6.8 Current Limitations

When the load is increased beyond the MCR’s rated value, a point is reached where the output voltage suddenly collapses and 
will not regain its normal value until the load is partially released. Under short-circuit conditions, the load current is limited to 
approximately twice of the rated full-load value, and the input power to less than 10% of normal. The unit will protect both itself 
and its load against damage from excessive fault currents. Fusing of load circuits is not necessary.

6.9 operation with Motor Loads

Because of the current-limiting effect described above, special attention should be given to motor applications. In general, the 
regulator must have a load rating nearly equal to the maximum power drawn during the starting cycle. This may run from two to 
eight times the normal (running) rating of the motor. In doubtful cases, it is advisable to measure the actual starting current. 

7.1 Service & Maintenance

The unit is a simple, rugged device with no moving parts. Routine service and/or maintenance is not required. If a problem does 
occur, please refer to “8.0 Troubleshooting” or contact SolaHD Technical Support for assistance.

7.2 Field replacement of Capacitors

Capacitors used in our units are the highest commercial grade, with each one given a rigid acceptance test upon receipt. SolaHD 
guarantees free replacement of any capacitors which fail within one year of sale. Older units can be replaced at a moderate 
charge. 

NOTE:

 It may be possible to test and identify defective capacitors in the field. Please contact SolaHD Technical Support at 

1.800.377.4384 or 1.847.268.6651 for further assistance.

8.0 Troubleshooting

Table 14: Troubleshooting

Problem

Action

Nominal voltage too high

1. 

The load may be considerably less than the full rating. See “6.2 Load Regulation”.

2. 

The load may have a leading power factor.

Nominal voltage too low

1. 

The load power factor may be lagging.

2. 

The unit may be slightly overloaded. See “6.8 Current Limitations”.

Unit does not regulate closely

1. 

The unit may be slightly overloaded. See “6.8 Current Limitations”.

2. 

The actual line voltage swings may be outside the rate range of the unit, particularly on the low 
side.

3. 

On varying loads, a certain amount of load regulation may be mixed with the line voltage regu-
lating action. See “6.2 Load Regulation”.

Output voltage is very low (20–60 V)

1. 

Unsuspected or unplanned overloads of substantial size may occur intermittently (motor-
starting currents, solenoid inrush currents, etc.). See “6.8 Current Limitations”.

2. 

One or more capacitors in the regulator may be defective.

No output voltage

1. 

Check power source breakers or fuses.

2. 

Check input switch.

3. 

Check continuity between input terminals, and also between output terminals.

Transformer operating temperature

1. 

The transformer used in the unit is designed to operate at high flux density and relatively high 
temperatures. After connection to the line for 30 minutes or so, the transformer core structure 
may be too hot to touch with your bare hands. This is normal and should not cause concern.

Unit is operating, but does not appear to 
have the correct output

The steps below will usually establish whether the apparent poor performance is due to a fault in 
the unit or to some peculiarity of the working load.

1. 

Disconnect the working load.

2. 

Connect a dummy load of lamps, heaters, or other resistive loads (substantially equal to the 
full load rating of the regulator) directly across the output terminals.

3. 

Measure the output voltage of the regulator (using a true RMS type voltmeter) directly across 
the output terminals.

Support

Please contact SolaHD Technical Support at 1.800.377.4384/1.847.268.6651 or by e-mail at [email protected] for further 
assistance.

7.0 Service & Maintenance

Summary of Contents for Sola HD 23-13-030-2

Page 1: ...CVS Hardwired Series 60 Hz User Manual ...

Page 2: ...ent Limitations 11 6 9 Operation with Motor Loads 11 7 0 Service Maintenance 11 7 1 Service Maintenance 11 7 2 Field Replacement of Capacitors 11 8 0 Troubleshooting 11 9 0 Specifications 12 10 0 Warranty Support 12 10 1 Warranty Information 12 10 2 Technical Support 12 While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Group LLC assumes no responsibi...

Page 3: ...nditioning equipment 4 0 Installation Instructions 4 1 Receiving Upon receipt immediately inspect the unit for obvious signs of shipping damage and or mishandling If damaged photograph the unit inform the carrier and contact your SolaHD representative 4 2 Mounting Ventilation These units are for use in an indoor humidity and temperature controlled environment Mount the unit in either a horizontal ...

Page 4: ...4 6 3 03 77 0 0 31 x 0 69 7 9 x 17 5 28 0 12 7 60 23 23 150 8 13 00 330 2 6 50 165 1 8 12 206 2 9 00 228 6 8 12 206 2 5 62 142 7 3 06 77 7 0 38 x 0 81 9 7 x 20 6 37 0 16 8 60 23 23 210 8 17 25 438 2 6 81 173 0 8 12 206 2 9 00 228 6 8 12 206 2 5 62 142 7 5 25 133 4 0 38 x 0 81 9 7 x 20 6 63 0 28 6 Table 3 Dimensions Figure 2 Hz Catalog Number Dimensions in inches mm Ship Weight lb kg A B C D E F G ...

Page 5: ...e 4 Dimensions Figure 3 Hz Catalog Number Dimensions in inches mm Ship Weight lb kg A B C D E F G H 60 23 28 275 6 26 91 683 5 9 27 235 6 23 55 598 2 25 81 655 6 24 81 630 2 6 62 168 1 8 88 225 6 0 44 x 0 69 11 2 x 17 5 365 0 165 6 FIGURE 3 ...

Page 6: ... Interconnect Connect Lines to 23 13 030 2 120 X1 and X2 23 13 060 2 120 X1 and X2 23 22 112 2 120 X1 and X2 23 28 275 6 120 X1 and X2 OR X3 and X2 240 X1 and X3 NOTE Secondaries are not grounded Ground X2 per code Table 6 Product Parameters Catalog Number VA BTU Output at Full load 40 C Ambient 23 13 030 2 30 60 23 13 060 2 60 85 23 22 112 2 120 136 23 28 275 6 7500 2407 Table 7 Fusing Wiring Cat...

Page 7: ...2 to H3 H4 to H5 H6 to H7 H1 and H8 Secondary Voltage Interconnect Connect Lines to 120 X1 and X2 FIGURE 5 Table 10 Fusing Wiring Catalog Number Required Circuit Protection Minimum Gauge for 90 C Wire Minimum Gauge for 90 C Wire Input Voltage Output Voltage 95 130 175 235 190 260 380 520 475 650 120 208 240 23 23 125 8 6 A 14 AWG 3 A 14 AWG 1 A 14 AWG 14 AWG Table 9 Product Parameters Catalog Numb...

Page 8: ...rcuit Protection Minimum Gauge for 90 C Wire Minimum Gauge for 90 C Wire Input Voltage Output Voltage 95 130 175 235 190 260 380 520 475 650 120 208 240 23 23 150 8 10 A 14 AWG 6 A 14 AWG 6 A 14 AWG 3 A 14 AWG 14 AWG 23 23 210 8 15 A 14 AWG 10 A 14 AWG 10 A 14 AWG 6 A 14 AWG 14 AWG 23 23 220 8 30 A 10 AWG 20 A 12 AWG 15 A 14 AWG 10 A 14 AWG 10 AWG 14 AWG 23 23 230 8 45 A 8 AWG 25 A 10 AWG 25 A 10 ...

Page 9: ... power conditioners with the same SolaHD catalog number The inputs must be connected in Delta Input fuses must be connected in the primary of each unit not in the three phase lines The outputs must be connected in WYE with the neutral solidly connected to a WYE load Alternatively these three outputs may serve three independent single phase loads Phase angles may vary somewhat from 120 degrees even...

Page 10: ...ls for a short duration This ringing occurs at the point when the switch mode power supply current demand drops to zero The ringing need not be a cause for concern since it is of relatively low magnitude and frequency Both series have been tested with a variety of switch mode power supplies and it has been determined that the ringing does not affect the dc outputs nor has it been found to degrade ...

Page 11: ... than the full rating See 6 2 Load Regulation 2 The load may have a leading power factor Nominal voltage too low 1 The load power factor may be lagging 2 The unit may be slightly overloaded See 6 8 Current Limitations Unit does not regulate closely 1 The unit may be slightly overloaded See 6 8 Current Limitations 2 The actual line voltage swings may be outside the rate range of the unit particular...

Page 12: ...I IEEE C62 41 Category A B waveforms formerly IEEE 587 1980 Ambient Temperature Operating 20 C to 50 C Storage 20 C to 85 C Humidity 95 non condensing Directives RoHS complaint Certifications UL 1012 CSA C22 2 No 107 1 Model Certification 23 13 030 2 cULus 23 13 060 2 23 22 112 2 23 23 125 8 23 23 150 8 23 23 220 8 23 23 230 8 23 23 250 8 23 28 275 6 Warranty 10 year limited warranty 9 0 Specifica...

Page 13: ......

Page 14: ...1 800 377 4384 US 1 847 268 6651 International www solahd com P N A272 283 Rev 2 8 16 ...

Page 15: ...Série CVS câblée 60 Hz Manuel d utilisation ...

Page 16: ...ques de l entrée 23 6 8 Limitations du courant 24 6 9 Utilisation avec des charges de moteur 24 7 0 Dépannage et entretien 24 7 1 Dépannage et entretien 24 7 2 Remplacement des condensateurs sur place 24 8 0 Dépannage 24 9 0 Spécifications 25 10 0 Garantie et assistance 25 10 1 Informations relatives à la garantie 25 10 2 Assistance technique 25 Bien que toutes les précautions possibles aient été ...

Page 17: ...mentation en courant alternatif 4 0 Instructions d installation 4 1 Réception Lors de la réception de l unité l inspecter immédiatement pour identifier tout signe de dommages pendant le transport ou de manutention inadéquate Si l appareil est endommagé prendre une photo de la partie endommagée en informer le transporteur et contacter un représentant SolaHD local 4 2 Montage et ventilation Ces appa...

Page 18: ...0 6 4 12 104 6 3 03 77 0 0 31 x 0 69 7 9 x 17 5 28 0 12 7 60 23 23 150 8 13 00 330 2 6 50 165 1 8 12 206 2 9 00 228 6 8 12 206 2 5 62 142 7 3 06 77 7 0 38 x 0 81 9 7 x 20 6 37 0 16 8 60 23 23 210 8 17 25 438 2 6 81 173 0 8 12 206 2 9 00 228 6 8 12 206 2 5 62 142 7 5 25 133 4 0 38 x 0 81 9 7 x 20 6 63 0 28 6 Tableau 3 Dimensions Figure 2 Hz Référence catalogue Dimensions en in mm Poids à l expéditi...

Page 19: ...eau 4 Dimensions Figure 3 Hz Référence catalogue Dimensions en in mm Poids à l expédition lb kg A B C D E F G H 60 23 28 275 6 26 91 683 5 9 27 235 6 23 55 598 2 25 81 655 6 24 81 630 2 6 62 168 1 8 88 225 6 0 44 x 0 69 11 2 x 17 5 365 0 165 6 FIGURE 3 ...

Page 20: ...et X2 23 13 060 2 120 X1 et X2 23 22 112 2 120 X1 et X2 23 28 275 6 120 X1 et X2 OU X3 et X2 240 X1 et X3 Remarque Secondaires ne sont pas ancrées Terrain X2 en vertu du code Tableau 6 Paramètres du produit Référence catalogue VA Sortie en BTU à charge maximale temp ambiante de 40 C 23 13 030 2 30 60 23 13 060 2 60 85 23 22 112 2 120 136 23 28 275 6 7500 2407 Tableau 7 Fusibles et câblage Référenc...

Page 21: ...H1 et H8 Tension secondaire Interconnexion Brancher les câbles à 120 X1 et X2 FIGURE 5 Tableau 10 Fusibles et câblage Référence catalogue Protection exigée du circuit calibre minimal des câbles à 90 C Calibre minimal des câbles à 90 C Tension d entrée Tension de sortie 95 130 175 235 190 260 380 520 475 650 120 208 240 23 23 125 8 6 A 14 AWG 3 A 14 AWG 1 A 14 AWG 14 AWG Tableau 9 Paramètres du pro...

Page 22: ...nimal des câbles à 90 C Calibre minimal des câbles à 90 C Tension d entrée Tension de sortie 95 130 175 235 190 260 380 520 475 650 120 208 240 23 23 150 8 10 A 14 AWG 6 A 14 AWG 6 A 14 AWG 3 A 14 AWG 14 AWG 23 23 210 8 15 A 14 AWG 10 A 14 AWG 10 A 14 AWG 6 A 14 AWG 14 AWG 23 23 220 8 30 A 10 AWG 20 A 12 AWG 15 A 14 AWG 10 A 14 AWG 10 AWG 14 AWG 23 23 230 8 45 A 8 AWG 25 A 10 AWG 25 A 10 AWG 15 A ...

Page 23: ...tionneurs d alimentation ferrorésonants ayant la même référence SolaHD Les entrées doivent être branchées en triangle Les fusibles de l entrée doivent être branchés dans la ligne primaire de chaque appareil et non pas dans les lignes triphasées Les sorties doivent être branchées en étoile le conducteur neutre solidement raccordé à une charge en étoile Ces trois sorties peuvent également alimenter ...

Page 24: ...oscillation se produit lorsque la demande en courant d alimentation de découpage s arrête Étant donné sa faible portée et sa rareté elle ne doit causer aucune inquiétude Des tests ont été effectués sur les deux gammes d appareils avec diverses alimentations de découpage Il en a été déduit que la suroscillation n affecte pas les sorties de courant continu et n endommage aucun composant de l aliment...

Page 25: ...cteur de puissance de la charge est en avance capacitif Tension nominale trop faible 1 Le facteur puissance de charge est en retard inductif 2 L appareil est légèrement en surcharge Consulter la section 6 8 Limitations du courant La régulation n est pas assez précise 1 L appareil est légèrement en surcharge Consulter la section 6 8 Limitations du courant 2 Les écarts de tension de la ligne se situ...

Page 26: ...me à la norme ANSI IEEE C62 41 relative aux ondes de catégorie A et B auparav IEEE 587 1980 Température ambiante Fonctionnement de 20 C à 50 C stockage de 20 C à 85 C Humidité 95 sans condensation Directives Conformité avec la directive RoHS Certifications UL 1012 CSA C22 2 n 107 1 Modèle Certification 23 13 030 2 cULus 23 13 060 2 23 22 112 2 23 23 125 8 23 23 150 8 23 23 220 8 23 23 230 8 23 23 ...

Page 27: ......

Page 28: ...1 800 377 4384 É U 1 847 268 6651 international www solahd com P N A272 283 Rev 2 8 16 ...

Reviews: