YarwaY

 SerieS AV-5 Air Vent

InstallatIon, operatIon and maIntenance InstructIons

Before installation these instructions must be fully read and understood

VCIOM-03127-EN 18/09

SpECIfICatIONS

Pressure-temperature rating:
Shell; ASMe Class 600 (Pn 100) B16.34.
Operating Pressure max.; 600 psig (41 bar).
Operating temperature max.; 650F (343C).
test Pressure max.; 800 psig (55 bar)

nominal Venting Capacity:
1.25 Actual cu ft/min. (0.6 Lit/sec) venting to 
atmosphere based on a minimum pressure of 
15 psig.

Failure Position:
Vent fails open upon bellows failure.

end Connections:
in-line ½”, ¾” nPt (Dn 15, 20) per ASMe
B1.20.1.

installation Position:
Vertical with discharge down.

Special Features:
integral Screen.

NOtE

All pressures are gauge

applICatION 

Series AV-5 vent has been designed to remove 
air and non-condensables from steam lines.

Emerson.com/finalControl

© 2017 emerson. All rights reserved.

OpEratION 

the vent operates by means of a thermostatic 
bellows which opens and closes an interval 
valve in response to temperature changes. 
Steam is prevented from discharging through 
the vent, and only subcooled non-condensables 
are discharged.

MaINtENaNCE

AV-5 vent is permanently assembled; no 
maintenance other than flushing or removing 
material from the screen is recommended.

trOublEShOOtINg

AV-5 vent is permanently assembled; 
no maintenance other than flushing or removing 
material from the screen is recommended. 

Air vent to pass subcooled gases:
a. Check integral strainer for clogging. 

rush or remove material clogging strainer

Air vent blows live steam:
a.  Dirt on valve seating area.
b.  Worn valve seat. replace the air vent.
c.  Failed bellows. replace the air vent. 

warNINg

Hot discharge from this product may cause severe 
burns. Discharge must be piped away or directed 
sothat persons in the vicinity are not endangered. 
This product must be isolated, vented and cool to 
the touch before repairing or inspecting. 

Conduct 

discharge to 

safe location

Acceptable alternative 

vent may cycle on 

some condensate

Preferred installation 

generally more sensitive 

to presence of air

AV-5