Terminal blocks

a) Transformer connected meter

 DANGER!

Risk of fatal injury in case of contact with live parts!

 

y

The electrician is responsible for coordination of the rating and 

line-side properties of the overcurrent protection devices with the 

maximum rated current.

 

y

The transformer connected meter must be fuse-protected in a  

voltage circuit using a pre-fuse with < 6 A.

 

y

The current paths must be fuse-protected as per the current specifi

-

cations on the meter’s name plate in accordance with the applicable 

technical regulations.

 DANGER!

Risk of fatal injury from high voltage when power converters 

disconnected!

In transformer connected meters, the high voltage generated on a dis-

connected power converter can cause fatal injuries, and will destroy 

the power converter.

 

y

Before disconnecting the current paths, short-circuit the secondary 

circuits of the power converter at its testing terminals.

Summary of Contents for NXT4

Page 1: ...Version November 2020 Subject to technical changes Scope of delivery 2 Important information 2 Target group 2 Intended use 2 Maintenance and warranty instructions 3 Care and disposal information 3 Bas...

Page 2: ...in may not be applicable for your particular device More comprehensive information about the device is available in the product manual Please also observe all the documents included with other compone...

Page 3: ...to be treated at the end of their life cycle Components Waste collection and disposal Printed circuit boards Electronic waste Dispose of such waste in accordance with the local regulations LEDs LC di...

Page 4: ...mage or other externally visible damage y Only use the device if it is in a technically flawless state and solely in line with its intended use y The connection cables used to connect a meter must be...

Page 5: ...range 25 C 55 C Limit for operation 40 C 70 C Limit for storage and transport 40 C 70 C Humidity Maximum 95 non condensing as per EN 62052 11 EN 50470 1 and EN 60068 2 30 Protection class II Degree o...

Page 6: ...Reset button sealable 3 Call up button 4 Optical data interface D0 optical call up button left 5 Test LEDs 6 Space for transformer plate for transformer connected meters only 7 Terminal cover sealable...

Page 7: ...ment of inputs and outputs interfaces 8 Information about connection to meter connection diagram 9 Temperature class as per EN 60721 3 3 10 Conformity and certification marking 11 Safety and applicati...

Page 8: ...ry or the internal power reserve of the real time clock Full power the real time clock is buffered in this instance Power reserve run down readout battery is empty or not available In this instance th...

Page 9: ...the meter The arrows indicate which tariff and maximum meter are active and how the meter is being controlled clock or ripple control receiver T1 T4 Tariff information for energy All activatable tari...

Page 10: ...p The meter can be wall mounted as per DIN 43857 2 The following figures show the relevant dimensions for mounting the meter depending on the model involved Mounting the meter a Meter with short termi...

Page 11: ...11 b Meter with long terminal cover Dimensions in mm c Meter with VARIOMOD NXT meter modem Dimensions in mm...

Page 12: ...s or cause any economic damage y To avoid any immediate hazards or damage take appropriate measures to prevent malfunctions before disconnection of the system y Do not use the internal disconnection r...

Page 13: ...cordance with the applicable technical regulations ATTENTION Application of excessive torque will damage the connection terminals The appropriate torque is dependent on the type of connection line inv...

Page 14: ...using a pre fuse with 6 A y The current paths must be fuse protected as per the current specifi cations on the meter s name plate in accordance with the applicable technical regulations DANGER Risk of...

Page 15: ...dimensions W x H mm 5 3 x 5 5 2 6 x 2 2 Minimum connection cross sections mm 2 5 1 0 Maximum connection cross sections mm 10 0 2 5 Maximum torques Nm 1 5 Screw type Screw with washer assembly with slo...

Page 16: ...and parameters of the supply side overcurrent protection devices with the maximum rated currents as well as the rated consumption category of the meter system for directly connected meters y The conne...

Page 17: ...ecting paths must be fuse protected as per the applicable technical regulations and in accordance with the current specifica tion on the meter s name plate y The installer bears responsibility for coo...

Page 18: ...x 2 2 Minimum connection cross sections mm 2 5 1 0 Maximum connection cross sections mm 35 0 2 5 Maximum torques Nm 3 5 Screw type Screw with washer assembly with slot and Pozidriv PZ2 drive Spring l...

Page 19: ...r self ignite y Never short circuit damage heat or force open batteries In delivery condition the battery function is inactive 1 Remove the battery from the holder in the terminal cover 2 Turn the bat...

Page 20: ...tection LC Liquid Crystal LED Light Emitting Diode OBIS Object Identification System P Active power P Positive active power power drawn by customer P Negative active power power supplied by customer Q...

Page 21: ...21...

Page 22: ...22 EU Declaration of Conformity The current EU Declaration of Conformity is available on the Internet site www emh metering com in the Products area for the meter s product description...

Page 23: ...23...

Page 24: ...24...

Reviews: