background image

SAG581126000

 

System Application Guide 

Issue AD, November 23, 2009 

Spec. No. 581126000 (Model 700

NVBA

 

Page 14 of 123 

 

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 

Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 

Notes: 

1)  Circuit breakers, fuses, and lugs should be specified for each distribution panel.  Unless otherwise 

specified, circuit breakers are plug-in bullet nose style and fuses are TPS/TLS style with plug-in fuse 
block. 

2)  Distribution panels are limited to 500A for single-row panels (except 960A for List ND), and 1000A for 

double-row panels.  Maximum cabinet capacity is 2000A. 

Home

Summary of Contents for SAG581126000

Page 1: ...fferent sizes of Distribution Cabinets may be ordered to accept from one 1 to four 4 Distribution Bus Panel assemblies A variety of Distribution Bus Panel assemblies are available that provide combinations of load distribution battery distribution low voltage load or battery disconnect manual battery disconnect and dual voltage load distribution for use with 48V converters The Distribution Cabinet...

Page 2: ...ed for 960A Rectifier Module PCU 87 7A 28 5VDC to 104 2A 24 0VDC 2500 Watts Converter Module 31 Amperes 1500W Agency Approval UL 1801 Listed c UL NEBS pending Framework Type Relay Rack Mounting Width 23 Inches nominal Mounting Depth Distribution Cabinet 18 Inches single bay 21 Inches multi bay List RC RD and RE adds 5 25 inches to back of system see Overall Dimensions Illustrations Module Mounting...

Page 3: ...n WinLink Compatible Web Interface SNMP MCA Interface Ethernet Option WinLink Compatible Web Interface Battery Monitoring MCA Interface Ethernet Option WinLink Compatible Web Interface SNMP Battery Monitoring Battery Stand System Battery Tray Pre Cabled Distribution Panels Accessories Options Relay Racks Transition Plates Distribution Devices Wiring Components Module Mounting Position Blank Cover ...

Page 4: ...Other Options List 29 Distribution Cabinet Top Shield List 31 Field Expansion Kit One 1 8 Position Module Mounting Assembly List 71 Optional Audible Alarm and Alarm Termination Circuit Card List 72 MCA Interface Modem Option List 73 MCA Interface WinLink Software List 74 MCA Interface Combination Modem RS 232 Option List 75 MCA Interface Ethernet Option WinLink Compatible Web Interface List 76 MCA...

Page 5: ...22 Two Row Distribution Cabinet 21 List 23 Three Row Distribution Cabinet 22 List 24 Four Row Distribution Cabinet 22 List 29 Top Shield for Distribution Cabinet 23 List 30 Module Mounting Assembly Interface Components 23 List 31 Field Expansion Kit One 1 8 Position Module Mounting Assembly 24 List 50 Rectifier Module PCU 25 List 60 DC DC Converter Option Interface Component Kit 25 List 62 DC DC C...

Page 6: ...ule P N 509852 16 Fuse Circuit Breaker System Positions and 4 Fuse Circuit Breaker Battery Disconnect Positions 52 List GB Distribution Bus Module P N 513806 8 Fuse Circuit Breaker System Positions w LVD and 1 TPH Fuse Battery Disconnect Position 53 List JA Distribution Bus Module Part No 509906 4 24V Fuse Circuit Breaker System Positions and 16 48V Fuse Circuit Breaker Subsystem Positions 54 List...

Page 7: ...its 88 AC Input Branch Circuit Protection and Wire Size Selection 90 Relay Rack Frame Grounding Requirements 90 External Alarm Reference and Control Wire Sizes 90 Module Mounting Position Blank Cover Panel P N 540959 91 Battery Charge Temperature Compensation Probe for Single Probe Digital Compensation P Ns 107021 and 106824 91 Battery Charge Temperature Compensation Probe Concentrator for Multipl...

Page 8: ...nc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited External Alarm Reference and Control 120 RELATED DOCUMENTATION 121 BATTERY MANUFACTURER INFORMATION 122 REVISION RECORD 123 ...

Page 9: ...0005 Remote Supplemental Bay Common Equipment Power and Distribution Includes communication cable Requires interbay power cabling Accepts Distribution Cabinet List 21 22 23 or 24 and Module Mounting Assembly Interface List 30 1 2 10 58112600010 MCA Standard Application Configuration No 534876 installed in Main Bay Distribution Cabinet 1 2 11 58112600011 MCA Special Application Configuration No 534...

Page 10: ...face Ethernet Option WinLink Compatible Web Interface SNMP Battery Monitoring 92 58112600092 Battery Stand System 93 58112600093 Battery Tray Pre Cabled As requested Notes 1 This power system must consist of a minimum configuration of 1 List 1 1 List 10 11 12 or 13 1 List 21 22 23 or 24 1 List 30 equipped w List 50 s A maximum of one supplemental bay List 2 or 5 may be added to the system 2 Separa...

Page 11: ... No No AC 581126000AC Distribution 3 GJ 218 Circuit Breaker 24V System Positions row 4 only Single No No AD 581126000AD Distribution 8 GJ 218 Circuit Breaker 24V System Positions rows 3 and 4 C and D Single No No AE 581126000AE Distribution 8 GJ 218 Circuit Breaker 24V System Positions rows 1 and 2 A and B or rows 2 and 3 B and C Single No No AG 581126000AG Distribution 2 TPH Fuse 24V System Posit...

Page 12: ... No CD 581126000CD Distribution 3 LVD Controlled GJ 218 Circuit Breaker 24V System Positions row 4 only Single Yes No CE 581126000CE Distribution 8 LVD Controlled GJ 218 Circuit Breaker 24V System Positions rows 3 and 4 Single Yes No CF 581126000CF Distribution 8 LVD Controlled GJ 218 Circuit Breaker 24V System Positions rows 1 and 2 or rows 2 and 3 Single Yes No CG 581126000CG Distribution 2 LVD ...

Page 13: ...ual No No LB 581126000LB Distribution 8 LVD Controlled 24V System Positions 8 48V Subsystem Positions one per system Dual Yes No LC 581126000LC Distribution 12 LVD Controlled 24V System Positions 4 48V Subsystem Positions one per system Dual Yes No NA 581126000NA Battery Disconnect 20 Bullet Nose Circuit Breaker and or TPS TLS Fuse 24V Battery Disconnect Positions row 1 only Single No Manual NB 58...

Page 14: ... copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Notes 1 Circuit breakers fuses and lugs should be specified for each distribution panel Unless otherwise specified circuit breakers are plug in bullet nose style and fuses are TPS TLS style with plug in fuse block 2 Distribution panels are limited to 500A...

Page 15: ...56 on Top of GNB Absolyte IIP Battery Stands GMT Load Distribution Fuse Block Assembly Kit 10 GMT Fuse Positions GMT Type Load Distribution Fuses Replacement Alarm Reference and Control Fuses TPH Type Fuses GJ 218 Type Circuit Breakers Bullet Nose Type Circuit Breakers and Bullet Nose Type Fuseholders e w TPS TLS Fuses Wiring Components Module Mounting Position Blank Cover Panel Battery Charge Tem...

Page 16: ... Rack P N 543156 on Top of GNB Absolyte IIP Batteries under ACCESSORY DESCRIPTIONS A ship loose option is available as described in Relay Racks under ACCESSORY DESCRIPTIONS 2 Order one 1 List 21 22 23 or 24 Distribution Cabinet 3 Order up to four 4 Distribution Bus Panels as required per Distribution Bus Arrangements and the capacity of the Distribution Cabinet ordered 4 Order one 1 List 10 11 12 ...

Page 17: ...used when List 5 is ordered Order List 2 or List 5 not both Supplemental Bays DO NOT accept Converter Modules DO NOT order List 60 or 62 for Supplemental Bays List 2 Supplemental Bay DOES NOT accept List 21 or 22 Distribution Cabinet List 21 and 22 are not provided with connection points for interbay busbars Rear access is required for installation of inter bay busbars Ordering Notes 1 Order a rel...

Page 18: ...The Module Mounting Assembly can consist of one 1 two 2 three 3 or four 4 factory interconnected 8 position Module Mounting Shelves Each Module Mounting Shelf in a Module Mounting Assembly provides eight 8 mounting positions for Rectifier Modules PCUs or Can be configured for distribution only no Module Mounting Assembly Restrictions Order maximum of one 1 List 2 or List 5 per Power System Cannot ...

Page 19: ...ORY DESCRIPTIONS List 10 MCA Standard Application Features Provides one standard application Meter Control Alarm MCA assembly Configuration No 534876 Refer to SPECIFICATIONS for a description of MCA functions Alarms Major Minor High Voltage 1 High Voltage 2 Battery on Discharge 50 Battery On Discharge AC Fail MCA Audible Test Equalize Mode Restrictions Only one 1 MCA per power system is required M...

Page 20: ... MCA Special Application Features Provides one special application Meter Control Alarm MCA assembly Configuration No 534879 Refer to SPECIFICATIONS for a description of MCA functions Alarms Major Minor Test Equalize 2 Fuse Circuit Breaker Battery on Discharge 50 Battery On Discharge AC Fail Low Voltage Disconnect Test Equalize 1 Restrictions Only one 1 MCA per power system is required Mounts in th...

Page 21: ...user can set the low voltage disconnect circuits for either automatic or manual reconnect Automatic Reconnect When system bus voltage recovers to a preset adjustable value the low voltage disconnect circuits automatically reconnect the loads or battery to the system bus Manual Reconnect When system bus voltage has recovered to a preset adjustable value the user must issue a command via the MCA to ...

Page 22: ...n List 1 List 2 and List 5 bays See also the description of the Quad Shunt circuit card under List 21 features See also the description of the Low Voltage Disconnect circuit card under List 21 features Ordering Notes 1 Order up to three 3 Distribution Bus Panels for each List 23 per Distribution Bus Arrangements 2 Order fuses and or circuit breakers as required per Distribution Devices under ACCES...

Page 23: ...fier Modules PCUs or 24V 48V DC DC Converter Modules Note that Supplemental Bays CANNOT have Converter Modules Refer to Power Data Sheet PD588705100 PD588705101 PD588705102 PD588705103 PD588705104 for Module Mounting Assembly information Restrictions Factory installed only on the Distribution Cabinet Includes Module Mounting Assembly to Power System Distribution Cabinet interconnect components onl...

Page 24: ... Modules PCUs or 24V 48V DC DC Converter Modules Note that Supplemental Bays CANNOT have Converter Modules Refer to Power Data Sheet PD588705100 for more information Restrictions For field installation only Maximum number of List 31 that can be installed in a power bay is one 1 Original system must have a Module Mounting Assembly up to twenty four 24 positions Cannot be used in a power bay equippe...

Page 25: ...ill accept DC DC Converters or Rectifier Modules PCUs Includes cables for connection of converter output to a dual voltage bus distribution panel assembly Restrictions MUST be factory installed only CANNOT be used in Supplemental Bays Must be used in conjunction with a dual voltage bus distribution panel assembly List JA JB JC JD KA LB or LC Up to two 2 converter kits can be used with a List JA JB...

Page 26: ...nverter Modules when equipped with a DC DC Converter Option Kit List 71 Optional Audible Alarm and Alarm Termination Circuit Card Features Provides an Audible Alarm and Alarm Termination circuit card P N 509539 This circuit card is interconnected to the MCA and via relays on the circuit card to external converter major and minor alarm circuits if converters are furnished The circuit card provides ...

Page 27: ... 74 RS 232 Modem MCA Interface Option Remote communications can be done via an RS 232 connection when the Power System is equipped with the 6List 74 RS 232 Modem MCA Interface Option Remote communications can be done via a TCP IP connection when the Power System is equipped with the Ethernet MCA Interface Option List 75 76 77 or 78 With WinLink Software most tasks accomplished via the Power System...

Page 28: ...EB Interface 2 Order optional Front Access Ethernet Connector Kit P N 525110 as required This includes an RJ45 connector mounting bracket and jumper that mounts in the cutout provided on the front of the MCA Panel 3 WinLink Software List 73 will operate with List 75 but is not required Internal WEB Pages are preferred List 76 MCA Interface Ethernet Option WinLink Compatible Web Interface SNMP Feat...

Page 29: ...EB Interface 2 Order optional Front Access Ethernet Connector Kit P N 525110 as required This includes an RJ45 connector mounting bracket and jumper that mounts in the cutout provided on the front of the MCA Panel 3 WinLink Software List 73 will operate with List 77 but is not required Internal WEB Pages are preferred List 78 MCA Interface Ethernet Option WinLink Compatible Web Interface SNMP Batt...

Page 30: ...t terminal VLRA batteries Batteries are configured as two 2 24V strings per tray Battery cabling is factory connected to Power System main bus Accepts various Valve Regulated Lead Acid VLRA batteries See Ordering Notes below Tray dimensions are 21 3 wide X 22 4 deep See List 93 Battery Tray under PHYSICAL SIZE INFORMATION for a typical battery tray arrangement Trays can be ordered with or without ...

Page 31: ...119 Northstar NSB170FT 167 4 92 x 22 05 x 12 60 8U 131 See Battery Manufacturer Information located at the end of this document 3 Specify rack spacing of 7U 12 25 or 8U 14 between trays and above top tray as required for battery clearance See table above 4 Specify the batteries you intend to use with each List 93 ordered Lugs for battery connections vary according to the batteries to be installed ...

Page 32: ...d 6 An assembly for connection of all List 93 is automatically added to the order Part number depends on system configuration 7 If ordering List 93 with circuit breakers order two 2 circuit breakers per List 93 from the following table Part Number Ampere Rating Electrical Mechanical Trip1 Black Handle Electrical Trip2 White Handle 50 256694300 256694400 60 256694700 256694800 70 256695100 25669520...

Page 33: ...to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Maximum size of wire to be connecte...

Page 34: ...Circuit Breaker Mounting Positions 100 to 600A GJ 218 Type NOTE RESTRICTIONS Restrictions Can be installed in bus positions A C row 1 3 of a 1 2 3 or 4 bus row cabinet Cannot be installed in bus position D row 4 of a 4 bus row cabinet See also List AC for similar application in bus position D row 4 Panel is designed to mount circuit breakers in the following possible combinations 3 100A to 250A 1 ...

Page 35: ...Capacity 3 Load Distribution Circuit Breaker Mounting Positions 100 to 600A GJ 218 Type NOTE RESTRICTIONS Restrictions For use in a 4 bus row cabinet only Must be installed in bus position D row 4 See also List AB for similar application in bus positions A C rows 1 3 Panel is designed to mount circuit breakers in the following possible combinations 3 100A to 250A 1 100A to 250A and 1 300A or 400A ...

Page 36: ...n rows For use in a 4 bus row cabinet only Must be installed in bus positions C and D rows 3 and 4 See also List AE for similar application in bus positions A and B rows 1 and 3 or B and C rows 2 and 3 Panel is designed to mount circuit breakers in the following possible combinations per side 4 100A to 250A 2 100A to 250A and 1 300A or 400A 2 300A or 400A 1 600A and 1 100A to 250A Unless otherwise...

Page 37: ... rows For use in a 2 3 or 4 bus row cabinet Must be installed in bus positions A and B rows 1 and 2 or B and C rows 2 and 3 See also List AD for similar application in bus positions C and D rows 3 and 4 Panel is designed to mount circuit breakers in the following possible combinations per side 4 100A to 250A 2 100A to 250A and 1 300A or 400A 2 300A or 400A 1 600A and 1 100A to 250A Unless otherwis...

Page 38: ...tion Fuse Mounting Positions 70 to 600A TPH Type Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Does not provide connection for load returns see Ordering Notes Ordering Notes 1 To terminate load returns within the distribution cabinet order one 1 List AH for up to two 2 List AG 2 Order fuses as required per Table 4 Order replacement alarm fuses 1 4A p...

Page 39: ...Distribution Bus Module Ground Bar Assembly P N 500676 for Use with Up to 2 List AG AJ CG or CJ Features Single Voltage Distribution 24V 1000A Maximum Capacity Groundbar Assembly for Use with Up to Two 2 List AG AJ CG or CJ if internal load returns are required Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Ordering Notes 1 To terminate load returns w...

Page 40: ...hunt leads are 22 AWG stranded wire approximately 7 10 ft long from exit point at bottom of Distribution Cabinet Each shunt lead is equipped with a 49 9 ohm current limiting resistor Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Does not provide connection for load returns see Ordering Notes Ordering Notes 1 To terminate load returns within the distr...

Page 41: ... restrictions apply if used in conjunction with a List AL See List AL for restrictions Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse w...

Page 42: ... North America Inc is strictly prohibited List AL Distribution Bus Module Ground Bar Assembly for Use with Up to 2 List AK Features Groundbar Assembly for Use with Up to Two 2 List AK when Internal Load Returns are Required 1000A Maximum Capacity Restrictions Can be installed in a 2 or 3 bus row cabinet List 22 or 23 Must be installed in top row Must be installed in the same bus row as a List AK O...

Page 43: ... or 4 bus row cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mountin...

Page 44: ...ed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating greater...

Page 45: ...it breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity Circuit breakers with greater than 100 ampere rating occupy two mounting positions Caution A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Maximum size of wire to be connected t...

Page 46: ...Positions 100 to 600A GJ 218 Type NOTE RESTRICTIONS Low Voltage Load Disconnect Contactor Restrictions Can be installed in any bus position A C row 1 3 of a 1 2 3 or 4 bus row cabinet Cannot be installed in bus position D row 4 of a four bus row cabinet See also List CD for similar application in bus position D row 4 Panel is designed to mount circuit breakers in the following possible combination...

Page 47: ...ribution Circuit Breaker Mounting Positions 100 to 600A GJ 218 Type NOTE RESTRICTIONS Low Voltage Load Disconnect Contactor Restrictions For use in a 4 bus row cabinet only Must be installed in bus position D row 4 See also List CB for similar application in bus positions A C rows 1 3 Panel is designed to mount circuit breakers in the following possible combinations 3 100A to 250A 1 100A to 250A a...

Page 48: ...4 bus row cabinet only Must be installed in bus positions C and D rows 3 and 4 See also List CF for similar application in bus positions A and B rows 1 and 2 Panel is designed to mount circuit breakers in the following possible combinations per side 4 100A to 250A 2 100A to 250A and 1 300A or 400A 2 300A or 400A 1 600A and 1 100A to 250A Unless otherwise specified circuit breakers are divided betw...

Page 49: ...row cabinet Must be installed in bus positions A and B rows 1 and 2 or B and C rows 2 and 3 See also List CE for similar application in bus positions C and D rows 3 and 4 Panel is designed to mount circuit breakers in the following possible combinations per side 4 100A to 250A 2 100A to 250A and 1 300A or 400A 2 300A or 400A 1 600A and 1 100A to 250A Unless otherwise specified circuit breakers are...

Page 50: ...Positions 70 to 600A TPH Type Low Voltage Load Disconnect Contactor Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Does not provide connection for load returns see Ordering Notes Ordering Notes 1 To terminate load returns within the distribution cabinet order one 1 List AH for up to two 2 List CG 2 Order fuses as required per Table 4 Order replacement...

Page 51: ...AWG stranded wire approximately 7 10 ft long from exit point at bottom of Distribution Cabinet Each shunt lead is equipped with a 49 9 ohm current limiting resistor Low Voltage Load Disconnect Contactor Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Does not provide connection for load returns see Ordering Notes Ordering Notes 1 To terminate load retu...

Page 52: ...net in List 1 if used with List 2 Cannot be used in second row of a 3 bus row cabinet in List 2 Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker ...

Page 53: ...y two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Maximum size of wire to be connected to a single TPS TLS type fuseholder or Bullet Nose type circuit breaker position is 2 AWG Ordering Notes 1 Order circu...

Page 54: ...neath that module must be a List AA AE AK AM BA CA CF EA NA NB RA or RB If ordering more than one 1 List 60 List JA must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting ...

Page 55: ...us module is mounted directly beneath that module must be a List AA AE AK AM BA CA CF EA GB NA NB RA or RB If ordering more than one 1 List 60 List JB must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A ci...

Page 56: ...us module is mounted directly beneath that module must be a List AA AE AK AM BA CA CF EA GB NA NB RA or RB If ordering more than one 1 List 60 List JC must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A ci...

Page 57: ...istribution bus module is mounted directly beneath that module must be a List AA AE AK AM BA CA CF EA GB NA NB RA or RB If ordering more than one 1 List 60 List JD must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150...

Page 58: ...t be installed in bus position A row 1 of a 1 2 3 or 4 bus row cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating gre...

Page 59: ...f a distribution bus module is mounted directly beneath that module must be a List AA AE AK AM BA CA CF EA GB NA NB RA or RB If ordering more than one 1 List 60 List LB must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125...

Page 60: ...nted directly beneath that module must be a List AA AE AK AM BA CA CF EA GB NA NB RA or RB If ordering more than one 1 List 60 List LC must be installed in bus position A row 1 of the distribution cabinet Unless otherwise specified fuses and or circuit breakers are mounted from left to right starting with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers o...

Page 61: ...ng with the highest capacity and working to the lowest capacity 125A 150A and 200A circuit breakers occupy two mounting positions 250A circuit breakers occupy three mounting positions Caution A circuit breaker or fuse with a rating greater than 150 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Maximum size of wire to be connected to a single f...

Page 62: ...itions 100 to 600A GJ 218 Type NOTE RESTRICTIONS Restrictions Limit one bus arrangement of this type per Distribution Cabinet Must be installed in bus position A or B row 1 or 2 of a 1 2 3 or 4 bus row cabinet Cannot be used in second row of a 3 bus row cabinet in List 1 if used with List 2 Cannot be used in second row of a 3 bus row cabinet in List 2 Panel is designed to mount circuit breakers in...

Page 63: ...TPH Fuse Battery Disconnect Position Features Single Voltage Distribution 24V 500A Maximum Capacity 1 Battery Disconnect Fuse Mounting Position 70 to 600A TPH Type Restrictions Can be installed in any bus position A D row 1 4 of a 1 2 3 or 4 bus row cabinet Ordering Notes 1 Order fuses as required per Table 4 Order replacement alarm fuses 1 4A per Table 3 2 Order battery lugs two hole 3 8 bolt cle...

Page 64: ...onnect Positions Features Single Voltage Distribution 24V 960A Maximum Capacity 2 Battery Disconnect Fuse Mounting Positions 70 to 600A TPH Type Restrictions Limit one bus arrangement of this type per Distribution Cabinet Must be installed in bus position A row 1 of a 1 2 3 or 4 bus row cabinet Ordering Notes 1 Order fuses as required per Table 4 Order replacement alarm fuses 1 4A per Table 3 2 Or...

Page 65: ...t P N 540808 Features Provides a battery disconnect contactor which is mounted in bus position A row 1 of the Distribution Cabinet Restrictions Limit one bus arrangement of this type per System Must be installed in bus position A row 1 of a 1 2 3 or 4 bus row cabinet Cannot be used with List 92 93 RB RC RD or RE Ordering Notes 1 Order as required 2 Order battery lugs two hole 3 8 bolt clearance ho...

Page 66: ...trol circuit which is mounted in bus position A row 1 of the Distribution Cabinet Also provides one set of Form C relay contacts for connection to customer external alarms Restrictions Limit one bus arrangement of this type per System Must be installed in bus position A row 1 of a 1 2 3 or 4 bus row cabinet Cannot be used with List 92 93 RA RC RD or RE Ordering Notes 1 Order as required 2 Order ba...

Page 67: ...to six lugs See Electrical Connection Locations and Dimensions Input Battery Connections to Optional Battery Busbar Extension Kit P N 514713 Installed in Lists 21 through 24 Distribution Cabinets under PHYSICAL SIZE INFORMATION for a dimensional drawing Also provides one set of Form C relay contacts for connection to customer external alarms Restrictions Must be installed in Main Bay List 1 only L...

Page 68: ...1 centers Allows back to back lug landing for up to six lugs See Electrical Connection Locations and Dimensions Input Battery Connections to Optional Battery Busbar Extension Kit P N 514713 Installed in Lists 21 through 24 Distribution Cabinets under PHYSICAL SIZE INFORMATION for a dimensional drawing Also provides one set of Form C relay contacts for connection to customer external alarms Restric...

Page 69: ...ws back to back lug landing for up to six lugs See Electrical Connection Locations and Dimensions Input Battery Connections to Optional Battery Busbar Extension Kit P N 514713 Installed in Lists 21 through 24 Distribution Cabinets under PHYSICAL SIZE INFORMATION for a dimensional drawing Also provides one set of Form C relay contacts for connection to customer external alarms Restrictions Same as ...

Page 70: ... brackets can mount a system up to 20U high Ordering Notes 1 Order from relay racks listed in Table 1 Part Number Size Available Mounting Positions 1RU 1 3 4 Notes 543151 25 656 H x 23 W 13RU Welded Notes 1 3 543152 27 406 H x 23 W 14RU Welded Notes 1 3 543153 36 156 H x 23 W 19RU Welded Notes 1 3 543154 39 656 H x 23 W 21RU Welded Notes 1 3 543155 43 156 H x 23 W 23RU Welded Notes 1 3 543156 51 9...

Page 71: ...o mount relay rack P Ns 543151 543152 543153 543154 543155 543156 and 543157 on top of GNB Absolyte IIP Battery Stands Each kit consists of two transition plates with three hole patterns and hardware 3 8 to mount the plates to the above listed relay racks Customer must supply hardware to mount the transition plates to the battery stands Restrictions Used with relay rack P Ns 543151 543152 543153 5...

Page 72: ...e Restrictions 30A maximum capacity Terminal block wire size capacity 24 to 14 AWG Can be used in a List AA AK AM BA CA EA GB JA JB JC JD KA LB and LC Distribution Bus Module only When factory ordered installation order of the assembly will be from top to bottom and right to left see illustration below for 4 row example unless otherwise specified Ordering Notes 1 Order kit P N 514432 as required P...

Page 73: ...al GMT Load Distribution Fuse Block Assembly Kit see previous section is available for additional load distribution Restrictions When used for power distribution load should not exceed 80 of device rating except 10 and 15 amp fuses for which load should not exceed 70 of device rating Ordering Notes 1 Order fuses as required per Table 2 GMT Fuses Ampere Rating Part Number Fuse Color 18 100 GMT A 24...

Page 74: ...System Voltage Monitoring 1 1 3 Bussmann GMT 248610700 F3 Fuse Alarm 1 1 3 Bussmann GMT 248610700 F4 LVD Side A 1 1 3 Bussmann GMT 248610700 F5 LVD Side B 1 1 3 Bussmann GMT 248610700 F6 Converter Fail Alarm Relays List 71 only 1 1 3 Bussmann GMT 248610700 F7 Not Used 5 Bussmann GMT 248611000 F8 Sense Voltage 1 1 3 Bussmann GMT 248610700 F9 Battery Stand Shunt POD Circuit Card 1 1 3 Bussmann GMT 2...

Page 75: ... the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited TPH Type Fuses Restrictions A bus arrangement must be specified that contains a TPH type fuseholder Load should not exceed 80 of device rating Ordering Notes 1 Order fuses as required per Table 4 TPH Fuses TPH Fuse Ampere Rating Part Number for wire size and lug selection refer to the following...

Page 76: ...reakers Ampere Rating Number of Positions P N Electrical Mechanical Trip1 without Internal Shunt P N Electrical Trip2 without Internal Shunt P N Electrical Trip2 with Internal Shunt 25mV full rated load 3 P N Electrical Mechanical Trip1 with Internal Shunt 25mV full rated load 3 for wire size and lug selection refer to the following table 100 1 256621700 256621300 516184 123580 125 1 256621600 256...

Page 77: ...ritten permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Breaker Ampere Rating Distribution Bus Module List No Breaker Jumper Kit P N Order 1 of the following kits for each circuit breaker W O an internal shunt Breaker Jumper Kit P N Order 1 of the following kits for each circuit breaker WITH an internal shunt 100A 250A AB AC AD AE CB CD CE CF NB 503787 51...

Page 78: ...let Nose type distribution positions This fuseholder provides a GMT A alarm type fuse which operates open to provide an alarm indication if the associated distribution fuse opens Restrictions Load should not exceed 80 of device rating Install distribution devices from left to right starting with the highest capacity and working to the lowest capacity Caution A circuit breaker with a rating greater...

Page 79: ...k Handle for wire size and lug selection refer to the following table 1 1 102272 101596 3 1 102273 101597 5 1 102274 101598 10 1 102275 101599 15 1 102276 101600 20 1 102277 101601 25 1 102278 101602 30 1 102279 101603 35 1 102280 101604 40 1 102281 101605 45 1 121998 121997 50 1 102282 101606 60 1 102283 101607 70 1 102284 101608 75 1 102285 101609 80 1 121996 121995 100 1 102286 101610 125 2 516...

Page 80: ...mpere Rating Part Number Bussmann P N Littelfuse P N for wire size and lug selection refer to the following table 3 248230900 TPS 3 TLS003 5 248231000 TPS 5 TLS005 6 248231200 TPS 6 TLS006 10 248231500 TPS 10 TLS010 15 248231800 TPS 15 TLS015 20 248232100 TPS 20 TLS020 25 248232400 TPS 25 TLS025 30 248232700 TPS 30 TLS030 40 248233300 TPS 40 TLS040 50 248233900 TPS 50 TLS050 60 248234200 TPS 60 TL...

Page 81: ...on Bus Modules Using GJ 218 Circuit Breakers or TPH Fuses are Provided Lug terminated load leads are connected to the individual load busbars located on the Distribution Bus Module and the respective distribution ground busbar The individual load busbars provide 3 8 16 captive nuts for installation of customer provided two hole lugs that have 1 inch centers and 3 8 inch bolt clearance holes Custom...

Page 82: ...or TPH Fuses are Provided Lug terminated input battery leads are connected to the individual battery busbars located on the Distribution Bus Module and the respective battery return busbar Battery Load Side The individual input battery busbars provide 3 8 16 captive nuts for installation of customer provided two hole lugs that have 1 inch centers and 3 8 inch bolt clearance holes Refer to the illu...

Page 83: ...ut battery busbars and associated battery return busbar are designed to accommodate the lugs listed in Table 10 Use Table 13 to select recommended battery wire sizes and lugs for various loop lengths per battery disconnect fuse circuit breaker ampere rating 2 When Distribution Bus Modules with Battery Disconnect Fuse Circuit Breaker Positions are NOT Provided Battery wire size and lug requirements...

Page 84: ...wer Energy Systems North America Inc is strictly prohibited Standard Crimp Lug Tables Lead Size Part Number 14 10 AWG 245342300 8 AWG 245390200 6 AWG 245346700 4 AWG 245346800 2 AWG 245346900 Table 9 Crimp Lug Two Hole 1 4 Bolt Clearance Hole 5 8 Centers Lead Size Part Number 6 AWG 245349900 4 AWG 245350000 2 AWG 245348200 1 0 AWG 245347100 2 0 AWG 245347200 3 0 AWG 245347300 4 0 AWG 245347400 250...

Page 85: ...and provides a crimp type lug which allows distribution wiring up to 350 kcmil size maximum size of wire to be connected to a single position is 2 AWG Designed for use with 125 ampere and larger bullet nose type circuit breakers or TPS TLS type fuses which require at least two mounting positions Restrictions If used with bullet nose type circuit breakers or TPS TLS type fuses smaller than 125 ampe...

Page 86: ...4 118 3 4 Recommended Crimp Lug 5 Lug 245342300 245342300 245342300 245390200 245346700 245346800 245346900 245393500 6 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For...

Page 87: ...e NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For other operating ambient temperatures refer to the NEC For operation in countries where the NEC is not recognized follow applicable codes 2 Recommended wire sizes are sufficient to restrict voltage drop to 1 0 volt or less at listed branch current for the loop lengths shown Loop leng...

Page 88: ...49900 245350000 245348200 245347100 245347200 245347300 245347400 245347500 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For other operating ambient temperatures refer ...

Page 89: ...00 per cable 245347600 per cable 245347700 per cable 245347800 per cable 245347900 per cable 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C and 40 C was used For other operating ambient te...

Page 90: ... top of each relay rack Provision is made for installing a lead with a two hole lug that has 1 4 bolt clearance holes on 5 8 centers Refer to Table 9 for lug selection External Alarm Reference and Control Wire Sizes Features External alarm reference and control connection points are located on J1 J4 on the optional List 71 Audible Alarm and Alarm Termination Circuit Card P N 509539 TB1 on circuit ...

Page 91: ...d Two probes are available P N 107021 has a 25 foot long cord P N 106824 has a 100 foot long cord See Overall Dimensions Optional Digital Battery Charge Temperature Compensation Probe P N 107021 and 106824 under PHYSICAL SIZE INFORMATION for a dimensional drawing Refer to PD588705100 PD588705101 PD588705102 PD588705103 PD588705104 for complete specifications Ordering Notes 1 Order one Battery Char...

Page 92: ...ures Provides busbar extension plates and mounting hardware for extending battery busbars through the top of a Distribution Cabinet Each busbar extension plate provides three pairs of clearance holes for 3 8 hardware on 1 centers Allows back to back lug landing for up to six lugs per polarity See Electrical Connection Locations and Dimensions Input Battery Connections to Optional Battery Busbar Ex...

Page 93: ... of a 125 200A bullet nose circuit breaker and provides a landing for one standard two hole lug having 3 8 bolt clearance holes on 1 centers Also includes one 1 busbar that mounts on two landings of the system ground return bar and provides one landing for a standard two hole lug having 3 8 bolt clearance Holes on 1 centers All busbar and lug mounting hardware is included Ordering Notes 1 Order 1 ...

Page 94: ...14912 Features Designed for field installation in a bullet nose type distribution bus assembly where the LVD function is no longer required Each kit provides a busbar designed to bypass one 1 low voltage disconnect contactor in a List BA CA GB LB or LC Restrictions Kit P N 514910 may be installed with power applied to system Kit P N 514912 must be installed with power removed from system Ordering ...

Page 95: ...tween the Module Mounting Shelf Interface circuit card P N 535250 located in the Bay Distribution Cabinet and the Interconnect Inhibit circuit card located in the same Distribution Cabinet Bay Internal Rectifier Module Control Interconnect Cable P N 529120 Provides pre assembled cable and mating connectors for connecting the Bay Module Mounting Shelf Interface circuit card to the top most Module M...

Page 96: ...nnect Cable A 7 1 2 ft cable is provided with List 2 For a replacement cable order P N 514335 A 25 ft cable is provided with List 5 For a replacement cable order P N 100575 Provides pre assembled cable and mating connectors for Rectifier Module control signal interconnection between the MCA in the Main Bay and Module Mounting Shelves located in the Supplemental Bay Connects between J8 J9 or J10 on...

Page 97: ... P N 535250 Cable P N 509071 Interconnect LVD Inhibit Circuit Card P N 509532 External Alarm Cable P N 514327 Connects Here if List 71 not installed on MCA Main Controller Circuit Card P N 534868 Cable P N 514335 or 100575 Cable P N 514334 or 100916 Connect Cable P N 529120 between pigtail on Circuit Card P N 535250 and connector inside Module Mounting Shelf Interconnect LVD Inhibit Circuit Card P...

Page 98: ...st 62 MCA MCA Main Controller Circuit Card MCA Keypad Display Circuit Card MCA Power Supply Circuit Card 534868 with 534876 Configuration List 10 Standard Configuration 534868 with 534877 Configuration List 11 Special Application Configuration 534868 with 534878 Configuration List 12 Special Application Configuration 534868 with 534879 Configuration List 13 Special Application Configuration 288710...

Page 99: ...tions to Spec Nos 588705100 588705101 588705102 588705103 and 588705104 Module Mounting Assemblies 4 Addition of a Module Mounting Assembly in the field For all other conditions required minimum spacing from the rear of the bay to a wall or other solid surface is that which is specified for proper Module Mounting Assembly ventilation Refer to the specific Module Mounting Assembly Power Data Sheet ...

Page 100: ...e The MCA turns off its display and PCU communications to conserve power when system voltage falls below 20 volts Full operation is restored when system voltage recovers to 23 5 volts The display and communications can be temporarily reactivated by the user 1 3 4 MCA Meter Accuracy 0 01 V 0 005 C 1 3 5 MCA Universal Adjustment Circuit Provides single point control of float output voltage test equa...

Page 101: ...it in volts DC Adjustable from float up to 29 25 volts DC but automatically limited to 0 5 volt below the High Voltage Shutdown setting Factory set as follows Power System List No 10 11 12 13 MCA Configuration No 534876 534877 534878 534879 Factory Setting Volts 28 25 28 25 28 25 28 25 c The minimum voltage limit in volts DC Adjustable from float down to 23 volts DC but automatically limited to 0 ...

Page 102: ... 534879 Factory Setting Volts 23 00 22 00 23 00 23 00 H System Load Current Alarm Adjustable from 0 to 60 000 amperes Factory set at 2 000 amperes unless otherwise specified I Subsystem High Voltage Alarm if subsystem installed Adjustable from 0 00 to 60 00 volts DC Factory set as follows unless otherwise specified Power System List No 10 11 12 13 MCA Configuration No 534876 534877 534878 534879 F...

Page 103: ...herwise specified R Relay Test Seconds Adjustable from 5 to 120 seconds in one second intervals Factory set at 45 seconds unless otherwise specified 1 3 6 MCA Audible Alarm Cutoff List 10 and List 11 MCA only An audible alarm can be connected to the MCA that sounds when any alarm condition monitored by the MCA occurs The alarm can be manually silenced cut off by pressing a local pushbutton A local...

Page 104: ...ocation NAME Description Type FUNCTION SELECT UP and DOWN Pushbutton Switches FUNCTION SET ENTER Pushbutton Switch FUNCTION SET YES and NO Pushbutton Switches MCA ALARM CUTOFF Pushbutton Switch 1 3 9 Local Status and Alarm Indicators Refer to the System Operating Procedures chapter in the Power System User Instructions Section 6013 for a complete description Location NAME Description Type Rectifie...

Page 105: ... Normal Configuration Menu Measurements Adjustment Menu Function Adjustable Settings Alarms Calibration Menu 22 LVD ACTIVATED 23 24 MAIN ALARM MENU 25 NORMAL DISPLAY Local Lockout On 9 ARE YOU SURE 9 RECONNECT LVD 29 MCA BOARD FAIL 1 30 A D INPUT FUSE 5 31 NO SYSTEM VOLTS 1 32 NO SUBSYS VOLTS 1 33 NO SENSE VOLTS 2 SENSE VOLT ERROR 2 34 SHUNT NO REPLY 2 SHUNT BAD TYPE 2 34A BAT CL INHIBITED 2 35 LV...

Page 106: ...E MENU 132 NORMAL DISPLAY 118 PCU TYPE A NO PCUs FOUND PCU TYPE 119 VACANT A A PLACES 120 SHUNT TYPE SYS SHUNT TYPE SUB SHUNT TYPE BAT NO SHUNTS FOUND 121 LVD INSTALLED NO LVDs FOUND 121A 122 SUBSYS INSTALLED NO SUBSYS FOUND 123 REMOTE INSTALLED REMOTE ACTIVE NO REMOTE FOUND 124 UPDATE INVENTORY PLEASE WAIT REPLACE PCUs 125 CONFIGURE MENU 126 NORMAL DISPLAY 127 SPEC NO 128 MCA SWV 129 REM SWV ANAL...

Page 107: ...hapters of the Power System User Instructions Section 6013 for alarm conditions Additional descriptions are provided in a and b below a MCA Audible Alarm These contacts change state if any alarm condition monitored by the MCA occurs and are provided for connection to an audible alarm circuit b Test Equalize Indication These contacts change state if the system is placed in the test equalize mode lo...

Page 108: ...fier Modules operate in the float mode when the signal is absent B External System Voltage Meter Reading Leads can be extended from the Power System to an external voltage source This is the voltage source the MCA monitors for system alarms and displays as System Output Voltage C External Voltage Sensing Leads can be extended from the Power System to the point at which output voltage is to regulat...

Page 109: ...is strictly prohibited PHYSICAL SIZE INFORMATION Overall Dimensions Refer to PD588705100 PD588705101 PD588705102 PD588705103 PD588705104 for Module Mounting Assembly dimensions List 24 Four Bus Row Cabinet Left Side View Front View Right Side View Notes 1 All dimensions are in inches unless otherwise specified 2 Weight in LBS minus relay rack Four Bus Row Cabinet Net Shipping 3 Finish Textured Gra...

Page 110: ...ritten permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 23 Three Bus Row Cabinet Left Side View Front View Right Side View Top View 26 25 15U 24 75 typical Note 4 11 50 6 00 17 50 5 25 Note 4 15 44 Note 4 Notes 1 All dimensions are in inches unless otherwise specified 2 Weight in LBS minus relay rack Four Bus Row Cabinet Net Shipping 3 Finish Texture...

Page 111: ...written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 22 Two Bus Row Cabinet Left Side View Front View Right Side View Top View 19 25 11U 24 75 typical Note 4 15 44 Note 4 11 50 6 00 17 50 5 25 Note 4 Notes 1 All dimensions are in inches unless otherwise specified 2 Weight in LBS minus relay rack Four Bus Row Cabinet Net Shipping 3 Finish Textured...

Page 112: ...ica Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 21 One Bus Row Cabinet Left Side View Front View Right Side View Top View Notes 1 All dimensions are in inches unless otherwise specified 2 Weight in LBS minus relay rack One Bus Row Cabinet Net Shipping 3 Finish Textured Gray M500 147 11 ...

Page 113: ...c Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited List 93 Battery Tray Notes Three trays shown as example Max available per rack four Dimensions are in inches Net Weight Per Tray Less Batteries With Circuit Breaker Option 35 lbs Without Circuit Breaker Option 29 lbs 1 2 3 FRONT VIEW 12 25 or 14 00 a...

Page 114: ...en permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Optional Digital Battery Charge Temperature Compensation Probe P N 107021 and 106824 2 25 57 15 0 75 19 05 0 35 8 89 300 7 620 or 1200 30 480 0 75 19 05 3 00 76 2 0 25 6 35 DIA Note All dimensions are in inches and millimeters Part No 107021 25 foot Part No 106824 100 foot Optional Analog Battery Tempera...

Page 115: ...ensions Input Battery Connections to Lists 21 through 24 Distribution Cabinets Note Battery busbars within distribution cabinets are rated for 2000A max For 2000A 4000A in List 2 make additional battery connections to inter bay busbars 2 000 2 000 1 000 0 625 0 625 0 750 0 625 0 625 0 750 0 625 Central Office Ground 0 750 FRONT VIEW TOP OF DISTRIBUTION CABINET BATTERY RETURN SIDE BUSBAR BATTERY LO...

Page 116: ...n Network Power Energy Systems North America Inc is strictly prohibited Connections to Optional Battery Busbar Extension Kit P N 514713 Installed in Lists 21 through 24 Distribution Cabinets Note See Battery Busbar Extension Kit P N 514713 under ACCESSORY DESCRIPTIONS for description 2 000 2 000 1 000 3 8 CLEARANCE HOLES 12 PLACES CUSTOMER MUST SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE BOLT LENGTH ...

Page 117: ...etwork Power Energy Systems North America Inc is strictly prohibited Connections to Optional Battery Busbar Extension Kit P N 529143 Installed in Lists 21 through 24 Distribution Cabinets Note See Battery Busbar Extension Kit P N 529143 under ACCESSORY DESCRIPTIONS for description 1 312 1 000 3 8 CLEARANCE HOLES 24 PLACES CUSTOMER MUST SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE BOLT LENGTH 1 1 4 FRO...

Page 118: ...ictly prohibited Connections to Inter bay Busbars P O List 2 Note Battery busbars within distribution cabinets are rated for 2000A max For 2000A 4000A in List 2 make battery connections to inter bay busbars shown here DETAIL A 1 2 3 8 2 3 8 2 3 8 5 8 3 4 3 4 3 4 1 5 8 1 5 8 3 8 16 CAPTIVE NUT 8 PLACES PER BUS CUSTOMER MUST PROVIDE LUG BOLTS AND ADDITIONAL HARDWARE BOLT LENGTH 1 1 4 1 4 20 CAPTIVE ...

Page 119: ...rson Network Power Energy Systems North America Inc is strictly prohibited Connections to Battery Disconnect Circuit Breakers and Low Battery Voltage Disconnect Options Refer to the illustrations located under the Bus Module and Low Battery Voltage Disconnect List descriptions in this document Load Distribution Refer to the illustrations located under the Bus Module List descriptions in this docum...

Page 120: ...l Alarm Reference and Control External alarm reference and control connection points are located on J1 J4 on the optional List 71 Audible Alarm and Alarm Termination Circuit Card P N 509539 TB1 on circuit card P N 509532 and J8 on circuit card P N 534868 if List 71 not installed MCA MAIN CONTROLLER CIRCUIT CARD P N 534868 MAIN BAY ONLY ALARM TERMINATION AUDIBLE ALARM CIRCUIT CARD P N 509539 LIST 7...

Page 121: ... Module Mounting Assemblies SD540827 1 Row Distribution Cabinet SD540828 2 Row Distribution Cabinet SD540829 3 Row Distribution Cabinet SD540830 4 Row Distribution Cabinet Wiring Diagrams T581126000 NETSURE Power System T588705100 T588705101 T588705102 T588705103 T588705104 Module Mounting Assemblies T540827 1 Row Distribution Cabinet T540828 2 Row Distribution Cabinet T540829 3 Row Distribution C...

Page 122: ...ORMATION Some equipment described in this System Application Guide is designed to accommodate batteries from various manufacturers The following are referenced in this document C D C D Technologies Inc Powercom Div 1400 Union Meeting Road Blue Bell PA 19422 0858 Deka East Penn Mfg Co Inc Lyon Station PA 19536 0147 Douglas Douglas Battery Mfg Co 500 Battery Dr Winston Salem NC 27117 2159 Fiamm FIAM...

Page 123: ...CO Description of Change Date Approved AA LLP210771 New 06 30 08 John Jasko AB LLP211402 List 93 Battery Tray spacing changed from 7U to 8U for P N 122018 battery Misc Updates 09 30 08 John Jasko AC LLP212882 Fan Failure statement added for NEBS 09 28 09 John Jasko AD LLP212840 List 92 Battery Stand System added 11 23 09 John Jasko Emerson Network Power Energy Systems North America Inc 1122 F Stre...

Reviews: