In normal operation the sequencer has been designed to operate with Run forward / Run reverse controls, or with a Run control and a forward
reverse selector. If Run forward / Run reverse control is required then bits Pr
6.30
and Pr
6.32
should be used to control the drive (digital inputs should
not be routed to bits Pr
6.33
and Pr
6.34
). If Run control with a forward reverse selector is required then bits Pr
6.33
and Pr
6.34
should be used to
control the drive (digital inputs should not be routed to bits Pr
6.30
and Pr
6.32
).
The Run forward and Run reverse, or Run sequencing bits can be made latching by setting bit Pr
6.40
. The Not stop bit (Pr
6.39
) should be one to
allow the sequencing bit to be latched. If the Not stop bit is zero all latches are cleared and held at zero. The jog or jog reverse sequencing bits can
also cause the drive to run provided the motor is stopped when these bits are activated and the normal run sequencing bits are not providing a run
signal.
6.32
Sequencing bit: Run reverse
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
0
Update rate
4ms read
6.33
Sequencing bit: Forward/reverse
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
0
Update rate
4ms read
6.34
Sequencing bit: Run
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
0
Update rate
4ms read
6.35
Forward limit switch
Drive modes
Open-loop, Closed-loop vector, Servo
Coding
Bit
SP
FI
DE
TE VM DP
ND
RA NC NV
PT
US RW BU
PS
1
1
1
Default
Open-loop, Closed-loop vector, Servo
0
Update rate
250
μ
s read