13
Issue Number: 2 www.controltechniques.com
3.3 Ratings
The above current ratings are given for max 40
°
C (104
°
F), and 3.0 kHz
switching. Derating is required for higher switching frequencies, ambient
temperature >40
°
C (104
°
F) and high altitude. For further information,
refer to both the
Unidrive SP and SPM User Guides
.
Table 3-1 200V Drive ratings (200V to 240V ±10%)
Model
Normal Duty
Heavy Duty
Maximum
continuous
output current
Nominal
power
at 220V
Motor
power
at 230V
Maximum
continuous
output current
Nominal
power
at 220V
Motor
power
at 230V
A
kW
hp
A
kW
hp
1201
5.2
1.1
1.5
4.3
0.75
1.0
1202
6.8
1.5
2.0
5.8
1.1
1.5
1203
9.6
2.2
3.0
7.5
1.5
2.0
1204
11
3.0
3.0
10.6
2.2
3.0
2201
15.5
4.0
5.0
12.6
3.0
3.0
2202
22
5.5
7.5
17
4.0
5.0
2203
28
7.5
10
25
5.5
7.5
3201
42
11
15
31
7.5
10
3202
54
15
20
42
11
15
4201
68
18.5
25
56
15
20
4202
80
22
30
68
18.5
25
4203
104
30
40
80
22
30
5201
130
37
50
105
30
40
5202
154
45
60
130
37
50
1201
192
55
175
156
45
60
1202
248
75
100
192
55
75
1203
312
90
125
250
75
100
1204
350
110
150
290
90
125
1
2
3
4
55
SPMD
NOTE
Summary of Contents for SP1201
Page 219: ......