6-
(Charge Generator Failure LED):
control on delay
At the end of
time
defined by parameter P19, the unit Voltage which comes from Charge
Generator via Pin 11. If there is no Voltage the unit decides to Charge Generator Failure.
In this case the LED flashes and the Horn is sounded.
7-
(Battery Voltage Failure LED):
Battery voltage lower limit
8-
(Configurable Failure Input-1 LED):
9-
(Configurable Failure Input-2 LED):
Battery Voltage Failure is monitored
continues in all modes except "OFF" mode. This failure occurs continuously when the
battery voltage falls below the value specified by the
parameter P11. In this case the LED flashes and the Horn is sounded. It is self resetting
once the fault has been removed.
The EAOM-19 measures battery voltage at the EAOM-19 terminals. Depending on the
size and length of the cable to the battery, this may be somewhat less than the voltage as
measured at the battery.
Configurable Failure-1 input works
on value determined in Parameter P22. When the input is active (Pin 9) the unit works
according to selection of user.
Configurable Failure-2 input works
on value determined in Parameter P23. When the input is active (Pin 10) the unit works
according to selection of user.
Bat.Voltage
Failure
SPARE 1
SPARE 2
Once the EAOM-19 has given a shutdown signal to the engine it expects the engine to rest. It
monitors the
sources and if they still indicate engine movement when
seconds time period expires, The
alarm signal is generated. The
LED
will flash continually.
Engine Started Signal
30
StPE
ALARM
StPE - Stop Error Message (Fail to Engine Stopping):
37
V
L12
GEN V.
GEN FRQ.
BATTERY
ALARM
V
L23
V
L31
°F