72
SI-DeviceNet User Guide
Issue Number: 2
12.1.5 Mapping Status
If the DeviceNet Network Diagnostic parameter (Pr
S.01.006
) indicates "Init Failed", a
mapping configuration error has been could have been detected. The reason for the
error is indicated by the SI-DeviceNet input mapping status parameter (Pr
S.01.022
)
and the SI-DeviceNet output mapping status parameter (Pr
S.01.023
).
When a mapping error has been corrected, reset the SI-DeviceNet module by setting
Pr
S.01.002
or MM.007 to On (1).
The mapping error codes are described in Table 12.5.
Table 12.5 Mapping error codes
12.1.6 Alarms
If the SI-DeviceNet detects an alarm during operation, it will cause the drive to display
the appropriate alarm on the drive keypad. If more than one alarm is present, it will be
shown as “first-in-first-out” (FIFO) order.
Value
Text
Description
0
No error
No error has been detected during mapping initialisation
1
Par impossible
The parameter may not exist or may not be readable
2
Hole in mapping
Cyclic data mapping parameters are not contiguous
3
Dup mapping
Two or more cyclic data mapping configuration
parameters have been configured with the same
destination parameter reference
4
Length exceed
The length of the mapped parameters exceeds the length
of the selected assembly object
5
Obj not support
The selected assembly object is not supported
6
Pre &
uncompress
If the predefined object is selected, the data alignment
must be set to 16 bits
7
Type unmatched
The IN and OUT objects both must be predefined objects,
or neither
8
Memory fault
Failed to allocate memory for mapping
9
No mapping
No parameter is assigned to the mapping
10
Reserved
Reserved
Value
Text
Description
0
No alarm
No alarm.
1
User Prog
A user program alarm has been generated.
2
eCMP
An eCMP alarm has been generated.
3
FS Usage
A file system alarm has been generated.
4
Too Hot
Module temperature is too high.
5
In Mapping
Error with Input mapping setup.
6
Out Mapping Error with Output mapping setup.
7
Fbus Init
Fieldbus Initialization failed, possibly due to external 24 V
missing or baud rate detection failed.
8
Read Err
Error during reading from a mapped parameter.
9
Write Err
Error during writing to a mapped parameter.