1. Completely tighten the flare nuts, A, B, C, D, connect 
    the manifold valve charge hose to a charge port of the 
    packed valve on the gas pipe side.
2. Connect the charge hose connection to the vacuum 
    pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting 
    evacuation, slightly loose the flare nut of the packed 
    valve on the gas pipe side and check that the air is 
    entering. (Operation noise of  the vacuum pump changes 
    and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the handle 
    Lo of the manifold valve and stop the operation of the 
    vacuum pump.
    Make evacuation for 15 minutes and more and check 

5

    that the compound meter indicates  -76cmHg(-1.0x10 Pa).

O

6. Turn the stem of the packed valve B about 45  counter-
    clockwise for 6~7 seconds after the gas coming out, then 
    tighten the flare nut again. Make sure the pressure display 
    in the pressure indicator is a little higher than the atmosphere 
    pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Packed valve

Perform  test operation after completing gas leak check at the flare nut connections and electrical 
safety check.
    Check that all tubing and wiring have been properly connected.
    Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions works 
     well. 

O

3.  When the ambient temperature is too low(lower than 17 C), the unit cannot be controlled by the 
     remote controller to run at cooling mode, manual operation can be taken. Manual operation is 
     used only when the remote controller is disable or maintenance necessary.
     Hold the panel sides and lift the panel up to an angle until it remains fixed with a clicking sound.
     Press the Manual control button to select the AUTO or COOL, the unit will operate under Forced 
     AUTO or COOL mode(see User Manual for details).
4.  The test operation should last about 30 minutes.

2. When using the Vacuum Pump

4. Test running

3. Safety and leakage check

A: Lo packed valve  B: Hi packed valve 
C and D are ends of indoor unit connection.

CAUTION

1. Soap water method:
     Apply a soap water or a liquid neutral detergent on the indoor 
     unit connections and outdoor unit connections by a soft brush 
     to check for leakage of the connecting points of the piping. If 
     bubbles come out, it indicates that the pipes have leakage.
2.  Leak detector
     Use the leak detector to check for leakage.

Indoor unit
check point

D

B

C

A

Outdoor unit
check point

Cover

Manual control 

button

AUTO/COOL

Summary of Contents for enviroair 12000 Btu

Page 1: ...ess Inverter Split Systems Installation Operation Manintenance Manual Air Handler Indoor Models FWCA Condenser Outdoor Models FCA An ISO 9001 2008 Certified Company ECR International Inc 2201 Dwyer Av...

Page 2: ...nd maintenance Operation tips Troubleshooting tips INSTALLATION PRECAUTIONS SAFETY PRECAUTIONS SELECT THE BEST LOCATION INDOOR UNIT INSTALLATION PLATE MOUNTING DRILL A HOLE IN THE WALL CONNECT THE CAB...

Page 3: ...cted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection 6 Wiring routing must be properly arranged so that control board cover is fixed properly If...

Page 4: ...om the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrow from wall ceiling fence or other obstacles D...

Page 5: ...right or the left and the hole should be slightly slanted to the outdoor side 4 Always take steps to protect the pipe when drilling metal grid metal plate or the like DRILL A HOLE IN THE WALL INSTALLA...

Page 6: ...which located on the side panel of the unit Please refer to the nameplate before selecting the cable fuse and switch NOTE Suggest Minimum Wire Size AWG American Wire Gage Appliance Amps AWG Wire Size...

Page 7: ...unit Do not allow the piping to let out from the back of the indoor unit Be careful not to let the drain hose slack Heat insulation should be done to the extension drain hose of indoor unit Be sure t...

Page 8: ...then insert the drain joint into the base pan hole of outdoor unit rotate 90 to securely assemble them To install drain joint as shown in Fig B insert the drain joint into the base pan hole of outdoor...

Page 9: ...p Additional amount of refrigerant to be charged Open the valve stem until it hits against the stopper Do not try to open it further Securely tighten the valve stem cap with a spanner or the like Valv...

Page 10: ...ak check at the flare nut connections and electrical safety check Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open 1 Conne...

Page 11: ...10 Before using your air conditioner please read this manual carefully and keep it for future reference 10 Before using your air conditioner please read this manual carefully and keep it for future r...

Page 12: ...SOCIABLE REMARK DISPOSAL Do not dispose of this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance...

Page 13: ...may cause fire and electric shock It may cause explosion fire and burns It may cause electric shock or fire due to heat generation It may cause electric shock It may cause failure of machine or elect...

Page 14: ...ty etc It may cause failure of product or fire Do not use for special purposes Turn off the main power switch when not using the unit for a long time If water enters the unit turn the unit off and dis...

Page 15: ...y panel Indoor unit VLED Display Window OPERATION indication lamp This lamp illuminates when the air conditioner is in operation TIMER indication lamp Lights up during Timer operation DEFROST indicati...

Page 16: ...h for the next operation The unit will operate as following sequence FAN ONLY mode at Low fan speed Heating operation with LOW fan speed applicable to cooling heating modles only FAN ONLY operation St...

Page 17: ...e floor and set HIGH fan mode Suggestion For the unit adopts an Electric Heater when the outside ambient temperature O O is below 0 C 32 F we strongly recommend you to keep the machine plugged in orde...

Page 18: ...o not put your fingers into the panel of blower and suction side The high speed fan inside may cause danger Do not operate the air conditioner for long periods with the air flow direction set downward...

Page 19: ...t it will switch off This mode saves you energy and brings you comfort at night DRYING operation Optimal operation To achieve optimal performance please note the following Adjust the air flow directio...

Page 20: ...h a soft dry cloth Do not use bleach or abrasives NOTE Power supply must be disconnectd before cleaning the indoor unit Filter Handle Cleaning the air filter A clogged air filter reduces the cooling e...

Page 21: ...rts of the unit when removing the filter Injuries can occur when handling sharp metal edges Do not use water to clean inside the air conditioner Exposure to water can destroy the insulation leading to...

Page 22: ...in HEAT mode operation after defrosting 3 Low noise of the air conditioner You may hear a low hissing sound when the compressor is running or has just stopped running It is the sound of the refrigera...

Page 23: ...re If a comfortable temperature can t be achieved by the air conditioner we suggest you use a supplementary heating device 10 Auto restart function Power failure during operation will stop the unit co...

Page 24: ...indows are open Air inlet or outlet of indoor or outdoor unit has been blocked Compressor 3 or 4 minutes protection has been activated If the trouble has not been corrected please contact a local deal...

Reviews: