multi-zone Heat Pump Condensing units

EMI AMErIcA SErIES MultI-zonE HEAt PuMP condEnSIng unItS

• Compressor and Fan Motor Contactor

• Capacitor

• Low Voltage Connections 

• Large Capacity Suction Accumulator (9, 

12, & 18 Only)

• High Pressure Control 

(18 & 24 Only)

• Solid Core Filter Drier

 

• Thermostatically controlled crankcase 

heater 

(9&12 Only)

• Common suction pressure access point 

• Hard Start Capacitor

iTemS For ConSideraTion

• Locate the unit as close to the indoor sec-

tion as possible. Maximum length allowed 

is 100 equivalent feet.

• Avoid high traffic areas and prevailing 

wind locations.

• Surface must be level.

• Mount unit above typical snow levels.

Ensure  free air  flow  through  the  unit. Air 

must not recirculate from discharge to in-

take. Air is drawn through the coil with side 

or top and discharged through the fan grille. 

A minimum 48” clearance is necessary 
for  the  condenser  discharge.  Intake 
(coil  side)  clearance  is  12”  minimum. 

Consider how power will be run to the unit 

from the power source. Refrigerant piping 

must be a direct line to the indoor unit.

Heat pump units produce condensate in the 

heat pump mode. Water will drain from the 

unit at the base. Place the unit so as not to 

create a hazard for pedestrians.

SYSTem oPTionS

• Sea Coast Style Coated Coils / 

Copper-Copper coils

• Wind Baffles - Louvers

inSTaller SuPPlied iTemS

• Power wiring

• Low Volt wiring - 18 AWG minimum

• Secure mounting pad or foundation

• Refrigerant piping 

• Disconnect switch

SiTe PreParaTion

Place the unit on a flat concrete surface or 

pad if on the ground.  Roof mounting should 

use a build up platform. Piping is through 

the wall or roof directly to the unit. In areas 

of heavy snowfall, condensers should be 

set above the level of maximum anticipated 

snowfall (12” is usually adequate).

EMI  offers  the  finest  multi-zone  heat  pump 

outdoor units in the ductless split market, the 

S & T series (S2HB, T2HB, T3HB & T4HB) 

Condensing Units. The S & T series (S2HB, 

T2HB, T3HB & T4HB)  allows the installation of 

two or more circuits from a single outside location 

when space or aesthetic requirements limit the 

use of the number of cabinets outdoors. Each 

zone is independent so no mixing of refrigerant 

occurs.

When  specifying  heat  pump(s),  it  is 

recommended that the matching indoor unit(s) 

be equipped with electric heat. All 9,000, and 

12,000 Btuh circuit units are equipped with the 

Duratec Performance 

P

ackage which includes 

a  large  capacity  suction  accumulator  with 

surge baffles and enhanced oil management, 

and a factory installed solid core filter drier. All 

18,000 and 24,000 Btuh circuit units include 

a solid core filter drier and high pressure limit 

switch.  The 18,000 Btuh circuits also include a 

large capacity suction accumulator with surge 

baffles and enhanced oil management.

noTe: The crankcase heater is installed 
with 9,000 and 12,000 Btuh heat pumps.

ConTrolS and ComPonenTS

(FACTORY INSTALLED OR SUPPLIED)

deSCriPTion

Thermostatically  controlled  crankcase 
heater

 – This feature energizes the crank

-

case  heater  only  when  needed,  removes 

the  heater  from  the  electrical  circuit  at 

conditions  where  it’s  not  required,  saving 

unnecessary Watts, and increasing overall 

system efficiency. 

Summary of Contents for S2HB

Page 1: ...r International LLC 5780 Success Dr Rome NY 13440 www enviromaster com installation operation and maintenance MANUAL An ISO 9001 2000 Certified Company S2HB Multi Zone S2HB T2HB T3HB and T4HB Heat Pum...

Page 2: ...supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn off the electri...

Page 3: ...ace the unit on a at concrete surface or pad if on the ground Roof mounting should use a build up platform Piping is through the wall or roof directly to the unit In areas of heavy snowfall condensers...

Page 4: ...permanent mounting through the feet This is highly recommended due to the vertical design of the unit S2HB Unit Mounting Section 5 Insert lag bolts through the holes in the bottom of the unit and tig...

Page 5: ...within 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief fitting 7 Run wires to th...

Page 6: ...diagram on the indoor unit Low volt interconnect should be at least 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge o...

Page 7: ...nt protection requirements 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating Removethe four screws on the front panel 4 To access wiring diagram...

Page 8: ...s 9 Connect the 24 volt wiring matching color to terminal blockdesignationforeachzone as labeled Refer to the wiring diagram on the inside front panel of the condenser and also refer to the wiring dia...

Page 9: ...apacity Maximum Length Maximum Lift Liquid Line OD Suction Line OD 9 000 100 35 1 4 1 2 12 000 100 35 1 4 1 2 18 000 100 35 3 8 5 8 24 000 100 35 3 8 3 4 NOTE Refrigerant Piping Installation for all o...

Page 10: ...way mark of the suction riser For example if the suction riser is 30 feet tall then a P trap is recommended at the 15 foot mark of the suction riser see Figure 1 A P trap may be fabricated using 2 str...

Page 11: ...ends of tubing and insert into fittings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap metal to protect the paint 4 Braze tubing into fittings Multi Zone Hea...

Page 12: ...ig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper system pressures and temperature at different outdoor condi tions Superheat should be used for fina...

Page 13: ...The S T series S2HB T2HB T3HB T4HB have manifold access points on each of the service valves for the high and low pressures in cooling mode There is an additional common suction access point above eac...

Page 14: ...www enviromaster com 14 Multi zone Heat Pump Condensing Units Multi zone Heat Pump Field Charging...

Page 15: ...www enviromaster com 15 Multi zone Heat Pump Condensing Units Multi zone Heat Pump Field Charging...

Page 16: ...www enviromaster com 16 Multi zone Heat Pump Condensing Units Multi zone Heat Pump Field Charging...

Page 17: ...www enviromaster com 17 Multi zone Heat Pump Condensing Units Multi zone Heat Pump Field Charging...

Page 18: ...s occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gauge 2 Meas...

Page 19: ...cific to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evap...

Page 20: ...C Heat pump condensers utilize a reversing valve to provide reverse cycle operation Therefore the outdoor unit will act as ei ther a condenser or an evaporator there by providing comfort cooling or he...

Page 21: ...l repeat until the jumpers are removed from the test pins Note If the condenser coil is heavily frosted up with ice it is likely that the Defrost Sensor is already closed In this case the R and DFT ju...

Page 22: ...y a QUALI FIED service agency only GENERAL RECOMMENDATIONS Do not charge the straight cool units on cold days unless weighing in the charge The heat pump systems may be charged in heat cycle between 3...

Page 23: ...208 230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compres...

Page 24: ...13 0 79 11 4 14 600 7 7 3 1 2200 CAH12 CAH12 22 600 13 0 75 11 3 18 400 7 7 3 2 9200 CAH12 CAH12 20 600 13 0 77 11 3 16 500 7 7 3 1 CAH S2HB CAH S2HB WLH System Performance MODEL COOLING HEATING S2HB...

Page 25: ...S2HB UNH Side discharge Model Cooling Heating S2HB Outdoor Indoor Units Btuh SEER SHR EER Btuh HSPF C O P 9900 UNH09 UNH09 18 600 13 0 75 11 9 14 800 7 7 3 3 2200 UNH12 UNH12 22 600 13 0 73 11 7 18 40...

Page 26: ...8 70 325 T2HB8400 3 8 5 8 3 4 70 325 T2HB4400 3 8 3 4 70 325 T2HB2400 1 4 3 8 1 2 3 4 70 325 T2HB9800 1 4 3 8 1 2 5 8 70 325 T3HB9990 1 4 1 2 70 325 T3HB9920 1 4 1 2 70 325 T3HB9980 1 4 3 8 1 2 5 8 7...

Page 27: ...4 23 4 3 27 4 3 27 13 8 14 9 15 197 9280 1 8 0 33 3 4 23 4 3 27 5 4 36 14 9 16 3 20 197 9240 1 8 0 33 3 4 23 4 3 27 8 8 54 18 3 20 5 25 197 2280 1 8 0 33 4 3 27 4 3 27 5 4 36 15 8 17 2 20 197 2240 1 8...

Page 28: ...8 33400 7 7 3 2 T3HB9220 1 WLH09 2 WLH12 31800 13 0 74 11 7 25800 7 7 3 3 T3HB9280 1 WLH09 1 WLH12 1 WLH24 38500 13 0 73 11 9 30000 7 7 3 3 T3HB9240 1 WLH09 1 WLH12 1 WLH24 44500 13 0 69 11 7 35200 7...

Page 29: ...2 CAH12 1 CAH24 36400 13 0 77 11 9 26800 7 7 3 1 T3HB9940 2 CAH12 1 CAH24 42500 13 0 72 11 6 33000 7 7 3 1 T3HB9220 3 CAH12 31800 13 0 76 11 3 25600 7 7 3 1 T3HB9280 2 CAH12 1 CAH24 38500 13 0 75 11 8...

Page 30: ...940 2 UNH09 1 UNH24 42500 13 0 71 11 8 33400 7 7 3 2 T3HB9220 1 UNH09 2 UNH12 31800 13 0 74 11 7 25800 7 7 3 3 T3HB9280 1 UNH09 1 UNH12 1 UNH24 38500 13 0 73 11 9 30000 7 7 3 3 T3HB9240 1 UNH09 1 UNH1...

Page 31: ...its EMI s High SEER Product Line Evaporators Condensers WLC WLH High Wall Evaporator CAC CAH Cassette Evaporator S1C S1H Single Zone Side Discharge S2C S2H Dual Zone Side Discharge T2C T3C T4C T2H T3H...

Page 32: ...Phone 1 800 228 9364 Fax 1 800 232 9364 5780 Success Drive Rome NY 13440...

Reviews: