Emerson SolaHD STC-HSP Series Manual Download Page 3

Page: 1

STCHSP121BT1RU

Introduction

The 

STCHSP121BT1RU

 is an advanced 3-stage hybrid, solid state power line protective device. Features 

such as noise filtering, common mode and normal mode suppression, nanosecond reaction time, power line 
tracking, and compression screw terminations, make this device an excellent choice in commercial 

 

and industrial applications. 

This SPD offers a replaceable fuse designed to remove the load from the line in the event the unit is overloaded 

or the internal protection stops working.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, 

NOM-029-STPS or CSA Z462.

• 

This equipment must only be installed and serviced by qualified electrical personnel.

• 

Turn off all power supplying this equipment before working on or inside equipment.

• 

Always use a properly rated voltage sensing device to confirm power is off.

• 

Replace all devices, doors and covers before turning on power to this equipment.

•  This equipment must be installed inside an enclosure and located so, as to prevent accidental contact with 

terminals during maintenance or servicing.

• 

Connect only to 120 VAC, 15 Amp Max., single phase, three wire circuit. 

• 

Disconnect AC source before replacing fuse. For proper operation, replace only with same type rating of fuse (3 

AB,15 A/250 V).

Failure to follow these instructions will result in death or serious injury.

WARNING:

 This product can expose you to chemicals including DINP, which is known to the State of 

California to cause cancer, and DIDP which is known to the State of California to cause birth defects or other 

reproductive harm. For more information go to: www.P65Warnings.ca.gov.

NOTICE

LOSS OF SURGE SUPPRESSION

• 

Make certain that Surge Protective Device is disconnected from the circuit it is protecting before conducting high 

potential insulation testing.

Failure to follow these instructions can result in equipment damage.

DANGER

Summary of Contents for SolaHD STC-HSP Series

Page 1: ...Surge Protective Devices STC HSP Series ...

Page 2: ...jury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE NOTICE is used to address practices not related to phy...

Page 3: ...perly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be installed inside an enclosure and located so as to prevent accidental contact with terminals during maintenance or servicing Connect only to 120 VAC 15 Amp Max single phase three wire circuit Disconnect AC source before replacing fuse For ...

Page 4: ...ic Operation Indicator Status ON The device is installed correctly and the line side has power Indicator Status OFF Check connections verify that the line voltage is at the point of connection if all is correct then replace the device Fuse Replacement 1 Determine the model number this is located on the silver UL label 2 Ensure all power is removed from the device 3 If the unit is catalog number ST...

Page 5: ...tion Dimensions in mm 4 86 123 44 1 17 29 72 1 17 29 72 5 25 133 35 Holes 3 16 4 76 DIA 2 95 74 93 LIGHT ON NORMAL LIGHT OFF SERVICE LINE EQUIPMENT AC NEUTRAL GROUND AC NEUTRAL GROUND STC SLAC Series Surge Protective Device STC HSP121BT1RU EXPOSED TERMINAL DESIGN ...

Page 6: ...ion Line to Neutral Line to Ground Neutral to Ground Status Indication Power On MOVs functional Connection Type 3 position terminal block w compression screws Terminals accept up to 14 AWG Operating Temperature 40 C to 85 C Dimensions in mm Exposed Terminal Design 1 8 x 2 9 x 5 3 in 46 x 75 x 133 mm Weight oz kg 10 oz 0 28 kg Certifications UL 1449 recognized Limited warranty 5 years Model STCHSP1...

Page 7: ... 4384 USA 847 268 6651 Warranty Please see the Terms Conditions of Sale document While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Group assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Page 8: ...riel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales Office Chennai T 91 44 3919 7300 Korea Sales Offic...