED display
Approvals
:
,
GOST-R