background image

Safe Use Guide 

SG0095GB Rev.06 
Year of Manufacture 2008

 

A/100

 

 

 

 

http://www.tartarini.it 

 

 

Self-operated regulator 

 

Introduction 

This Installation Guide provides instructions and  safety 
information on pressure equipment so as to avoid any 
foreseeable risk during the use. 

For further information refer to Types A/100 and A/110 
Instruction Manual, n° 0095 and Bulletin, n° 0068. 

To receive a copy of the Bulletin, contact your local O.M.T. 
Tartarini Sales Office or O.M.T Tartarini Sales 
Representative. 

General Remark 

The standard gas pressure devices (regulators and safety 
shut-off devices) are those used in the assemblies dealt 
with into EN 12186 and EN 12279 and their use has to be  
under the provisions into ENs 12186 & 12279. 

Fail-to-open stand-alone regulators cannot be used as a 
safety accessory according PED 97/23/EC to protect 
downstream pressure equipment. 

In the pressure regulators (with or without built-in safety 
shut-off devices) manufactured by OMT Tartarini shall be 
used additionary pressure accessories (e.g. pilots or 
filters) manufactured and labeled by OMT Tartarini.  

OMT Tartarini will be not responsible for any possible 
inefficiency due to installation of not own production 
additionary pressure accessories (e.g. pilots or filters). 

When pressure containing parts of possible built-in safety 
shut-off device (SSD) valve and pilot have different 
maximum allowable pressures,  the SSD is differential 
strength type. 

P.E.D. Categories and Fluid Group 

According to EN 14382, only in integral strength type and 
Class A configuration (when both over and under pressure 
protections are set up), the possible built-in safety shut-off 
device can be classified like a  safety accessory according 
to PED. 

The minimum PS between SSD valve and pilot shall be 
the PS of the safety accessory to comply the provisions of 
EN 14382 about integral strength type. 

Downstream equipments, protected by possible built-in 
safety shut-off device (in its Class A and integral strength 
configuration) of this product, shall have technical features 
such as to be category per table below according Directive 
97/23/EC “PED”. 

Product Size 

Category 

Fluid Group 

DN 2“ 

Possible built-in pressure accessories (e.g. pilots OS66/) 
conform to Pressure Equipment Directive (PED) 97/23/EC 
Article 3 section 3 and were designed and manufactured 
in accordance with sound engineering practice (SEP). 

Per Article 3 section 3, these “SEP” products must not 
bear the CE marking. 

Specifications 

Body Sizes and End Connection Styles 

DN 2” BSP inlet and outlet 

DN 2” PN 16 UNI/DIN - Sliding flanges 

(available on request) 

DN 2” ANSI 150 - Sliding flanges 

(available on request)

 

!  WARNING  ! 

Maximum Operating Inlet Pressure 

(1) 

A/102 

 A/109: 8 bar 

A/102-AP 

 A/109-AP: 8 bar 

Operating

 

Outlet Set Pressure Ranges 

A/102 

 A/109: 10 

÷

 60 mbar 

A/102-AP 

 A/109-AP: 60 

÷

 300 mbar 

Minimum/Maximum Allowable Temperature (TS)

 (1)

 

See nameplate

 

(1)

 : The pressure/temperature limits in this Safe Use 

Guide and any applicable standard or code limitation 
should not be exceeded. 

Marking 

 

Note 1: 

See  “

Specifications

” paragraph 

Note 2:

  See page header 

Note 3:

  Class 1:  -10/+60 °C 

Note 4:

  PN 16 PS = 16 bar 

 

  ANSI 150 PS = 19.3 bar 

 

  Threaded 2” = 20 bar 

Reviews: