176
Unidrive M400 User Guide
Issue Number: 2
Card Product
NV Media Card data blocks are not compatible with the drive derivative
175
The
Card Product
trip is initiated either at power-up or when the card is accessed, If
Drive Derivative
(11.028) is different
between the source and target drives. This trip can be reset and data can be transferred in either direction between the
drive and the card.
Recommended actions:
•
Use a different NV Media Card
•
This trip can be suppressed by setting Pr
mm.000
to 9666 and resetting the drive
Card Rating
NV Media Card Trip; The voltage and / or current rating of the source and destination drives are different
186
The
Card Rating
trip indicates that parameter data is being transferred from the NV Media Card to the drive, but the current
and / or voltage ratings are different between source and destination drives. This trip also applies if a compare (using
Pr
mm.000
set to 8yyy) is attempted between the data block on a NV Media Card and the drive. The Card Rating trip does
not stop the data transfer but is a warning that rating specific parameters with the RA attribute may not be transferred to the
destination drive.
Recommended actions:
•
Reset the drive to clear the trip
•
Ensure that the drive rating dependent parameters have transferred correctly
Card Read Only
NV Media Card has the Read Only bit set
181
The
Card Read Only
trip indicates that an attempt has been made to modify a read-only NV Media Card or a read-only data
block. A NV Media Card is read-only if the read-only flag has been set.
Recommended actions:
•
Clear the read only flag by setting Pr
mm.000
to 9777 and reset the drive. This will clear the read-only flag for all data
blocks in the NV Media Card
Card Slot
NV Media Card trip; Option module file transfer has failed
174
The Card Slot trip is initiated, if the transfer of an option module file to or from a module failed because the option module
does not respond correctly. If this happens this trip is produced with the sub-trip number indicating the option module slot
number.
Control Word
Trip initiated from the
Control Word
(06.042)
35
The
Control Word
trip is initiated by setting bit 12 on the control word in Pr
06.042
when the control word is enabled
(Pr
06.043
= On).
Recommended actions:
•
Check the value of Pr
06.042.
•
Disable the control word in
Control Word Enable
(Pr
06.043
)
Bit 12 of the control word set to a one causes the drive to trip on Control Word
When the control word is enabled, the trip can only be cleared by setting bit 12 to zero
Current Offset
Current feedback offset error
225
The
Current Offset
trip indicates that the current offset is too large to be trimmed.
Recommended actions:
•
Ensure that there is no possibility of current flowing in the output phases of the drive when the drive is not enabled
•
Hardware fault – Contact the supplier of the drive
Data Changing
Drive parameters are being changed
97
A user action or a file system write is active that is changing the drive parameters and the drive has been commanded to
enable, i.e.
Drive Active
(10.002) = 1.
Recommended actions:
•
Ensure the drive is not enabled when defaults are loading
Derivative ID
Derivative file error
246
Derivative file error with sub-trips:
Sub-trip
Reason
1
Derivative file different
2
Derivative file missing